Post on 08-Nov-2018
Desde1963
Proveedor Integral de Soluciones para
la Industria
INTERRUPTORES Y SENSORES DE PRESION Y
TEMPERATURA
INTERRUPTORES Y SENSORES DE PRESION Y TEMPERATURA
Los interruptores ASCO Tripoint, utilizan la tecnología de diafragma/pistón para un sensado preciso de presión y temperatura, garantizado un excelente tiempo de vida. Los materiales de fabricación son diversos y dependen de fluido a manejar.
Los SENSORES ASCO son maquinados en una sola pieza (cuerpo y diafragma) para eliminar los problemas ocasionados por el desgaste de partes internas, garantizando así el tiempo más largo del mercado.
Sensores ASCO
Interruptores ASCO TRIPOINT
ASCO® Pressure and Temperature SwitchSELECTION GUIDE and INDEX
PRESSURE
J-SERIES Miniature Pressure Switches with Non-Adjustable Set Points
H-SERIES Miniature Pressure Switches with Adjustable Set Points
P-SERIES Switches for Vacuum - 6000 psig with Open Frame, Type 1 or Type 4 Enclosures
TEMPERATURE
P-SERIES Switches for -60 through 510°F with Open Frame, Type 1 or Type 4 Enclosures
S-SERIES Switches for -60 through 640° F with Type 1, Type 4 or Type 7, 9 Enclosures
Options, Definitions and Compatibility Table.........Pages 34 through Inside Back Cover
S-SERIES Switches for Vacuum - 8000 psig, or Differential with Type 1, Type 4 or Type 7, 9 Enclosures
Switches Type Set Point Reset Point Enclosure Ranges Pages
Pressure Non-Adjustable Fixed Sealed 6.5 - 162(psig)
2 - 3
Pressure Adjustable Fixed,Adjustable
Open Frame,General Purpose,
Watertight
4 - 200(psig)
4 - 7
Temperature Adjustable Fixed,Adjustable
Open Frame,General Purpose,
Watertight-60 - 510°F 24 - 29
Temperature AdjustableFixed,
Adjustable,Manual Reset
General Purpose,Watertight,
Explosion-Proof-60 - 640°F 30 - 33
Vacuum,Compound,
PressureAdjustable Fixed,
Adjustable
Open Frame,General Purpose,
Watertight
Vacuum - 6000(psig)
8 - 13
Pressure,Vacuum,
Differential,CombustionIn. of W.C.
AdjustableFixed,
Adjustable,Manual Reset
General Purpose,Watertight,
Explosion-Proof
Vacuum - 8000(psig)
14 - 23
1
2
J-SERIES Miniature Pressure Switches
Features:• Tamperproof, factory-set, non-adjustable set points.• Fixed deadband.• Environmentally sealed against dust, water, oil and
salt spray, e.g., for off-highway equipment.• Vented construction for stable set points throughout
operating range.• Vibration and shock resistant to 10 G’s.• Precision electrical snap-action switch.
General Description:J-Series miniature pressure switches have factory-setnon-adjustable set points and fixed deadband, withdiaphragm/piston sensor. J-Series switches are CSAapproved and UL listed under “Industrial ControlEquipment”. J-Series switches are sealed with speciallycompounded epoxy that maintains its sealing integrityfrom -40 to 250°F.
Proof pressure:250 psig. (Consult factory for higher pressures).
Process connection:Standard: 1/8” NPT Ext, 1/8” NPT Int, 1/4” NPT Ext.Optional: 1/4” NPT Int (eighth digit “3”).
Standard Electrical Ratings
Low-Cost Switches with Non-Adjustable Set Points
5 Amp Res., 125 VAC5 Amp Res., 250 VAC3 Amp Res., 28 VDC %
Standard Temperature Ratings
Ambient: -4°F (-20°C) to 140°F (60°C)Fluid: -4°F (-20°C) to 180°F (82°C)
Wetted Materials (Process Connection & Diaphragm)
Standard: Brass and Buna “N”Optional Process Connections:
• 316 SS (sixth digit “4”)• Carbon steel (sixth digit “6”)
Optional Diaphragms:
• Neoprene (seventh digit “3”)• Ethylene propylene (seventh digit “6”)• Fluorosilicone (seventh digit “7”)
&
Dimensions (inches)
18
1 INCHDIA.
3.5
1/8 NPT INTERNAL,1/8 NPT EXTERNAL OR1/4 EXTERNAL
1 INCHDIA.
4
J-Series Pressure
With TerminalScrew Connections
With Lead Wires
Switch Options
Gold contacts for low power circuits: Add Suffix “P”Tight deadband, 25-50% reduction: Add Suffix “T”11 Amp Res., 125 VAC contacts: Add Suffix “Y”
• FKM (seventh digit “2”)
3
4 123
How to Select and OrderASCO J-Series switches are asingle switch and transducerassembly.
How to Select1. Select type of switch (normally open,normally closed or SPDT and screwterminal or wire leads).2. Select desired set point for eitherdecreasing pressure or increasingpressure.3. Select desired process connection.
How to OrderSimply order the selected J-Seriespressure switch by catalog number,e.g., JB67A218A describes a normallyopen, screw terminal pressure switchwith set point decreasing of 6.5 psigand set point increasing of 8.5 psig,1/8” NPT external brass processconnection and Buna “N” diaphragm.
OptionsAdd appropriate suffix or changeappropriate digit in catalog numberfor desired option, e.g., JB67A2 2 8A Pdescribes a normally open, screwterminal pressure switch with optional
gold contact snap switch (suffix “P”).
Normally open, screw terminals, Brass and Buna “N”
Normally open, 18” lead wires, Brass and Buna “N”
Normally closed, screw terminals, Brass and Buna “N”
Normally closed, 18” lead wires, Brass and Buna “N”
SPDT (Form “C” contact), 18” lead wires, Brass and Buna “N”
IncreasingPressure
(psig)
DecreasingPressure
(psig)
1/8” NPTInternal Process
Connection
1/4” NPTExternal Process
Connection
1/8” NPTExternal Process
Connection
Catalog No.Catalog No.Catalog No.
Mfg. SetPoint
Tolerance(psig)
3
6.510.518.5
3040567193138
6.510.518.5
3040567193138
6.510.518.5
3040567193138
6.510.518.5
3040567193138
6.510.518.5
3040567193138
8.512.52235456585
108162
8.512.52235456585
108162
8.512.52235456585
108162
8.512.52235456585
108162
8.512.52235456585
108162
1.21.5234678
12
1.21.5234678
12
1.21.5234678
12
1.21.5234678
12
1.21.5234678
12
JB67A218AJB57A218AJB47A218AJB37A218AJB27A218AJB17A218AJC37A218AJC27A218AJC17A218A
JB68A218AJB58A218AJB48A218AJB38A218AJB28A218AJB18A218AJC38A218AJC28A218AJC18A218A
JB67A218BJB57A218BJB47A218BJB37A218BJB27A218BJB17A218BJC37A218BJC27A218BJC17A218B
JB68A218BJB58A218BJB48A218BJB38A218BJB28A218BJB18A218BJC38A218BJC28A218BJC18A218B
JB68A218CJB58A218CJB48A218CJB38A218CJB28A218CJB18A218CJC38A218CJC28A218CJC18A218C
JB67A214AJB57A214AJB47A214AJB37A214AJB27A214AJB17A214AJC37A214AJC27A214AJC17A214A
JB68A214AJB58A214AJB48A214AJB38A214AJB28A214AJB18A214AJC38A214AJC28A214AJC18A214A
JB67A214BJB57A214BJB47A214BJB37A214BJB27A214BJB17A214BJC37A214BJC27A214BJC17A214B
JB68A214BJB58A214BJB48A214BJB38A214BJB28A214BJB18A214BJC38A214BJC28A214BJC18A214B
JB68A214CJB58A214CJB48A214CJB38A214CJB28A214CJB18A214CJC38A214CJC28A214CJC18A214C
JB67A215AJB57A215AJB47A215AJB37A215AJB27A215AJB17A215AJC37A215AJC27A215AJC17A215A
JB68A215AJB58A215AJB48A215AJB38A215AJB28A215AJB18A215AJC38A215AJC28A215AJC18A215A
JB67A215BJB57A215BJB47A215BJB37A215BJB27A215BJB17A215BJC37A215BJC27A215BJC17A215B
JB68A215BJB58A215BJB48A215BJB38A215BJB28A215BJB18A215BJC38A215BJC28A215BJC18A215B
JB68A215CJB58A215CJB48A215CJB38A215CJB28A215CJB18A215CJC38A215CJC28A215CJC18A215C
Values shown are nominal.1
Deadband value is difference between the increasing and decreasing set points.2
May be used for panel or bracket mounting.3
Select J-Series pressure switch belowSet Point 1 2
FKM diaphragm (seventh digit “2”) and
4
H-SERIES Miniature Pressure Switches
Features:• Field adjustable set points.• Fixed deadband.• Choice of open frame type, general purpose or
watetight enclosure.• Small size.• Mounts in any position.• Rugged and vibration resistant, e.g., for compressors.• Visual adjustment scales in psig and bars.
General Description:H-Series miniature pressure switches have fieldadjustable set points and fixed deadband, withdiaphragm/piston sensor. They are available in openframe construction, Type 1 general purpose or Type 4watertight enclosures. The resilient diaphragm/pistonconstruction helps provide long life and maintains setpoint repeatability despite environmental temperaturevariations. The full size electical switch is a precision ULlisted, snap-action type. H-Series switches areCSA approved and are UL listed under “IndustrialControl Equipment”.
Proof pressure:250 psig. (Consult factory for higher pressures).
Process connection:Standard: 1/8” NPT Ext, 1/8” NPT Int, 1/4” NPT Ext.Optional: 1/4” NPT Int (eighth digit “3”).
Low-Cost Switches with Adjustable Set Points
Standard Temperature Ratings
Ambient: -4°F (-20°C) to 140°F (60°C)Fluid: -4°F (-20°C) to 180°F (82°C)
Wetted Materials (Process Connection & Diaphragm)
Standard: Brass and Buna “N”Optional Process Connections:
• 316 SS (sixth digit “4”)• Carbon steel (sixth digit “6”)
Optional Diaphragms:
• Neoprene (seventh digit “3”)• Ethylene propylene (seventh digit “6”)• Fluorosilicone (seventh digit “7”)
Switch Options
See page 34 for optional snap switches.
Standard Electrical Ratings
15 Amp Res., 125 VAC10 Amp Res., 250 VAC1/8 HP, 125 VAC1/4 HP, 250 VAC1/2 Amp Res., 125 VDC1/4 Amp Res., 250 VDC
^ %
SPDTNO
NC
C
Open frame construction, UL recognized component.1
1 • FKM (seventh digit “2”)
Values shown are nominal.1 May be used for panel or bracket mounting.2
5
4 123
Dimensions (inches)
1/8 NPT INTERNAL 1/8 NPT EXTERNAL OR1/4 EXTERNAL
1/8 NPT INTERNAL
1/2NPT4.0
.8
3.5
.9
2.2 2.8
5.0
2.11.7
2.51.0
5.2
7/8KNOCKOUTBOTHSIDES
1/8 NPT INTERNAL 1.0
H-Series Pressure
General Purpose Enclosure
Open Frame Watertight Enclosure
Open frame construction
Type 1 - General purpose enclosure
Type 4 - Watertight enclosure
AdjustableOperating
Range(psig)
1/8” NPTInternal Process
Connection
1/4” NPTExternal Process
Connection
1/8” NPTExternal Process
Connection
Catalog No.Catalog No.Catalog No.
FixedDeadband
AtMid-Range
(psig)
2
SPDT (Form “C” Contact), Brass and Buna “N”
1
4 - 128 - 25
20 - 5035 - 8040 - 12080 - 200
4 - 128 - 25
20 - 5035 - 8040 - 12080 - 200
4 - 128 - 25
20 - 5035 - 8040 - 12080 - 200
1.61.82.43.57.0
10.0
1.61.82.43.57.0
10.0
1.61.82.43.57.0
10.0
HB46A218HB36A218HB26A218HB16A218HC26A218HC16A218
HB40A218HB30A218HB20A218HB10A218HC20A218HC10A218
HB41A218HB31A218HB21A218HB11A218HC21A218HC11A218
HB46A214HB36A214HB26A214HB16A214HC26A214HC16A214
HB40A214HB30A214HB20A214HB10A214HC20A214HC10A214
HB41A214HB31A214HB21A214HB11A214HC21A214HC11A214
HB46A215HB36A215HB26A215HB16A215HC26A215HC16A215
HB40A215HB30A215HB20A215HB10A215HC20A215HC10A215
HB41A215HB31A215HB21A215HB11A215HC21A215HC11A215
How to Select and OrderASCO H-Series switches are a singleswitch and transducer assembly.
How to Select1. Select type of switch (open frame,general purpose or watertight)..2. Select the adjustable operating rangebased on the desired actuation pressure.3. Select desired process connection.
How to OrderSimply order the selected H-Series pressureswitch by catalog number, e.g., HB46A218describes an open frame pressure switchwith adjustable operating range of 4 to 12psig, 1/8” NPT external brass processconnection and Buna “N” diaphragm.
OptionsAdd appropriate suffix or change appropriatedigit in catalog number for desired option, e.g.,HB46A2 2 8 P describes an open frame pres-
switch (suffix “P”).
Select H-Series pressure switch below
(seventh digit “2”) and gold contact snapsure switch with optional FKM diaphragm
6
H-SERIES Miniature Pressure Switches
Features:• Field adjustable set points.• Limited adjustable deadband.• Choice of open frame type, general
purpose or watetight enclosure.• Small size.• Mounts in any position.• Rugged and vibration resistant,
e.g., for compressors.• Visual adjustment scales in psig
and bars.
Standard Ratings andWetted Materials(See page 4)
Dimensions(See page 5)
How to Select and OrderASCO H-Series Suffix S switches are asingle switch and transducer assembly.
How to Select1. Select type of switch enclosure (openframe, general purpose or watertight).2. Select the adjustable operating rangebased on the desired actuation pressure anddesired deadband (reactuation) pressure.3. Select desired process connection.
How to OrderSimply order the selected H-Series Suffix Spressure switch by catalog number,e.g., HB46A218S describes an open frameH-Series Suffix S pressure switch withadjustable operating range of 4 to 12 psigand adjustable deadband at mid-range of 1.5to 3.5 psig, 1/8” NPT external brass processconnection and Buna “N” diaphragm.
Options (See page 4)Change appropriate digit in catalog numberfor desired option, e.g., HB46A2 2 8Sdescribes an open frame pressure switchwith adjustable operating range and deadband
Suffix S: Low-Cost Switches withAdjustable Set Points and Adjustable Deadband
Open frame construction
Type 1 - General purpose enclosure
Type 4 - Watertight enclosure
AdjustableOperating
Range(psig)
1/8” NPTInternal Process
Connection
1/4” NPTExternal Process
Connection
1/8” NPTExternal Process
Connection
Catalog No.Catalog No.Catalog No.
AdjustableDeadband
AtMid-Range
(psig)From/To
2
SPDT (Form “C” Contact), Brass and Buna “N”
1
4 - 128 - 25
20 - 5035 - 8040 - 12080 - 200
4 - 128 - 25
20 - 5035 - 8040 - 12080 - 200
4 - 128 - 25
20 - 5035 - 8040 - 12080 - 200
1.5 - 3.52 - 43 - 56 - 88 - 13
15 - 20
1.5 - 3.52 - 43 - 56 - 88 - 13
15 - 20
1.5 - 3.52 - 43 - 56 - 88 - 13
15 - 20
HB46A218SHB36A218SHB26A218SHB16A218SHC26A218SHC16A218S
HB40A218SHB30A218SHB20A218SHB10A218SHC20A218SHC10A218S
HB41A218SHB31A218SHB21A218SHB11A218SHC21A218SHC11A218S
HB46A214SHB36A214SHB26A214SHB16A214SHC26A214SHC16A214S
HB40A214SHB30A214SHB20A214SHB10A214SHC20A214SHC10A214S
HB41A214SHB31A214SHB21A214SHB11A214SHC21A214SHC11A214S
HB46A215SHB36A215SHB26A215SHB16A215SHC26A215SHC16A215S
HB40A215SHB30A215SHB20A215SHB10A215SHC20A215SHC10A215S
HB41A215SHB31A215SHB21A215SHB11A215SHC21A215SHC11A215S
Values shown are nominal.1 May be used for panel or bracket mounting.2
Select H-Series Suffix S switch below
with optional FKM diaphragm (seventh digit “2”).
7
4 123
Features:• Low cost for OEM applications.• Miniature size.• Wide selection of adjustable ranges.• Fixed deadband.• Resilient diaphragm/piston sensor
for long life.• Precision single-pole, double-throw
snap switch with quick-connect 1/4”spade terminals.
Standard Ratings andWetted Materials(See page 4)
How to Select and OrderASCO H-Series Suffix L switches are asingle switch and transducer assembly.
How to Select1. Select the adjustable operating rangebased on the desired actuation pressure.2. Select desired process connection.
How to OrderSimply order the selected H-Series Suffix Lpressure switch by catalog number,e.g., HB46A218L describes an open framepressure switch with adjustable operatingrange of 4 to 12 psig, 1/8” NPT external brassprocess connection and Buna “N” diaphragm.
Options (See page 4)Change appropriate digit in catalog numberfor desired option, e.g., HB46A2 2 8Ldescribes an open frame pressure switchwith adjustable operating range and optional
Note: Optional snap switches not availableon suffix “L” units.
Suffix L: Lowest-Cost Switches withAdjustable Set Points (Open Frame Construction)
Dimensions (inches)
1.2 2.2
3.4
Select H-Series Suffix L switch below
AdjustableOperating
Range(psig)
1/8” NPTInternal Process
Connection
1/4” NPTExternal Process
Connection
1/8” NPTExternal Process
Connection
Catalog No.Catalog No.Catalog No.
FixedDeadband
AtMid-Range
(psig)
2
SPDT (Form “C” Contact), Brass and Buna “N”
1
4 - 128 - 25
20 - 5035 - 8040 - 12080 - 200
HB46A218LHB36A218LHB26A218LHB16A218LHC26A218LHC16A218L
3.03.65.57.0
14.021.0
HB46A214LHB36A214LHB26A214LHB16A214LHC26A214LHC16A214L
HB46A215LHB36A215LHB26A215LHB16A215LHC26A215LHC16A215L
Values shown are nominal.1 May be used for panel or bracket mounting.2
FKM diaphragm (seventh digit “2”).
8
P-SERIES Pressure Switches
Features:• Set point repeatability, +1% of operating range.• All wiring terminals, adjustments and visual scales
are accessible from the front of the switch.• Choice of open frame type, general purpose or
watertight enclosure.• Choice of fixed, limited-adjustable or full-range
adjustable deadband.• Choice of single or two-stage units.• Compact size.• Mounts in any position.• Rugged and vibration resistant; e.g., for compressors.• Visual adjustment scales in psig and bars.• Wide selection of transducer wetted materials
suitable for air, water, oil or corrosive fluids.• Mix and match switch and transducer components for
increased stock flexibility or to change pressure ranges in field.
General Description:ASCO P-Series pressure switches consist of an openframe or enclosure protected switch unit and atransducer unit. They can be ordered separately for cus-tomer stocking and/or field assembly or as acomplete factory-assembled unit.
SwitchP-Series pressure switch units incorporate the uniqueASCO TRI-POINT alternating fulcrum balance plate tocontrol the operation of one or more electrical snap-action swtiches. The electrical snap-action switchtogether with the adjusting mechanism is a fully-tested,self-contained subassembly.
TransducerTransducer unit incorporates a diaphragm/piston type pressure sensor, and is also a fully-tested, self-contained subassembly.
OperationWhen pressure is applied to the transducer it is converted into movement of the piston. This pistonmovement is then used to control the operation of the electrical snap-action switch in the switch unit.
Options (See pages 34-35)
Standard Electrical Ratings
Switches for Vacuum through 6000 psig withAdjustable Set Points and Fixed or Adjustable Deadband
Standard Temperature Ratings
Ambient: -4°F (-20°C) to 122°F (50°C)Fluid: For Buna “N” or Neoprene Diaphragm
-4°F (-20°C) to 180°F (82°C)
-4°F (-20°C) to 250°F (121°C)For 316 SS Diaphragm-50°F (-45°C) to 300°F (149°C)For Nylon Transducers-4°F (-20°C) to 180°F (82°C)
PA, PB, PC Series15 Amp Res., 125 VAC10 Amp Res., 250 VAC1/8 HP, 125 VAC1/4 HP, 250 VAC1/2 Amp Res., 125 VDC1/4 Amp Res., 250 VDC
PG Series15 Amp Res., 125 VAC10 Amp Res., 250 VAC1/8 HP, 125 VAC1/4 HP, 250 VAC
^ %
SPDTNO
NC
C
PC Series, UL recognized component, rated10 Amp Res., 125/250 VAC; 1/3 HP 125/250 VAC.Open frame construction, UL recognized component.FM listed for air flow interlocking service.
1
23
1
#
2
3
For FKM Diaphragm
9
4 123
EnclosuresASCO TRI-POINT switches are available in either ageneral purpose or watertight enclosure, in addition toopen frame construction. These enclosed units aremade in accordance with NEMA and UL standards.These standards define the protection level an enclosure gives and the tests it must pass to meet a particular design.
General Purpose – Type 1. These enclosures aredesigned for indoor use to protect personnel fromaccidental contact with the equipment. P-Series general purpose enclosures are painted, zinc-coated
steel and have a 7/8” diameter hole at the top for electrical entry.
Watertight – Type 4. Watertight and dust-tight enclosures are intended for use indoors and outdoorsto protect the enclosed equipment against splashing orfalling water, windblown dust and water, hose directedwater, and severe external condensation. P-Serieswatertight switch enclosures are epoxy-painted, zinc-coated steel with a 1/2” conduit hub in the side of thelower housing for electrical entry. (For optional 316 SSwatertight enclosure see page 13.)
Dimensions (inches)
5.5
4.9
1.52.7 1.8
.08
.3
2.5
5.2
5.7 4.6
1.5
2.5
1/4 OR1/2 NPT
.233 DIA HOLESFOR MOUNTINGWITH #10 (.190 DIA.)SCREWS (2 PLACES)
1.8
2.7
1/4 OR1/2 NPT
1.82.5
.08
.3
.233 DIA HOLES FORMOUNTING WITH #10(.190 DIA.) SCREWS (2 PLACES)
2.61.8
.5
1.5
.9
.7
5.7
6.2
1.32.8
2.9
1/4 OR1/2 NPT
4.94.5
2.5
1.8.08
.4
.8
.233 DIA.HOLES FORMOUNTINGWITH #10(.190 DIA.)SCREWS(2 PLACES)
2.5
1/4 OR1/2 NPT
4.0.3
.081.8
2.0
5.2
5.2
.08
5.4
2.03.280 DIA.HOLES (2 PLACES)
.233 DIA. HOLES FOR MOUNTINGWITH #10 (.190 DIA.) SCREWS (2 PLACES)
1/2 NPTCONDUITCONNECTION
1.8
4.0
ADDITIONAL SPACING REQUIREDFOR REMOVAL OF COVER
7/8 DIA. HOLEFOR 1/2 CONDUITCONNECTION
.223 DIA. HOLESFOR MOUNTINGWITH #10 (.190 DIA.)SCREWS (2 PLACES)
.233 DIA. HOLES FORMOUNTING WITH #10(.190 DIA.) SCREWS (2 PLACES)
2.5
P-Series Pressure (Mounting brackets optional)
Open Frame PA and PC Switch Unitswith Transducer Unit
Open Frame PB and PG Switch Unitswith Transducer Unit
Type 1 General Purpose Switch Unitwith Transducer Unit
Type 4 Watertight Switch Unitwith Transducer Unit
How to Select and OrderASCO P-Series switches consist of two components, the switch unit and the transducer unit.
How to Select1. Select the adjustable operating range based on desired actuation pressure.2. Check that proof pressure is sufficient.3. Read across and select the desired P-Series switch unit with the proper enclosure.4. Continue across and select a matching transducer unit compatible with the fluid.
10 11
Two-Stage Fixed Deadband Transducer Units
P-SERIES Pressure Switches
Single-Stage Adjustable Deadbandunits allow independent adjustment of theset and reset points over the full operatingrange of the switch. Theminimum differencebetween set and resetpoints is the deadbandlisted below; the maximum differenceis the full range ofthe switch .
Single-Stage Fixed Deadband units have an adjustable set point and a non-adjustable automatic reset point.
PB Switch UnitPA Switch Unit PC Switch Unit
Open Frame Open Frame
Select P-Series pressure switch
Specifications Adjustable Deadband Fixed Deadband
All switch units above are in stock for immediate delivery.
Values shown are nominal.1
All switch units and transducer units above are in stock for immediate delivery.
AdjustableOperating
Range(psig)
ProofPressure
(psig)Catalog
No.
OpenFrame
GeneralPurpose
WatertightEnclosure
OpenFrame
GeneralPurpose
WatertightEnclosure
OpenFrame
GeneralPurpose
WatertightEnclosure
CatalogNo.
CatalogNo.
FixedDeadband
AtMid-Range
(psig) 1
FixedDeadband
AtMid-Range
(psig) 1
Minimum AtMid-Range
(psig)
Separation
MaximumFull Scale
1
Minimum AtMid-Range
(In W.C.)
AdjustableDeadband
MaximumFull Scale
1
CatalogNo.
CatalogNo.
CatalogNo.
CatalogNo.
CatalogNo.
CatalogNo.
50
50
606060
100150150200400450500
20002000500050009000
0 - 30” Hg
30”Hg - 14 psig
4” Hg
6” Hg
---1.21.82.54.05.491827365490250300650
1” Hg
1” Hg
0.050.40.40.60.70.91.53.05.06
1215
100125200
2.7” Hg
4.3” Hg
---0.60.81.22.02.448
12163040
200250400
3” Hg
6” Hg
---1.01.81.83.66.01020304060
100300400600
PA36A
PA26A
---PA36APA26APA36APA26APA16APA16APA16APA16APA16APA26APA16APA26APA16APA16A
PA30A
PA20A
---PA30APA20APA30APA20APA10APA10APA10APA10APA10APA20APA10APA20APA10APA10A
PA31B
PA21B
---PA31BPA21BPA31BPA21BPA11BPA11BPA11BPA11BPA11BPA21BPA11BPA21BPA11BPA11B
PC36A
PC26A
---PC36APC26APC36APC26APC16APC16APC16APC16APC16APC26APC16APC26APC16APC16A
PC30A
PC20A
---PC30APC20APC30APC20APC10APC10APC10APC10APC10APC20APC10APC20APC10APC10A
PC31B
PC21B
--PC31BPC21BPC31BPC21BPC11BPC11BPC11BPC11BPC11BPC21BPC11BPC21BPC11BPC11B
PB36A
PB26A
PB46APB36APB26APB36APB26APB16APB16APB16APB16APB16APB26APB16APB26APB16APB16A
PB30A
PB20A
PB40APB30APB20APB30APB20APB10APB10APB10APB10APB10APB20APB10APB20APB10APB10A
PB31B
PB21B
PB41BPB31BPB21BPB31BPB21BPB11BPB11BPB11BPB11BPB11BPB21BPB11BPB21BPB11BPB11B
CatalogNo.
Aluminum &Buna “N”
Brass &Buna “N”
All316 SS
Corrosive Fluids
CatalogNo.
CatalogNo.
316 SS &Viton
CatalogNo.
RV34A11
RV24A11
RD40A11RD30A11RD20A11
---RE20A11RE10A11RF10A11RG10A11RH10A11RJ10A11
---------------
CatalogNo.
Nylon &Buna “N”
Air, Oil orGas
Water, Air,Oil or Gas
Air or Gas
---
---
RD40A71RD30A71RD20A71
---RE20A71RE10A71RF10A71RG10A71
---------------------
RV34A21
RV24A21
RD40A21RD30A21RD20A21
---RE20A21RE10A21RF10A21RG10A21RH10A21RJ10A21RL20A21RL10A21RN20B21RN10B21
---
---
---
---------
RE30A44RE20A44RE10A44RF10A44RG10A44RH10A44RJ10A44
---------------
RV34A32
RV24A32
RD40A42RD30A42RD20A42
---RE20A42RE10A42RF10A42RG10A42RH10A42RJ10A42RL20A42RL10A42RN20B42RN10B42RQ10B42
Two-Stage Fixed Deadband units consist of twoseparate snap-action switches, each with anindependently adjustable set point and non-adjustablereset point. The difference betweenthe set and reset points of eachswitch is the deadband listed below;the minimum difference betweenthe set points of the two switches isthe separation.
Open Frame
Select transducer unit below
These guage pressure type transducers provide for onepressure connection in the bottom of the transducer. Theyare diaphragm/piston type transducers using an elastomerin contact with the fluid, backed by a piston cylinder. Thisallows high sensitivity for low pressures and strength forhigh pressures.
4 123
0 - 40 - 92 - 182 - 184 - 366 - 60
10 - 10020 - 20030 - 30040 - 40060 - 600
100 - 1000160 - 1650270 - 2700600 - 6000
Vacuum
Compound
Pressure
Rated proof pressure on RF10A71 is 150 psig and on RG10A71 is 300 psig.2 316 SS transducer deadbands are approx. 50% greater than listed.3 Transducers ending in 32 have 303 SS process connections, not 316 SS.4
Transducer Unit
Standard connection is 1/4” NPT(optional 1/2” NPT add suffix “B” to catalog number)
How to OrderFactory assembled – Simply order the switch andtransducer unit by catalog number joined by a slash (/), e.g., PA36A/RD30A11.Field assembled – Simply order the switch andtransducer units separately by individual catalognumber, e.g., one PA36A and one RD30A11.Options – Add appropriate suffix for desired optionor accessory (see pages 34-35).Important Note: The third digit of each of the catalognumbers must be identical,e.g., PA 3 6A and RD 3 0A11.
Watertight Enclosure
General Purpose Enclosure
43
2
PA, PB, or PC unit below
How to Select and OrderASCO P-Series switches consist of two components, the switch unit and the transducer unit.
How to Select1. Select the adjustable operating range based on desired actuation pressure.2. Check that proof pressure is sufficient.3. Read across and select the desired P-Series switch unit with the proper enclosure.4. Continue across and select a matching transducer unit compatible with the fluid.
10 11
Two-Stage Fixed Deadband Transducer Units
P-SERIES Pressure Switches
Single-Stage Adjustable Deadbandunits allow independent adjustment of theset and reset points over the full operatingrange of the switch. Theminimum differencebetween set and resetpoints is the deadbandlisted below; the maximum differenceis the full range ofthe switch .
Single-Stage Fixed Deadband units have an adjustable set point and a non-adjustable automatic reset point.
PB Switch UnitPA Switch Unit PC Switch Unit
Open Frame Open Frame
Select P-Series pressure switch
Specifications Adjustable Deadband Fixed Deadband
All switch units above are in stock for immediate delivery.
Values shown are nominal.1
All switch units and transducer units above are in stock for immediate delivery.
AdjustableOperating
Range(psig)
ProofPressure
(psig)Catalog
No.
OpenFrame
GeneralPurpose
WatertightEnclosure
OpenFrame
GeneralPurpose
WatertightEnclosure
OpenFrame
GeneralPurpose
WatertightEnclosure
CatalogNo.
CatalogNo.
FixedDeadband
AtMid-Range
(psig) 1
FixedDeadband
AtMid-Range
(psig) 1
Minimum AtMid-Range
(psig)
Separation
MaximumFull Scale
1
Minimum AtMid-Range
(In W.C.)
AdjustableDeadband
MaximumFull Scale
1
CatalogNo.
CatalogNo.
CatalogNo.
CatalogNo.
CatalogNo.
CatalogNo.
50
50
606060
100150150200400450500
20002000500050009000
0 - 30” Hg
30”Hg - 14 psig
4” Hg
6” Hg
---1.21.82.54.05.491827365490250300650
1” Hg
1” Hg
0.050.40.40.60.70.91.53.05.06
1215
100125200
2.7” Hg
4.3” Hg
---0.60.81.22.02.448
12163040
200250400
3” Hg
6” Hg
---1.01.81.83.66.01020304060
100300400600
PA36A
PA26A
---PA36APA26APA36APA26APA16APA16APA16APA16APA16APA26APA16APA26APA16APA16A
PA30A
PA20A
---PA30APA20APA30APA20APA10APA10APA10APA10APA10APA20APA10APA20APA10APA10A
PA31B
PA21B
---PA31BPA21BPA31BPA21BPA11BPA11BPA11BPA11BPA11BPA21BPA11BPA21BPA11BPA11B
PC36A
PC26A
---PC36APC26APC36APC26APC16APC16APC16APC16APC16APC26APC16APC26APC16APC16A
PC30A
PC20A
---PC30APC20APC30APC20APC10APC10APC10APC10APC10APC20APC10APC20APC10APC10A
PC31B
PC21B
--PC31BPC21BPC31BPC21BPC11BPC11BPC11BPC11BPC11BPC21BPC11BPC21BPC11BPC11B
PB36A
PB26A
PB46APB36APB26APB36APB26APB16APB16APB16APB16APB16APB26APB16APB26APB16APB16A
PB30A
PB20A
PB40APB30APB20APB30APB20APB10APB10APB10APB10APB10APB20APB10APB20APB10APB10A
PB31B
PB21B
PB41BPB31BPB21BPB31BPB21BPB11BPB11BPB11BPB11BPB11BPB21BPB11BPB21BPB11BPB11B
CatalogNo.
Aluminum &Buna “N”
Brass &Buna “N”
All316 SS
Corrosive Fluids
CatalogNo.
CatalogNo.
316 SS &
CatalogNo.
RV34A11
RV24A11
RD40A11RD30A11RD20A11
---RE20A11RE10A11RF10A11RG10A11RH10A11RJ10A11
---------------
CatalogNo.
Nylon &Buna “N”
Air, Oil orGas
Water, Air,Oil or Gas
Air or Gas
---
---
RD40A71RD30A71RD20A71
---RE20A71RE10A71RF10A71RG10A71
---------------------
RV34A21
RV24A21
RD40A21RD30A21RD20A21
---RE20A21RE10A21RF10A21RG10A21RH10A21RJ10A21RL20A21RL10A21RN20B21RN10B21
---
---
---
---------
RE30A44RE20A44RE10A44RF10A44RG10A44RH10A44RJ10A44
---------------
RV34A32
RV24A32
RD40A42RD30A42RD20A42
---RE20A42RE10A42RF10A42RG10A42RH10A42RJ10A42RL20A42RL10A42RN20B42RN10B42RQ10B42
Two-Stage Fixed Deadband units consist of twoseparate snap-action switches, each with anindependently adjustable set point and non-adjustablereset point. The difference betweenthe set and reset points of eachswitch is the deadband listed below;the minimum difference betweenthe set points of the two switches isthe separation.
Open Frame
Select transducer unit below
These guage pressure type transducers provide for onepressure connection in the bottom of the transducer. Theyare diaphragm/piston type transducers using an elastomerin contact with the fluid, backed by a piston cylinder. Thisallows high sensitivity for low pressures and strength forhigh pressures.
4 123
0 - 40 - 92 - 182 - 184 - 366 - 60
10 - 10020 - 20030 - 30040 - 40060 - 600
100 - 1000160 - 1650270 - 2700600 - 6000
Vacuum
Compound
Pressure
Rated proof pressure on RF10A71 is 150 psig and on RG10A71 is 300 psig.2 316 SS transducer deadbands are approx. 50% greater than listed.3 Transducers ending in 32 have 303 SS process connections, not 316 SS.4
Transducer Unit
Standard connection is 1/4” NPT(optional 1/2” NPT add suffix “B” to catalog number)
How to OrderFactory assembled – Simply order the switch andtransducer unit by catalog number joined by a slash (/), e.g., PA36A/RD30A11.Field assembled – Simply order the switch andtransducer units separately by individual catalognumber, e.g., one PA36A and one RD30A11.Options – Add appropriate suffix for desired optionor accessory (see pages 34-35).Important Note: The third digit of each of the catalognumbers must be identical,e.g., PA 3 6A and RD 3 0A11.
Watertight Enclosure
General Purpose Enclosure
43
2
PA, PB, or PC unit below
FKM
12
P-SERIES Pressure Switches
How to Select1. Select the adjustable operating range basedon desired actuation pressure.2. Check that rated proof pressure is sufficient.3. Read across and select the desiredP-Series switch unit with the proper enclosure.4. Continue across and select a matchingtransducer unit compatible with the fluid.
How to Select and OrderASCO P-Series switches consist of two components, the switch unit and the transducer unit.
How to OrderFactory assembled – Simply order the switch and transducer unit bycatalog number joined by a slash (/), e.g., PG36A/RV34A11.Field assembled – Simply order the switch and transducer units separatelyby individual catalog number, e.g., one PG36A and one RV34A11.Options – Add appropriate suffix for desired option (see pages 34-35).Important Note: The third digit of each of the catalog numbers must beidentical, e.g., PG 3 6A and RV 3 4A11.
Limited Adjustable Deadband unitshave an adjustable set point and usea special snap-action switch thatvaries the deadbandwithin the limitslisted below.
These guage pressure type transducers arediaphragm/piston type transducers using an elastomerin contact with the fluid, backed by a piston cylinder. Thisallows highsensitivity for lowpressures andstrength for highpressures.
Transducer UnitPG Switch Unit
Open Frame
Specifications Limited Adjustable Deadband Transducer Units
All switch units and transducer units above are in stock for immediate delivery.
Values shown are nominal.1
AdjustableOperating
Range(psig)
ProofPressure
(psig)Catalog
No.
OpenFrame
GeneralPurpose
WatertightEnclosure
CatalogNo.
CatalogNo.
50
50
6060
100150150200400450500
20002000500050009000
0 - 30” Hg
30”Hg-14 psig
RV34A11
RV24A11
RD30A11RD20A11
---RE20A11RE10A11RF10A11RG10A11RH10A11RJ10A11
---------------
---
---
RD30A71RD20A71
---RE20A71RE10A71RF10A71RG10A71
---------------------
PG36A
PG26A
PG36APG26APG36APG26APG16APG16APG16APG16APG16APG26APG16APG26APG16APG16A
1.8 - 5.0
2.8 - 6.0
0.7 - 1.30.8 - 2.11.8 - 3.12.0 - 4.02.1 - 4.6
4 - 88 - 17
15 - 2522 - 4535 - 7565 - 110
190 - 290200 - 300300 - 500
PG30A
PG20A
PG30APG20APG30APG20APG10APG10APG10APG10APG10APG20APG10APG20APG10APG10A
PG31B
PG21B
PG31BPG21BPG31BPG21BPG11BPG11BPG11BPG11BPG11BPG21BPG11BPG21BPG11BPG11B
RV34A21
RV24A21
RD30A21RD20A21
---RE20A21RE10A21RF10A21RG10A21RH10A21RJ10A21RL20A21RL10A21RN20B21RN10B21
---
---
---
------
RE30A44RE20A44RE10A44RF10A44RG10A44RH10A44RJ10A44
---------------
RV34A32
RV24A32
RD30A42RD20A42
---RE20A42RE10A42RF10A42RG10A42RH10A42RJ10A42RL20A42RL10A42RN10B42RN10B42RQ10B42
0 - 92 - 182 - 184 - 366 - 60
10 - 10020 - 20030 - 30040 - 40060 - 600
100 - 1000160 - 1650270 - 2700600 - 6000
Vacuum
Compound
Pressure
Rated proof pressure on RF10A71 is 150 psig and on RG10A71 is 300 psig.2
Standard port connection is 1/4” NPT(optional 1/2” NPT add suffix “B” to catalog number)
AdjustableDeadband
AtMid-Range
(psig)From/To
1 CatalogNo.
Aluminum& Buna “N”
Brass &Buna “N”
All316 SS
Corrosive Fluids
CatalogNo.
CatalogNo.
316 SS &
CatalogNo.
CatalogNo.
Nylon &Buna “N”
Air, Oil orGas
Water, Air,Oil or Gas
Air or Gas 2
3 4
316 SS transducer deadbands are approx. 50% greater than listed.3 Transducers ending in 32 have 303 SS process connections, not 316 SS.4
Select P-Series switch unit and transducer unit below
FKM
14
S-SERIES Pressure Switches
Features:• Set point repeatability, +1% of operating range.• All wiring terminals, adjustments and visual scales are
accessible from the front of the switch.• Choice of general purpose, watertight or explosion-
proof enclosures.• Choice of fixed or full-range adjustable deadband.• Choice of single or two-stage units.• Manual reset units available.• Mounts in any position.• Rugged and vibration resistant.• Visual adjustment scales in psi and bars.• External adjusting nuts.• Separate electrical, pressure and adjusting
chambers.• Wide selection of transducer wetted materials suitable for air, water, oil or corrosive fluids.• Mix and match switch and transducer components for
increased stock flexibility or to change pressure ranges in field.
General Description:ASCO S-Series pressure switches consist of a switchunit and a transducer unit. They can be ordered separately for customer stocking and/or field assemblyor as a complete factory-assembled unit.
SwitchS-Series pressure switch units incorporate the uniqueASCO TRI-POINT alternating fulcrum balance plate tocontrol the operation of one or more electrical snap-action swtiches. The electrical snap-action switchtogether with the adjusting mechanism is a fully-tested,self-contained subassembly.
TransducerTransducer unit incorporates a diaphragm/piston type pressure sensor, and is also a fully-tested, self-contained subassembly.
OperationWhen pressure is applied to the transducer it is converted into movement of the piston. This pistonmovement is then used to control the operation of the electrical snap-action switch in the switch unit.
Standard Electrical Ratings
Switches for Pressure to 8000 psig, Vacuum, or Differentialwith General Purpose, Watertight orExplosion-Proof Enclosures
SA, SB, SC, SD and SE Series15 Amp Res., 125 VAC10 Amp Res., 250 VAC1/8 HP, 125 VAC1/4 HP, 250 VAC1/2 Amp Res., 125 VDC1/4 Amp Res., 250 VDC
^ %
SPDTNO
NC
C
Standard Temperature Ratings
Ambient: -4°F (-20°C) to 140°F (60°C)Fluid: For Buna “N” or Neoprene Diaphragm
-4°F (-20°C) to 180°F (82°C)
-4°F (-20°C) to 250°F (121°C)For 316 SS Diaphragm-50°F (-45°C) to 300°F (149°C)
Options (See pages 34-35)
For FKM Diaphragm
13
Every ASCO P-Series pressure switch isavailable in a corrosion-resistant, stainlesssteel enclosure. Typical applicationsinclude:• Offshore platforms• Hydrocarbon processing plants• Oil & gas fields• Oil & gas transmission lines• Chemical plants• Breweries• Paper pulp mills• Salt spray locations
Stainless Steel EnclosureASCO Type 4X watertight enclosure isdesigned to provide protection againstwindblown dust, rain, sleet or external iceformation. The switch and transducer unitare available only as factory-assembledunits, and include a UL-approved 1/2”NPT conduit hub.
How to Select and OrderASCO P-Series switches with 316 SSenclosure consist of two factory-assembledcomponents, the switch unit and thetransducer unit.
How to Select (use tables on pages 10-12)1. Select the adjustable operating range basedon desired actuation pressure.2. Check that rated proof pressure is sufficient.3. Read across and select the desired P-Seriesswitch unit with open frame construction.4. To add a 316 SS enclosure, change the fourthdigit of the open frame catalog number from “6”to “4”, e.g., PG3 6 A becomes PG3 4 A.5. Continue across and select a matchingtransducer unit compatible with the fluid.
How to OrderFactory assembled only – Simply order theswitch and transducer unit by catalog numberjoined by a slash (/), e.g., PG34A/RV34A32.Options – Add appropriate suffix for desiredoption (see pages 34-35).
Dimensions (inches)
4.94.5
1.8 1/2 NPT CONDUITCONNECTION
4.32.3
1.7
5.35
4.0
.41/4 OR1/2 NPT
2.1.27 DIA.2 HOLESFOR MOUNTING NOTE: THIS DIMENSION WILL VARY FROM
5.0 MIN. TO 6.04 MAX. DEPENDING ON TRANSDUCER SPECIFIED.
* MOUNTING BRACKET OPTIONAL
P-Series Pressure with Optional 316 SS Enclosure
Switches with Optional 316 Stainless Steel Enclosure
4 123
4 123
EnclosuresASCO TRI-POINT S-Series switches are available inthree standard enclosures. All of these enclosed unitsare made in accordance with NEMA and UL standards.
General Purpose – Type 1. These enclosures aredesigned for indoor use to protect personnel fromaccidental contact with the equipment. S-Series general purpose switch units consist of a copper-free*aluminum die-cast body with a formed copper-free* aluminum cover; two 3/4” conduit hubs with one plugare provided.
Watertight – Type 4. Watertight and dust-tight enclo-sures are intended for use indoors and outdoors to protect the enclosed equipment against splashing orfalling water, windblown dust and water, hose directedwater, and severe external condensation. S-Serieswatertight switch units have a copper-free* aluminumdie-cast body and a formed copper-free* aluminumcover with Buna “N” gaskets; two 3/4” conduit hubs with one plug are provided.
Explosion-Proof – Types 7 and 9. Type 7 enclosuresare intended for use in locations defined by the NationalElectrical Code as Class I. Type 9 enclosures areintended for Class II locations.
Class I locations are those in which flammable gasesare or may be present in the air in sufficient quantitiesto produce explosive or ignitable mixtures. Class I loca-tions are classified by group letter, which defines partic-ular atmospheres. Division 1 locations are areas wherethe hazardous concentration exists continuously, inter-mittently or periodically under normal operating condi-tions. Division 2 locations are those where the haz-ardous vapors are present only in case of accidentalrupture or breakdown of equipment.
ASCO TRI-POINT explosion-proof enclosures with letter B, C or D in the fifth position are listed for Class I,Groups B, C, and D, Division 1. They are also suitablefor the less stringent Division 2 environment.
Class II locations are those which are hazardousbecause of the presence of combustible dust. All ASCO TRI-POINT explosion-proof enclosures are listed for Groups E, F, and G locations.
The switch body and cover are die-cast copper-free*aluminum with a Buna “N” gasket. Two 3/4” conduithubs with one plug are provided.
Dimensions (inches)
* Less than 0.6% copper.
2.2
4.06
1.03
3.5
3.2
3.7
7.5 1 1.0
4.3 1
1.6 2.32.3
11/32 DIA. FORMOUNTING(2PLACES)
3/4 NPT FORCONDUIT CONN.BOTH ENDS
ADDITIONAL SPACE REQUIREDFOR REMOVAL OF COVER
1/4 OR 1/2 NPT
1 ON TV SERIES ADD 7/16" TO THESE DIMENSIONS3.2
7.0
2.9
1.7
4.1
1.0
7.4
1.6
3.5
2.3
7.0
1.03
1.5
2.2
3.7
1/4 NPT
11/32 DIA. FORMOUNTING(2PLACES)
3/4 NPT FORCONDUIT CONN.BOTH ENDS
ADDITIONAL SPACE REQUIREDFOR REMOVAL OF COVER
1/4 NPT VENT CONNECTION ONDOUBLE CHAMBER TRANSDUCERS
S-Series Pressure
With Types TD - TV Transducers With Types TA - TC Transducers
15
Two-Stage Fixed Deadband Transducer Units
16
S-SERIES Pressure Switches (to 8000 psig)
How to Select1. Select the adjustable operating range based on desired actuation pressure.2. Check that proof pressure is sufficient.3. Read across and select thedesired S-Series switch unit with the proper enclosure.4. Continue across and select a matching transducer unit compatible with the fluid.
How to OrderFactory assembled – Simplyorder the switch and transducerunit by catalog number joined by a slash (/), e.g., SA40D/TA40A11.Field assembled – Simply order the switch and transducerunits separately by individual catalog number, e.g., one SA40D and one TA40A11.
How to Select and OrderASCO S-Series switches consist of two components, the switch unit and the transducer unit.
Single-Stage Adjustable Deadbandunits allow independent adjustment ofthe set and resetpoints over the fulloperating range ofthe switch. Theminimum differencebetween set andreset points is thedeadband listedbelow; the maximumdifference is the fullrange of the switch .
SB Switch Unit: Single-Stage FixedDeadband units have an adjustable set pointand a non-adjustable automatic reset point.SD Switch Unit: Manual reset on decreasingpressure units operate automatically onincreasing pressure and must be reset manually on decreasing pressure.(To order, change second digit to letter “D”,e.g., S B 40D becomes S D 40D).SE Switch Unit: Manual reset on increasingpressure units operate automatically ondecreasing pressure and must be reset manually on increasing pressure.(To order, change second digit to letter “E”,e.g., S B 40D becomes S E 40D).
SA Switch Unit SB, SD or SE Switch Unit SC Switch Unit
General Purpose
Specifications Adjustable Deadband Fixed Deadband or Manual Reset
All switch units above are in stock for immediate delivery.
Values shown are nominal.1
All switch units and transducer units above are in stock for immediate delivery.
316 SS transducers increase deadband by 50%.2 Transducers ending in 32 have 303 SS process connections, not 316 SS.3
AdjustableOperating
Range(psig)
ProofPressure
(psig)
Minimum AtMid-Range
(psig)
AdjustableDeadband
MaximumFull Scale
CatalogNo.
GeneralPurpose
WatertightEnclosure
Explosion-Proof
CatalogNo.
CatalogNo.1
FixedDeadband
AtMid-Range
(psig) 1
FixedDeadband
AtMid-Range
(psig) 1
Minimum AtMid-Range
(psig)
Separation
MaximumFull Scale
1
CatalogNo.
GeneralPurpose
WatertightEnclosure
Explosion-Proof
CatalogNo.
CatalogNo.
CatalogNo.
GeneralPurpose
WatertightEnclosure
Explosion-Proof
CatalogNo.
CatalogNo.
252525404040
100100150100150150150
3000200
30003000400600600900
1500230050009000
0 - 12” W.C.0 - 27” W.C.0 - 65” W.C.
15 - 140” W.C.15 - 250” W.C.25 - 400” W.C.
1.5” W.C.2.0” W.C.2.5” W.C.6” W.C.10” W.C.15” W.C.
0.40.61.41.11.62.23.66.06.010141218243675115225450
1.0” W.C.1.2” W.C.1.4” W.C.3” W.C.6” W.C.8” W.C.
0.30.30.80.41.00.91.54.02.55.06.05.08
10153045
125275
1.2” W.C.1.4” W.C.1.6” W.C.4.0” W.C.7.0” W.C.
13.0” W.C.0.40.41.00.61.21.42.25.53.57.08.57.01014204060
150300
2.4” W.C.2.7” W.C.6.5” W.C.14” W.C.25” W.C.40” W.C.
0.70.91.61.81.83.668
10122020304060
100150350800
SA40DSA30DSA20DSA20DSA10DSA10DSA40DSA30DSA40DSA20DSA30DSA20DSA10DSA30DSA10DSA20DSA10DSA10DSA10DSA10DSA10DSA10DSA10DSA10DSA10D
SA41DSA31DSA21DSA21DSA11DSA11DSA41DSA31DSA41DSA21DSA31DSA21DSA11DSA31DSA11DSA21DSA11DSA11DSA11DSA11DSA11DSA11DSA11DSA11DSA11D
SA42DSA32DSA22DSA22DSA12DSA12DSA42DSA32DSA42DSA22DSA32DSA22DSA12DSA32DSA12DSA22DSA12DSA12DSA12DSA12DSA12DSA12DSA12DSA12DSA12D
SC40DSC30DSC20DSC20DSC10DSC10DSC40DSC30DSC40DSC20DSC30DSC20DSC10DSC30DSC10DSC20DSC10DSC10DSC10DSC10DSC10DSC10DSC10DSC10DSC10D
SC41DSC31DSC21DSC21DSC11DSC11DSC41DSC31DSC41DSC21DSC31DSC21DSC11DSC31DSC11DSC21DSC11DSC11DSC11DSC11DSC11DSC11DSC11DSC11DSC11D
SC42DSC32DSC22DSC22DSC12DSC12DSC42DSC32DSC42DSC22DSC32DSC22DSC12DSC32DSC12DSC22DSC12DSC12DSC12DSC12DSC12DSC12DSC12DSC12DSC12D
SB40DSB30DSB20DSB20DSB10DSB10DSB40DSB30DSB40DSB20DSB30DSB20DSB10DSB30DSB10DSB20DSB10DSB10DSB10DSB10DSB10DSB10DSB10DSB10DSB10D
SB41DSB31DSB21DSB21DSB11DSB11DSB41DSB31DSB41DSB21DSB31DSB21DSB11DSB31DSB11DSB21DSB11DSB11DSB11DSB11DSB11DSB11DSB11DSB11DSB11D
SB42DSB32DSB22DSB22DSB12DSB12DSB42DSB32DSB42DSB22DSB32DSB22DSB12DSB32DSB12DSB22DSB12DSB12DSB12DSB12DSB12DSB12DSB12DSB12DSB12D
CatalogNo.
Brass &Buna “N”
All 316 SS
316 SS &Viton
CatalogNo.
CatalogNo.
------------------
TD40A21TD30A21
---TD20A21
---TE20A21TE10A21
---TF10A21
------
TG10A21TH10A21TJ10A21TK10A21TL10A21TM10A21TN10B21
---
CatalogNo.
Aluminum &Buna “N”
Water, AirOil or Gas Corrosive Fluids
Air, Oilor Gas
TA40A11TA30A11TA20A11TB20A11TB10A11TC10A11TD40A11TD30A11
---TD20A11
---TE20A11TE10A11
---TE10A11
------
TG10A11TH10A11TJ10A11
---------------
------------------------
TE40A44---
TE30A44TE20A44TE10A44
---TF10A44
------
TG10A44TH10A44TJ10A44
---------------
TA40A32TA30A32TA20A32TB20A32TB10A32TC10A32TD40A42TD30A42
---TD20A42
---TE20A42TE10A42TG33A42TF10A42TG23A42TG13A42TG10A42TH10A42TJ10A42TK10A42TL10A42TM10A42TN10B42TQ10B42
0.4 - 4.50.7 - 9.00.8 - 9.01.0 - 181.0 - 181.5 - 36
2 - 605 - 603 - 1005 - 1205 - 2006 - 200
13 - 30015 - 40030 - 60050 - 100075 - 1500
200 - 3500500 - 8000
Two-Stage Fixed Deadbandunits consist of two separate snap-actionswitches, each with an independentlyadjustable set point and non-adjustablereset point. The difference between theset and reset points of each switch is thedeadband listed below; the minimumdifference between the set points of thetwo switches is the separation.
Explosion Proof
Select transducer unit below
Transducer Unit
These guage pressure type transducers provide for one pressure connection in the bottom of thetransducer. They are diaphragm/piston type transducers using an elastomer in contact with thefluid, backed by a piston cylinder. This allows highsensitivity for low pressures and strength for highpressures.
Standard connection is 1/4” NPT; (Optional 1/2” NPTadd suffix “B” to catalog numbers TD thru TQ)
Series TA-TC Series TD-TQ
32
Options – Add appropriate suffix for desired option(see pages 34-35).Important Note: The third digit of each of the catalog numbersmust be identical, e.g., SA 4 0D and TA 4 0A11.
4 123
17
Select S-Series pressure switch SA, SB, SC, SD and SE unit below
Two-Stage Fixed Deadband Transducer Units
16
S-SERIES Pressure Switches (to 8000 psig)
How to Select1. Select the adjustable operating range based on desired actuation pressure.2. Check that proof pressure is sufficient.3. Read across and select thedesired S-Series switch unit with the proper enclosure.4. Continue across and select a matching transducer unit compatible with the fluid.
How to OrderFactory assembled – Simplyorder the switch and transducerunit by catalog number joined by a slash (/), e.g., SA40D/TA40A11.Field assembled – Simply order the switch and transducerunits separately by individual catalog number, e.g., one SA40D and one TA40A11.
How to Select and OrderASCO S-Series switches consist of two components, the switch unit and the transducer unit.
Single-Stage Adjustable Deadbandunits allow independent adjustment ofthe set and resetpoints over the fulloperating range ofthe switch. Theminimum differencebetween set andreset points is thedeadband listedbelow; the maximumdifference is the fullrange of the switch .
SB Switch Unit: Single-Stage FixedDeadband units have an adjustable set pointand a non-adjustable automatic reset point.SD Switch Unit: Manual reset on decreasingpressure units operate automatically onincreasing pressure and must be reset manually on decreasing pressure.(To order, change second digit to letter “D”,e.g., S B 40D becomes S D 40D).SE Switch Unit: Manual reset on increasingpressure units operate automatically ondecreasing pressure and must be reset manually on increasing pressure.(To order, change second digit to letter “E”,e.g., S B 40D becomes S E 40D).
SA Switch Unit SB, SD or SE Switch Unit SC Switch Unit
General Purpose
Specifications Adjustable Deadband Fixed Deadband or Manual Reset
All switch units above are in stock for immediate delivery.
Values shown are nominal.1
All switch units and transducer units above are in stock for immediate delivery.
316 SS transducers increase deadband by 50%.2 Transducers ending in 32 have 303 SS process connections, not 316 SS.3
AdjustableOperating
Range(psig)
ProofPressure
(psig)
Minimum AtMid-Range
(psig)
AdjustableDeadband
MaximumFull Scale
CatalogNo.
GeneralPurpose
WatertightEnclosure
Explosion-Proof
CatalogNo.
CatalogNo.1
FixedDeadband
AtMid-Range
(psig) 1
FixedDeadband
AtMid-Range
(psig) 1
Minimum AtMid-Range
(psig)
Separation
MaximumFull Scale
1
CatalogNo.
GeneralPurpose
WatertightEnclosure
Explosion-Proof
CatalogNo.
CatalogNo.
CatalogNo.
GeneralPurpose
WatertightEnclosure
Explosion-Proof
CatalogNo.
CatalogNo.
252525404040
100100150100150150150
3000200
30003000400600600900
1500230050009000
0 - 12” W.C.0 - 27” W.C.0 - 65” W.C.
15 - 140” W.C.15 - 250” W.C.25 - 400” W.C.
1.5” W.C.2.0” W.C.2.5” W.C.6” W.C.10” W.C.15” W.C.
0.40.61.41.11.62.23.66.06.010141218243675115225450
1.0” W.C.1.2” W.C.1.4” W.C.3” W.C.6” W.C.8” W.C.
0.30.30.80.41.00.91.54.02.55.06.05.08
10153045
125275
1.2” W.C.1.4” W.C.1.6” W.C.4.0” W.C.7.0” W.C.
13.0” W.C.0.40.41.00.61.21.42.25.53.57.08.57.01014204060
150300
2.4” W.C.2.7” W.C.6.5” W.C.14” W.C.25” W.C.40” W.C.
0.70.91.61.81.83.668
10122020304060
100150350800
SA40DSA30DSA20DSA20DSA10DSA10DSA40DSA30DSA40DSA20DSA30DSA20DSA10DSA30DSA10DSA20DSA10DSA10DSA10DSA10DSA10DSA10DSA10DSA10DSA10D
SA41DSA31DSA21DSA21DSA11DSA11DSA41DSA31DSA41DSA21DSA31DSA21DSA11DSA31DSA11DSA21DSA11DSA11DSA11DSA11DSA11DSA11DSA11DSA11DSA11D
SA42DSA32DSA22DSA22DSA12DSA12DSA42DSA32DSA42DSA22DSA32DSA22DSA12DSA32DSA12DSA22DSA12DSA12DSA12DSA12DSA12DSA12DSA12DSA12DSA12D
SC40DSC30DSC20DSC20DSC10DSC10DSC40DSC30DSC40DSC20DSC30DSC20DSC10DSC30DSC10DSC20DSC10DSC10DSC10DSC10DSC10DSC10DSC10DSC10DSC10D
SC41DSC31DSC21DSC21DSC11DSC11DSC41DSC31DSC41DSC21DSC31DSC21DSC11DSC31DSC11DSC21DSC11DSC11DSC11DSC11DSC11DSC11DSC11DSC11DSC11D
SC42DSC32DSC22DSC22DSC12DSC12DSC42DSC32DSC42DSC22DSC32DSC22DSC12DSC32DSC12DSC22DSC12DSC12DSC12DSC12DSC12DSC12DSC12DSC12DSC12D
SB40DSB30DSB20DSB20DSB10DSB10DSB40DSB30DSB40DSB20DSB30DSB20DSB10DSB30DSB10DSB20DSB10DSB10DSB10DSB10DSB10DSB10DSB10DSB10DSB10D
SB41DSB31DSB21DSB21DSB11DSB11DSB41DSB31DSB41DSB21DSB31DSB21DSB11DSB31DSB11DSB21DSB11DSB11DSB11DSB11DSB11DSB11DSB11DSB11DSB11D
SB42DSB32DSB22DSB22DSB12DSB12DSB42DSB32DSB42DSB22DSB32DSB22DSB12DSB32DSB12DSB22DSB12DSB12DSB12DSB12DSB12DSB12DSB12DSB12DSB12D
CatalogNo.
Brass &Buna “N”
All 316 SS
316 SS &
CatalogNo.
CatalogNo.
------------------
TD40A21TD30A21
---TD20A21
---TE20A21TE10A21
---TF10A21
------
TG10A21TH10A21TJ10A21TK10A21TL10A21TM10A21TN10B21
---
CatalogNo.
Aluminum &Buna “N”
Water, AirOil or Gas Corrosive Fluids
Air, Oilor Gas
TA40A11TA30A11TA20A11TB20A11TB10A11TC10A11TD40A11TD30A11
---TD20A11
---TE20A11TE10A11
---TE10A11
------
TG10A11TH10A11TJ10A11
---------------
------------------------
TE40A44---
TE30A44TE20A44TE10A44
---TF10A44
------
TG10A44TH10A44TJ10A44
---------------
TA40A32TA30A32TA20A32TB20A32TB10A32TC10A32TD40A42TD30A42
---TD20A42
---TE20A42TE10A42TG33A42TF10A42TG23A42TG13A42TG10A42TH10A42TJ10A42TK10A42TL10A42TM10A42TN10B42TQ10B42
0.4 - 4.50.7 - 9.00.8 - 9.01.0 - 181.0 - 181.5 - 36
2 - 605 - 603 - 1005 - 1205 - 2006 - 200
13 - 30015 - 40030 - 60050 - 100075 - 1500
200 - 3500500 - 8000
Two-Stage Fixed Deadbandunits consist of two separate snap-actionswitches, each with an independentlyadjustable set point and non-adjustablereset point. The difference between theset and reset points of each switch is thedeadband listed below; the minimumdifference between the set points of thetwo switches is the separation.
Explosion Proof
Select transducer unit below
Transducer Unit
These guage pressure type transducers provide for one pressure connection in the bottom of thetransducer. They are diaphragm/piston type transducers using an elastomer in contact with thefluid, backed by a piston cylinder. This allows highsensitivity for low pressures and strength for highpressures.
Standard connection is 1/4” NPT; (Optional 1/2” NPTadd suffix “B” to catalog numbers TD thru TQ)
Series TA-TC Series TD-TQ
32
Options – Add appropriate suffix for desired option(see pages 34-35).Important Note: The third digit of each of the catalog numbersmust be identical, e.g., SA 4 0D and TA 4 0A11.
4 123
17
Select S-Series pressure switch SA, SB, SC, SD and SE unit below
FKM
Two-Stage Fixed Deadband Transducer Units
18
S-SERIES Vacuum, Differential Switches
How to Select1. Select the adjustable operating range based on desired actuation point.2. Check that proof pressure is sufficient.3. Read across and select thedesired S-Series switch unit with the proper enclosure.4. Continue across and select a matching transducer unit compatible with the fluid.
How to OrderFactory assembled – Simplyorder the switch and transducerunit by catalog number joined by a slash (/), e.g., SA30D/TA34A11.Field assembled – Simplyorder the switch and transducerunits separately by individual catalog number, e.g., one SA30D and one TA34A11.
How to Select and OrderASCO S-Series switches consist of two components, the switch unit and the transducer unit.
Single-Stage Adjustable Deadbandunits allow independent adjustment ofthe set and reset points over the fulloperating range of the switch. Theminimum differencebetween set andreset points is thedeadband listedbelow; the maximumdifference is the fullrange of the switch .
SB Switch Unit: Single-Stage FixedDeadband units have an adjustable setpoint and a non-adjustable automatic reset point.SD Switch Unit: Manual reset on decreas-ing pressure units operate automatically on increasing pressure and must be reset manually on decreasing pressure.(To order, change second digit to letter “D”,e.g., S B 30D becomes S D 30D).SE Switch Unit: Manual reset on increas-ing pressure units operate automatically ondecreasing pressure and must be reset manually on increasing pressure.(To order, change second digit to letter “E”,e.g., S B 30D becomes S E 30D).
SA Switch Unit SB, SD or SE Switch Unit SC Switch Unit
General Purpose
Specifications Adjustable Deadband Fixed Deadband or Manual Reset
All switch units above are in stock for immediate delivery.
Values shown are nominal.1
All switch units and transducer units above are in stock for immediate delivery.
AdjustableOperating
Range(In W.C.)
AdjustableDeadband
AtMid-Range
(In W.C.)From/To
ProofPressure
(psig)Catalog
No.
GeneralPurpose Watertight
Explosion-Proof
CatalogNo.
CatalogNo.
FixedDeadband
AtMid-Range
(In W.C.) 1
1
FixedDeadband
AtMid-Range
(In W.C.) 1
Minimum AtMid-Range
(In W.C.)
Separation
MaximumFull Scale
1
CatalogNo.
GeneralPurpose Watertight
Explosion-Proof
CatalogNo.
CatalogNo.
CatalogNo.
GeneralPurpose Watertight
Explosion-Proof
CatalogNo.
CatalogNo.
50501515252525
151515252525
0 - 30” Hg15 PSI - 30” Hg
0 - 270 - 65
15 - 14015 - 25025 - 400
0 - 120 - 270 - 65
15 - 14015 - 25025 - 400
2 - 28” Hg3 - 57” Hg
1.2” Hg1.7” Hg
1.21.43.06.08.0
1.01.21.43.06.08.0
1.7” Hg2.0” Hg
1.72.04.07.0
13.0
1.41.72.04.07.0
13.0
3” Hg8” Hg
2.76.5
14.025.040.0
2.42.76.5
14.025.040.0
SA30DSA20DSA30DSA20DSA20DSA10DSA10D
SA40DSA30DSA20DSA20DSA10DSA10D
SA31DSA21DSA31DSA21DSA21DSA11DSA11D
SA41DSA31DSA21DSA21DSA11DSA11D
SA32DSA22DSA32DSA22DSA22DSA12DSA12D
SA42DSA32DSA22DSA22DSA12DSA12D
SC30DSC20DSC30DSC20DSC20DSC10DSC10D
SC40DSC30DSC20DSC20DSC10DSC10D
SC31DSC21DSC31DSC21DSC21DSC11DSC11D
SC41DSC31DSC21DSC21DSC11DSC11D
SC32DSC22DSC32DSC22DSC22DSC12DSC12D
SC42DSC32DSC22DSC22DSC12DSC12D
SB30DSB20DSB30DSB20DSB20DSB10DSB10D
SB40DSB30DSB20DSB20DSB10DSB10D
SB31DSB21DSB31DSB21DSB21DSB11DSB11D
SB41DSB31DSB21DSB21DSB11DSB11D
SB32DSB22DSB32DSB22DSB22DSB12DSB12D
SB42DSB32DSB22DSB22DSB12DSB12D
CatalogNo.
Brass &Buna “N”
303 SS &
CatalogNo.
TV34A21TV24A21
---------------
------------------
CatalogNo.
Aluminum &Buna “N”
Water, AirOil or Gas
CorrosiveFluids
Air or Gas
TV34A11TV24A11TA31A11TA21A11TB21A11TB11A11TC11A11
TA41A11TA31A11TA21A11TB21A11TB11A11TC11A11
TV34A32TV24A32
---------------
------------------
Two-Stage Fixed Deadbandunits consist of two separate snap-action switches,each with an independently adjustable set point andnon-adjustable reset point. Thedifference between the set andreset points of each switch is thedeadband listed below; theminimum difference between theset points of the two switches isthe separation.
Explosion Proof
Select transducer unit below
The vacuum transducer has aspring which preloads the switchunit when no vacuum is applied.On application, the vacuum actson a piston area to overcome thespring to operate the switch unit. Vacuum Transducer
Options – Add appropriate suffix for desired option(see pages 34-35).Important Note: The third digit of each of the catalognumbers must be identical, e.g., SA 3 0D and TA 3 4A11.
4 123
Differential Pressure Transducer
The differential pressure transducer has two pressuresources acting on the piston area inopposite directions. The forceoutput is proportional to thedifference between thesepressures, allowing thedifferential pressure to becontolled by adjustmentof the switch unit.
2 - 273 - 656 - 125
10 - 23515 - 375
2 - 122 - 273 - 656 - 125
10 - 23515 - 375
Vacuum
Differential
19
Select S-Series pressure switch SA, SB, SC, SD and SE unit below
FKM
20
S-SERIES Combustion Switches
Features:• Set point repeatability, +1% of operating range.• UL Listed in the gas and oil equipment list.• FM Approved as “pressure supervisory switches.”• Externally visible pressure setting scales.• External adjusting nuts.• Choice of fixed or full-range adjustable deadbands.• Choice of single or two-stage units.• Mounts in any position.• Rugged and vibration resistant.• Separate electrical, pressure and adjusting
chambers.• Mix and match switch and transducer components for
increased stock flexibility or to change pressure ranges in field.
• Withstands high surge pressures.
General Description:ASCO S-Series combustion switches consist of aswitch unit and a transducer unit. They can be orderedseparately for customer stocking and/or field assemblyor as a complete factory-assembled unit.
SwitchS-Series combustion switch units incorporate theunique ASCO TRI-POINT alternating fulcrum balanceplate to control the operation of one or more electricalsnap-action swtiches. The electrical snap-action switchtogether with the adjusting mechanism is a fully-tested,self-contained subassembly.
TransducerTransducer unit incorporates a diaphragm/piston type pressure sensor, and is also a fully-tested, self-contained subassembly.
OperationWhen pressure is applied to the transducer it is converted into movement of the piston. This pistonmovement is then used to control the operation of the electrical snap-action switch in the switch unit.
Options (See pages 34-35)
Dimensions (See page 15)
Standard Electrical Ratings
Standard Temperature Ratings
Pressure Switches Designed to UL or FM Requirementsfor Combustion Service
SA, SD and SE Series5 Amp Res., 125, 250 VAC1/8 HP, 125 VAC1/4 HP, 250 VAC1/2 Amp Res., 125 VDC1/4 Amp Res., 250 VDC
SB and SC Series5 Amp Res., 125, 250 VAC1/4 HP, 125 VAC1/2 HP, 250 VAC.4 Amp Res., 125, VDC
Ambient: -4°F (-20°C) to 140°F (60°C)Fluid: For Buna “N” or Neoprene Diaphragm
-4°F (-20°C) to 180°F (82°C)
-4°F (-20°C) to 250°F (121°C)For 316 SS Diaphragm-50°F (-45°C) to 300°F (149°C)
SD and SE Series not FM Approved.1
^ #
1
SPDTNO
NC
C
For FKM Diaphragm
4 123
UL RequirementsUnderwriters’ Laboratories, Inc.’s Standard UL 353defines construction and performance requirements forlimit controls.
SwitchS-Series combustion switch units when mated to thepressure transducers described below form pressureswitches in accordance with UL requirements.
TransducersFuel Gas – UL requires a pressure transducer with asecondary chamber. This chamber allows the gas to be vented to a safe location in the event of primary sensing element rupture. The “double chamber” withvent pressure transducers meet this requirement.
Fuel Oil – UL requirements for fuel oil applications waive the double chamber requirement, providing thesensing element is made of Type 316 or 321 SS. S-Series type 316 SS pressure transducers aredesigned to meet this requirement.
General Service – Pressure transducers for water,steam and air service may be of the single chamberdesign.
EnclosuresASCO TRI-POINT S-Series switches are available inthree standard enclosures. All of these enclosed unitsare made in accordance with NEMA and UL standards.
General Purpose – Type 1. These enclosures aredesigned for indoor use to protect personnel fromaccidental contact with the equipment. S-Series general purpose switch units consist of a copper-free*aluminum die-cast body with a formed copper-free* aluminum cover; two 3/4” conduit hubs with one plugare provided.
Watertight – Type 4. Watertight and dust-tight enclo-sures are intended for use indoors and outdoors to protect the enclosed equipment against splashing orfalling water, windblown dust and water, hose directedwater, and severe external condensation. S-Serieswatertight switch units have a copper-free* aluminumdie-cast body and a formed copper-free* aluminumcover with Buna “N” gaskets; two 3/4” conduit hubs with one plug are provided.
Explosion-Proof – Types 7 and 9. Type 7 enclosuresare intended for use in locations defined by the NationalElectrical Code as Class I. Type 9 enclosures areintended for Class II locations.
Class I locations are those in which flammable gasesare or may be present in the air in sufficient quantitiesto produce explosive or ignitable mixtures. Class Ilocations are classified by group letter, which definesparticular atmospheres. Division 1 locations are areaswhere the hazardous concentration exists continuously,intermittently or periodically under normal operatingconditions. Division 2 locations are those where thehazardous vapors are present only in case of acciden-tal rupture or breakdown of equipment.
ASCO TRI-POINT explosion-proof enclosures with letter B, C or D in the fifth position are listed for Class I,Groups B, C, and D, Division 1. They are also suitablefor the less stringent Division 2 environment.
Class II locations are those which are hazardousbecause of the presence of combustible dust. All ASCO TRI-POINT explosion-proof enclosures are listed for Groups E, F, and G locations.
The switch body and cover are die-cast copper-free*aluminum with a Buna “N” gasket. Two 3/4” conduithubs with one plug are provided.
FM RequirementsFuel Gas and Fuel Oil – FM requires that fuel gas and fuel oil pressure supervisory switches shall have avisible external means of determining switch position.No specific constructions are required for the pressuretransducer. Switch units with visual position indication(suffix “V”) in conjunction with single chamber pressuretransducers will meet these requirements.
General Service – Standard switch units with an adjusting nut cover, when mated to single chambertransducers, meet FM requirements for general applications such as “airflow interlocking switches”.
EnclosuresGeneral Purpose – Designed to Type 1 specificationsfor indoor applications. Die casting is copper-free* aluminum; covers are polycarbonate. Two 3/4” conduithubs with one plug are provided.
Watertight – Designed to Types 4 specifications forindoor/outdoor use. Die casting is copper-free* aluminum. Cover are polycarbonate and gaskets areneoprene. Two 3/4” conduit hubs with one plug are provided.
* Less than 0.6% copper.
21
Two-Stage Fixed Deadband Transducer Units
22
S-SERIES Combustion Switches
How to Select1. Select the adjustable operating range based on desired actuation pressure.2. Check that proof pressure is sufficient.3. Read across and select thedesired S-Series switch unit with the proper enclosure.4. Continue across and select a matching transducer unit compatible with the fluid.
How to OrderFactory assembled – Simplyorder the switch and transducerunit by catalog number joined by a slash (/), e.g., SA30D/TA31A11.Field assembled – Simply order the switch and transducerunits separately by individual catalog number, e.g., one SA30D and one TA31A11.
How to Select and OrderASCO S-Series switches consist of two components, the switch unit and the transducer unit.
Single-Stage Adjustable Deadbandunits allow independentadjustment of the setand reset points overthe full operating rangeof the switch. Theminimum differencebetween set and resetpoints is the deadbandlisted below; themaximum differenceis the full range ofthe switch .
SB Switch Unit: Single-Stage FixedDeadband units have an adjustable setpoint and a non-adjustable automatic reset point.SD Switch Unit: Manual reset on decreas-ing pressure units operate automatically on increasing pressure and must be reset manually on decreasing pressure.(To order, change second digit to letter “D”,e.g., S B 30D becomes S D 30D).SE Switch Unit: Manual reset on increas-ing pressure units operate automaticallyon decreasing pressure and must be reset manually on increasing pressure.(To order, change second digit to letter “E”,e.g., S B 30D becomes S E 30D).
SA Switch Unit SB, SD or SE Switch Unit SC Switch Unit
UL General Purpose
Specifications Adjustable Deadband Fixed Deadband or Manual Reset
Values shown are nominal.1
AdjustableOperating
Range(psig)
ProofPressure
(psig)Catalog
No.
GeneralPurpose
WatertightEnclosure
WatertightEnclosure
WatertightEnclosure
Explosion-Proof
CatalogNo.
CatalogNo.
FixedDeadband
AtMid-Range
(psig.) 1
FixedDeadband
AtMid-Range
(psig) 1
Minimum AtMid-Range
(psig)
Separation
MaximumFull Scale
1
Minimum AtMid-Range
(psig)
AdjustableDeadbandMaximumFull Scale
CatalogNo.
GeneralPurpose
Explosion-Proof
CatalogNo.
CatalogNo.
CatalogNo.
GeneralPurpose
Explosion-Proof
CatalogNo.
CatalogNo.
1515252525
150150200150150200200
252525404040
100100100150150200
0 - 27” W.C.0 - 65” W.C.
15 - 140” W.C.15 - 250” W.C.25 - 400” W.C.0.8 - 9.01.0 - 181.5 - 301.5 - 362.0 - 602.0 - 603.0 - 100
2 - 12” W.C.2 - 27” W.C.2 - 65” W.C.
15 - 140” W.C.15 - 250” W.C.25 - 400” W.C.0.4 - 4.50.8 - 9.01.0 - 181.5 - 362.0 - 603.0 - 100
1.2” W.C.1.4” W.C.3.0” W.C.6.0” W.C.8.0” W.C.
0.90.61.51.42.32.03.7
1.0” W.C.1.2” W.C.1.4” W.C.3.0” W.C.6.0” W.C.8.0” W.C.
0.30.30.40.91.52.5
2.0” W.C.2.5” W.C.6.0” W.C.
10.0” W.C.15.0” W.C.
1.44.64.03.35.45.09.0
1.5” W.C.2.0” W.C.2.5” W.C.6.0” W.C.
10.0” W.C.1 5.0” W.C.
0.40.61.12.23.66.0
1.7” W.C.2.0” W.C.4.0” W.C.7.0” W.C.
13.0” W.C.1.51.02.02.03.53.05.0
1.4” W.C.1.7” W.C.2.0” W.C.4.0” W.C.7.0” W.C.
13.0” W.C.0.50.50.51.22.13.5
2.7” W.C.6.5” W.C.
14.0” W.C.25.0” W.C.40.0” W.C.
1.61.83.03.66.06.0
10.0
2.4” W.C.2.7” W.C.6.5” W.C.
14.0” W.C.25.0” W.C.40.0” W.C.
0.70.91.83.66.0
10.0
SA30DSA20DSA20DSA10DSA10DSA40DSA30DSA30DSA20DSA10DSA20DSA10D
SA40DVSA30DVSA20DVSA20DVSA10DVSA10DVSA40DVSA30DVSA20DVSA20DVSA10DVSA10DV
SA31DSA21DSA21DSA11DSA11DSA41DSA31DSA31DSA21DSA11DSA21DSA11D
SA41DVSA31DVSA21DVSA21DVSA11DVSA11DVSA41DVSA31DVSA21DVSA21DVSA11DVSA11DV
SA32DSA22DSA22DSA12DSA12DSA42DSA32DSA32DSA22DSA12DSA22DSA12D
------------------------------------
SC30DSC20DSC20DSC10DSC10DSC40DSC30DSC30DSC20DSC10DSC20DSC10D
SC40DVSC30DVSC20DVSC20DVSC10DVSC10DVSC40DVSC30DVSC20DVSC20DVSC10DVSC10DV
SC31DSC21DSC21DSC11DSC11DSC41DSC31DSC31DSC21DSC11DSC21DSC11D
SC41DVSC31DVSC21DVSC21DVSC11DVSC11DVSC41DVSC31DVSC21DVSC21DVSC11DVSC11DV
SC32DSC22DSC22DSC12DSC12DSC42DSC32DSC32DSC22DSC12DSC22DSC12D
------------------------------------
SB30DSB20DSB20DSB10DSB10DSB40DSB30DSB30DSB20DSB10DSB20DSB10D
SB40DVSB30DVSB20DVSB20DVSB10DVSB10DVSB40DVSB30DVSB20DVSB20DVSB10DVSB10DV
SB31DSB21DSB21DSB11DSB11DSB41DSB31DSB31DSB21DSB11DSB21DSB11D
SB41DVSB31DVSB21DVSB21DVSB11DVSB11DVSB41DVSB31DVSB21DVSB21DVSB11DVSB11DV
SB32DSB22DSB22DSB12DSB12DSB42DSB32DSB32DSB22DSB12DSB22DSB12D
------------------------------------
CatalogNo.
Brass &Buna “N”
All 316 SS
316 SS &Viton
CatalogNo.
CatalogNo.
---------------------
TF32A21------
TF22A21TF12A21
------------------
TD40A21TD30A21TD20A21TE20A21TE10A21TF10A21
CatalogNo.
Aluminum &Buna “N”
TA31A11TA21A11TB21A11TB11A11TC11A11
---------------------
TA40A11FTA30A11FTA20A11FTB20A11TB10A11TC10A11TD40A11TD30A11TD20A11TE20A11TE10A11TF10A11
---------------
TE40A44TE30A44
---TE20A44TE10A44
---TF10A44
------------------------------------
------------------------------------
TA40A32FTA30A32FTA20A32FTB20A32TB10A32TC10A32TD40A42TD30A42TD20A42TE20A42TE10A42TF10A42
Two-Stage Fixed Deadbandunits consist of two separate snap-actionswitches, each with an independentlyadjustable set point and non-adjustablereset point. The difference between theset and reset points of each switch is thedeadband listed below; the minimumdifference between the set points of thetwo switches is the separation.
Select transducer unit belowOptions – Add appropriate suffix for desired option(see pages 34-35).Important Note: The third digit of each of the catalognumbers must be identical, e.g., SA 3 0D and TA 3 1A11.
4 123
UL Listed
FM Approved
Transducer Unit
These guage pressure type transducers provide for one pressure connection in the bottom of thetransducer. They are diaphragm/piston type trans-ducers using an elastomer in contact with the fluid,backed by a piston cylinder. UL requires a doublechamber transducer for fuel gas service and singlechamber 316 SS transducer for fuel oil service.
Standard connection is 1/4” NPT
UL Listed FM Approved
FM General Purpose
Manual reset units not available for FM.2 316 SS transducers increase deadband by 50%.3 Transducers ending in 32 have 303 SS process connections, not 316 SS.4
43
1
2
Fuel Gas and Fuel Oil
Fuel Gas Fuel Oil
23
Select S-Series pressure switch SA, SB, SC, SD and SE unit below
Two-Stage Fixed Deadband Transducer Units
22
S-SERIES Combustion Switches
How to Select1. Select the adjustable operating range based on desired actuation pressure.2. Check that proof pressure is sufficient.3. Read across and select thedesired S-Series switch unit with the proper enclosure.4. Continue across and select a matching transducer unit compatible with the fluid.
How to OrderFactory assembled – Simplyorder the switch and transducerunit by catalog number joined by a slash (/), e.g., SA30D/TA31A11.Field assembled – Simply order the switch and transducerunits separately by individual catalog number, e.g., one SA30D and one TA31A11.
How to Select and OrderASCO S-Series switches consist of two components, the switch unit and the transducer unit.
Single-Stage Adjustable Deadbandunits allow independentadjustment of the setand reset points overthe full operating rangeof the switch. Theminimum differencebetween set and resetpoints is the deadbandlisted below; themaximum differenceis the full range ofthe switch .
SB Switch Unit: Single-Stage FixedDeadband units have an adjustable setpoint and a non-adjustable automatic reset point.SD Switch Unit: Manual reset on decreas-ing pressure units operate automatically on increasing pressure and must be reset manually on decreasing pressure.(To order, change second digit to letter “D”,e.g., S B 30D becomes S D 30D).SE Switch Unit: Manual reset on increas-ing pressure units operate automaticallyon decreasing pressure and must be reset manually on increasing pressure.(To order, change second digit to letter “E”,e.g., S B 30D becomes S E 30D).
SA Switch Unit SB, SD or SE Switch Unit SC Switch Unit
UL General Purpose
Specifications Adjustable Deadband Fixed Deadband or Manual Reset
Values shown are nominal.1
AdjustableOperating
Range(psig)
ProofPressure
(psig)Catalog
No.
GeneralPurpose
WatertightEnclosure
WatertightEnclosure
WatertightEnclosure
Explosion-Proof
CatalogNo.
CatalogNo.
FixedDeadband
AtMid-Range
(psig.) 1
FixedDeadband
AtMid-Range
(psig) 1
Minimum AtMid-Range
(psig)
Separation
MaximumFull Scale
1
Minimum AtMid-Range
(psig)
AdjustableDeadbandMaximumFull Scale
CatalogNo.
GeneralPurpose
Explosion-Proof
CatalogNo.
CatalogNo.
CatalogNo.
GeneralPurpose
Explosion-Proof
CatalogNo.
CatalogNo.
1515252525
150150200150150200200
252525404040
100100100150150200
0 - 27” W.C.0 - 65” W.C.
15 - 140” W.C.15 - 250” W.C.25 - 400” W.C.
0.8 - 9.01.0 - 181.5 - 301.5 - 362.0 - 602.0 - 603.0 - 100
2 - 12” W.C.2 - 27” W.C.2 - 65” W.C.
15 - 140” W.C.15 - 250” W.C.25 - 400” W.C.
0.4 - 4.50.8 - 9.01.0 - 181.5 - 362.0 - 603.0 - 100
1.2” W.C.1.4” W.C.3.0” W.C.6.0” W.C.8.0” W.C.
0.90.61.51.42.32.03.7
1.0” W.C.1.2” W.C.1.4” W.C.3.0” W.C.6.0” W.C.8.0” W.C.
0.30.30.40.91.52.5
2.0” W.C.2.5” W.C.6.0” W.C.
10.0” W.C.15.0” W.C.
1.44.64.03.35.45.09.0
1.5” W.C.2.0” W.C.2.5” W.C.6.0” W.C.
10.0” W.C.1 5.0” W.C.
0.40.61.12.23.66.0
1.7” W.C.2.0” W.C.4.0” W.C.7.0” W.C.
13.0” W.C.1.51.02.02.03.53.05.0
1.4” W.C.1.7” W.C.2.0” W.C.4.0” W.C.7.0” W.C.
13.0” W.C.0.50.50.51.22.13.5
2.7” W.C.6.5” W.C.
14.0” W.C.25.0” W.C.40.0” W.C.
1.61.83.03.66.06.0
10.0
2.4” W.C.2.7” W.C.6.5” W.C.
14.0” W.C.25.0” W.C.40.0” W.C.
0.70.91.83.66.0
10.0
SA30DSA20DSA20DSA10DSA10DSA40DSA30DSA30DSA20DSA10DSA20DSA10D
SA40DVSA30DVSA20DVSA20DVSA10DVSA10DVSA40DVSA30DVSA20DVSA20DVSA10DVSA10DV
SA31DSA21DSA21DSA11DSA11DSA41DSA31DSA31DSA21DSA11DSA21DSA11D
SA41DVSA31DVSA21DVSA21DVSA11DVSA11DVSA41DVSA31DVSA21DVSA21DVSA11DVSA11DV
SA32DSA22DSA22DSA12DSA12DSA42DSA32DSA32DSA22DSA12DSA22DSA12D
------------------------------------
SC30DSC20DSC20DSC10DSC10DSC40DSC30DSC30DSC20DSC10DSC20DSC10D
SC40DVSC30DVSC20DVSC20DVSC10DVSC10DVSC40DVSC30DVSC20DVSC20DVSC10DVSC10DV
SC31DSC21DSC21DSC11DSC11DSC41DSC31DSC31DSC21DSC11DSC21DSC11D
SC41DVSC31DVSC21DVSC21DVSC11DVSC11DVSC41DVSC31DVSC21DVSC21DVSC11DVSC11DV
SC32DSC22DSC22DSC12DSC12DSC42DSC32DSC32DSC22DSC12DSC22DSC12D
------------------------------------
SB30DSB20DSB20DSB10DSB10DSB40DSB30DSB30DSB20DSB10DSB20DSB10D
SB40DVSB30DVSB20DVSB20DVSB10DVSB10DVSB40DVSB30DVSB20DVSB20DVSB10DVSB10DV
SB31DSB21DSB21DSB11DSB11DSB41DSB31DSB31DSB21DSB11DSB21DSB11D
SB41DVSB31DVSB21DVSB21DVSB11DVSB11DVSB41DVSB31DVSB21DVSB21DVSB11DVSB11DV
SB32DSB22DSB22DSB12DSB12DSB42DSB32DSB32DSB22DSB12DSB22DSB12D
------------------------------------
CatalogNo.
Brass &Buna “N”
All 316 SS
316 SS &
CatalogNo.
CatalogNo.
---------------------
TF32A21------
TF22A21TF12A21
------------------
TD40A21TD30A21TD20A21TE20A21TE10A21TF10A21
CatalogNo.
Aluminum &Buna “N”
TA31A11TA21A11TB21A11TB11A11TC11A11
---------------------
TA40A11FTA30A11FTA20A11FTB20A11TB10A11TC10A11TD40A11TD30A11TD20A11TE20A11TE10A11TF10A11
---------------
TE40A44TE30A44
---TE20A44TE10A44
---TF10A44
------------------------------------
------------------------------------
TA40A32FTA30A32FTA20A32FTB20A32TB10A32TC10A32TD40A42TD30A42TD20A42TE20A42TE10A42TF10A42
Two-Stage Fixed Deadbandunits consist of two separate snap-actionswitches, each with an independentlyadjustable set point and non-adjustablereset point. The difference between theset and reset points of each switch is thedeadband listed below; the minimumdifference between the set points of thetwo switches is the separation.
Select transducer unit belowOptions – Add appropriate suffix for desired option(see pages 34-35).Important Note: The third digit of each of the catalognumbers must be identical, e.g., SA 3 0D and TA 3 1A11.
4 123
UL Listed
FM Approved
Transducer Unit
These guage pressure type transducers provide for one pressure connection in the bottom of thetransducer. They are diaphragm/piston type trans-ducers using an elastomer in contact with the fluid,backed by a piston cylinder. UL requires a doublechamber transducer for fuel gas service and singlechamber 316 SS transducer for fuel oil service.
Standard connection is 1/4” NPT
UL Listed FM Approved
FM General Purpose
Manual reset units not available for FM.2 316 SS transducers increase deadband by 50%.3 Transducers ending in 32 have 303 SS process connections, not 316 SS.4
43
1
2
Fuel Gas and Fuel Oil
Fuel Gas Fuel Oil
23
Select S-Series pressure switch SA, SB, SC, SD and SE unit below
FKM
24
P-SERIES Temperature Switches
Features:• Set point repeatability, +1°F (1/2°C).• All wiring terminals, adjustments and visual scales
are accessible from the front of the switch.• Choice of open frame type, general purpose, or
watertight enclosure.• Choice of fixed, limited adjustable or full-range
adjustable deadband.• Choice of single or two-stage units.• Compact size.• Mounts in any position.• Rugged and vibration resistant.• Visual adjustment scales in °F and °C.• Direct mount (local) or capillary and bulb (remote)
sensors.• Temperature transducers available with copper or
316 SS wetted material.• Withstands high overrange temperatures.• Mix and match switch and transducer components for
increased stock flexibility or to change pressure ranges in field.
General Description:ASCO P-Series temperature switches consist of anopen frame or enclosure protected switch unit and atransducer unit. They can be ordered separately forcustomer stocking and/or field assembly or as a complete factory-assembled unit.
SwitchP-Series temperature switch units incorporate theunique ASCO TRI-POINT alternating fulcrum balanceplate to control the operation of one or more electricalsnap-action swtiches. The electrical snap-action switchtogether with the adjusting mechanism is a fully-tested,self-contained subassembly.
TransducerThe temperature transducer unit uses a vapor pressureprinciple where the internal pressure within the unit isgenerated by the vapor pressure of a chemical within asealed system. Temperature transducers are availablein two constructions, a direct mount or capillary andbulb construction. The direct mount unit includes a 1/2”NPT connection for direct mounting to the process. Thecapillary and bulb construction allows remote mountingfrom the process. The transducer unit (like the switchunit) is a fully-tested, self-contained subassembly.
Standard Electrical Ratings
Switches for -60 through 510°F with Adjustable Set Pointsand Fixed or Adjustable Deadband
PA, PB, PC Series15 Amp Res., 125 VAC10 Amp Res., 250 VAC1/8 HP, 125 VAC1/4 HP, 250 VAC1/2 Amp Res., 125 VDC1/4 Amp Res., 250 VDC
PG Series15 Amp Res., 125 VAC10 Amp Res., 250 VAC1/8 HP, 125 VAC1/4 HP, 250 VAC
^ %
SPDTNO
NC
C
Standard Temperature Ratings
Ambient: -4°F (-20°C) to 122°F (50°C)Fluid: See specification table on page 26
for rated overrange temperature.
OperationTemperature sensed by the bulb creates an internalpressure within the transducer. This pressure is thenconverted into movement of the piston. This pistonmovement is then used to control the operation of the electrical snap-action switch in the switch unit.
Options (See pages 34-35)
PC and PG Series not UL listed or CSA approved, PC Seriesrated 10 Amp Res., 125/250 VAC; 1/3 HP 125/250 VAC.
1
1
1
4 123
EnclosuresASCO TRI-POINT switches are available in either ageneral purpose or watertight enclosure, in addition toopen frame construction. These enclosed units aremade in accordance with NEMA and UL standards.These standards define the protection level an enclosure gives and the tests it must pass to meet a particular design.
General Purpose – Type 1. These enclosures aredesigned for indoor use to protect personnel fromaccidental contact with the equipment. P-Series general purpose enclosures are painted, zinc-coated
steel and have a 7/8” diameter hole at the top for electrical entry.
Watertight – Type 4. Watertight and dust-tight enclosures are intended for use indoors and outdoorsto protect the enclosed equipment against splashing orfalling water, windblown dust and water, hose directedwater, and severe external condensation. P-Serieswatertight switch enclosures are epoxy-painted, zinc-coated steel with a 1/2” conduit hub in the side of thelower housing for electrical entry. (For optional 316 SSwatertight enclosure see page 29.)
Dimensions (inches)
9.9265.54
2.5
1.5
3.8DIA.
1/2 NPT 1.8
.4
2.4
.233 DIA HOLES FORMOUNTING WITH #10(.190 DIA.) SCREWS(2 PLACES)
4.2
3.8DIA.
1.5
3.8DIA.
1/2 NPT
5.7
9.5 5.1
2.5
2.7
.233 DIA HOLESFOR MOUNTINGWITH #10 (.190 DIA.)SCREWS (2 PLACES)1.8
1.8
.4
.233 DIA HOLES FORMOUNTING WITH #10(.190 DIA.) SCREWS(2 PLACES)
3.8DIA.
2.5
4.5
4.0
1.4
.8
6.5
10.3
7/8 DIA. HOLEFOR 1/2 CONDUITCONNECTION
1.8
1.5
3.8DIA.
1/2 NPT
6.4
3.0
2.61.8
.5 .08.223 DIA. HOLESFOR MOUNTINGWITH #10 (.190 DIA.)SCREWS (2 PLACES)
1.8
.4
.233 DIA HOLES FORMOUNTING WITH #10(.190 DIA.) SCREWS(2 PLACES)
5.3
3.8DIA.
4.8
4.94.5
2.5
2.5
5.3
1/2 NPTCONDUITCONNECTION
1.7
4.0
ADDITIONAL SPACING REQUIREDFOR REMOVAL OF COVER
9.6 3.0
2.0
3.8DIA.
1/2 NPT
4.0
5.8
1.82.04
.3
.233 DIA HOLES FORMOUNTING WITH #10(.190 DIA.) SCREWS(2 PLACES)
3.8DIA.
4.7
1.9
P-Series Temperature (Mounting brackets optional)
Open Frame PA and PC Switch Unitswith Transducer Unit Types RD-RV
Open Frame PB and PG Switch Unitswith Transducer Unit
Type 1 General Purpose Switch Unitwith Transducer Unit
Type 4 Watertight Switch Unitwith Transducer Unit
25
26 27
Two-Stage Fixed Deadband Temperature Transducer Units
P-SERIES Temperature Switches
How to OrderFactory assembled – Simply order the switch andtransducer unit by catalog number joined by a slash (/), e.g., PA16A/KA10A1.Field assembled – Simply order the switch andtransducer units separately by individual catalognumber, e.g., one PA16A and one KA10A1.Options – Add appropriate suffix for desired optionor accessory (see pages 34-35).Important Note: The third digit of each of the catalognumbers must be identical,e.g., PA 1 6A and KA 1 0A1.
How to Select and OrderASCO P-Series switches consist of two components, the switch unit and the transducer unit.
How to Select1. Select the adjustable operating range based on desired actuation temperature.2. Check that rated overrange temperature is sufficient.3. Read across and select the desired P-Series switch unit with the proper enclosure.4. Continue across and select a matching transducer unit.
Single-Stage Adjustable Deadbandunits allow independent adjustment ofthe set and reset points over the fulloperating range of the switch. Theminimum differencebetween set andreset points is thedeadband listedbelow; themaximumdifference isthe full rangeof the switch .
Single-Stage Fixed Deadband unitshave an adjustable set point and anon-adjustable automatic reset point.
PA Switch Unit PB Switch Unit PC Switch Unit
Open Frame Open Frame
Specifications Adjustable Deadband Fixed Deadband
All switch units above are in stock for immediate delivery.
Values shown are nominal.1
All switch units and transducer units above are in stock for immediate delivery.
AdjustableOperating
Range(°F)
RatedOverrange
Temperature (°F)
Minimum AtMid-Range
(°F)
AdjustableDeadband
MaximumFull Scale
CatalogNo.
DirectMount Copper SS
OpenFrame
WatertightEnclosure
GeneralPurpose
CatalogNo.
CatalogNo.1
FixedDeadband
AtMid-Range
(°F) 1
FixedDeadband
AtMid-Range
(°F)
Minimum AtMid-Range
(°F)
Separation
MaximumFull Scale
CatalogNo.
OpenFrame
GeneralPurpose
WatertightEnclosure
CatalogNo.
CatalogNo.
CatalogNo.
OpenFrame
GeneralPurpose
WatertightEnclosure
CatalogNo.
CatalogNo.
250
260
260
260
260
---
---
---
250
300
350
400
500
550
550
550
250
300
350
450
500
600
700
800
10
10
10
10
10
10
12
12
4
4
4
4
4
4
5
5
7
7
7
7
7
7
9
9
9
9
11
12
10
12
15
16
PA16A
PA16A
PA16A
PA16A
PA16A
PA16A
PA16A
PA16A
PA10A
PA10A
PA10A
PA10A
PA10A
PA10A
PA10A
PA10A
PA11B
PA11B
PA11B
PA11B
PA11B
PA11B
PA11B
PA11B
PC16A
PC16A
PC16A
PC16A
PC16A
PC16A
PC16A
PC16A
PC10A
PC10A
PC10A
PC10A
PC10A
PC10A
PC10A
PC10A
PC11B
PC11B
PC11B
PC11B
PC11B
PC11B
PC11B
PC11B
PB16A
PB16A
PB16A
PB16A
PB16A
PB16A
PB16A
PB16A
PB10A
PB10A
PB10A
PB10A
PB10A
PB10A
PB10A
PB10A
PB11B
PB11B
PB11B
PB11B
PB11B
PB11B
PB11B
PB11B
CatalogNo.
316 SS 316 SSCopper Copper 316 SS
CatalogNo.
CatalogNo.
KB10A4
KD10A4
KF10A4
KJ10A4
KL10A4
---
---
---
CatalogNo.
KB11A1
KD11A1
KF11A1
KJ11A1
KL11A1
KN11A1
KT11A1
KU11A1
CatalogNo.
KB11A4
KD11A4
KF11A4
KJ11A4
KL11A4
KN11A4
KT11A4
KU11A4
CatalogNo.
Copper
12’ Capillary and Bulb6’ Capillary and BulbDirect Mount
KB10A1
KD10A1
KF10A1
KJ10A1
KL10A1
---
---
---
KB11A1D
KD11A1D
KF11A1D
KJ11A1D
KL11A1D
KN11A1D
KT11A1D
KU11A1D
KB11A4D
KD11A4D
KF11A4D
KJ11A4D
KL11A4D
KN11A4D
KT11A4D
KU11A4D
-30 - 60
0 - 90
50 - 160
100 - 220
160 - 260
225 - 340
300 - 450
350 - 510
Two-Stage Fixed Deadband units consist oftwo separate snap-action switches, each with anindependently adjustable set point and non-adjustable reset point. The difference between theset and reset points of each switch isthe deadband listed below;the minimum differencebetween the set pointsof the two switchesis the separation.
Open Frame
Select transducer unit below
Transducer Unit
The temperature transducer works on the vapor principle wherethe internal pressure within the system is generated by the vaporpressure of a chemical within a sealed system. The temperaturesensed by the bulb is related uniquely to an internal pressurewithin the system. The pressure acts on a diaphragm/piston tocreate the force output from the transducer into the switch unit.Temperature transducers are available in two constructions. Thedirect mount (local) unit includes a 1/2” NPT connection fordirect application to the process. The capillary and bulb-typeconstruction allows for remote mounting from the process.
Direct Mount1/2” NPT
Capillaryand Bulb
4 123
°C = (°F -32) x 5/9
Capillary
Watertight Enclosure
General Purpose Enclosure
Select P-Series temperature switch PA, PB, or PC unit below
26 27
Two-Stage Fixed Deadband Temperature Transducer Units
P-SERIES Temperature Switches
How to OrderFactory assembled – Simply order the switch andtransducer unit by catalog number joined by a slash (/), e.g., PA16A/KA10A1.Field assembled – Simply order the switch andtransducer units separately by individual catalognumber, e.g., one PA16A and one KA10A1.Options – Add appropriate suffix for desired optionor accessory (see pages 34-35).Important Note: The third digit of each of the catalognumbers must be identical,e.g., PA 1 6A and KA 1 0A1.
How to Select and OrderASCO P-Series switches consist of two components, the switch unit and the transducer unit.
How to Select1. Select the adjustable operating range based on desired actuation temperature.2. Check that rated overrange temperature is sufficient.3. Read across and select the desired P-Series switch unit with the proper enclosure.4. Continue across and select a matching transducer unit.
Single-Stage Adjustable Deadbandunits allow independent adjustment ofthe set and reset points over the fulloperating range of the switch. Theminimum differencebetween set andreset points is thedeadband listedbelow; themaximumdifference isthe full rangeof the switch .
Single-Stage Fixed Deadband unitshave an adjustable set point and anon-adjustable automatic reset point.
PA Switch Unit PB Switch Unit PC Switch Unit
Open Frame Open Frame
Specifications Adjustable Deadband Fixed Deadband
All switch units above are in stock for immediate delivery.
Values shown are nominal.1
All switch units and transducer units above are in stock for immediate delivery.
AdjustableOperating
Range(°F)
RatedOverrange
Temperature (°F)
Minimum AtMid-Range
(°F)
AdjustableDeadband
MaximumFull Scale
CatalogNo.
DirectMount Copper SS
OpenFrame
WatertightEnclosure
GeneralPurpose
CatalogNo.
CatalogNo.1
FixedDeadband
AtMid-Range
(°F) 1
FixedDeadband
AtMid-Range
(°F)
Minimum AtMid-Range
(°F)
Separation
MaximumFull Scale
CatalogNo.
OpenFrame
GeneralPurpose
WatertightEnclosure
CatalogNo.
CatalogNo.
CatalogNo.
OpenFrame
GeneralPurpose
WatertightEnclosure
CatalogNo.
CatalogNo.
250
260
260
260
260
---
---
---
250
300
350
400
500
550
550
550
250
300
350
450
500
600
700
800
10
10
10
10
10
10
12
12
4
4
4
4
4
4
5
5
7
7
7
7
7
7
9
9
9
9
11
12
10
12
15
16
PA16A
PA16A
PA16A
PA16A
PA16A
PA16A
PA16A
PA16A
PA10A
PA10A
PA10A
PA10A
PA10A
PA10A
PA10A
PA10A
PA11B
PA11B
PA11B
PA11B
PA11B
PA11B
PA11B
PA11B
PC16A
PC16A
PC16A
PC16A
PC16A
PC16A
PC16A
PC16A
PC10A
PC10A
PC10A
PC10A
PC10A
PC10A
PC10A
PC10A
PC11B
PC11B
PC11B
PC11B
PC11B
PC11B
PC11B
PC11B
PB16A
PB16A
PB16A
PB16A
PB16A
PB16A
PB16A
PB16A
PB10A
PB10A
PB10A
PB10A
PB10A
PB10A
PB10A
PB10A
PB11B
PB11B
PB11B
PB11B
PB11B
PB11B
PB11B
PB11B
CatalogNo.
316 SS 316 SSCopper Copper 316 SS
CatalogNo.
CatalogNo.
KB10A4
KD10A4
KF10A4
KJ10A4
KL10A4
---
---
---
CatalogNo.
KB11A1
KD11A1
KF11A1
KJ11A1
KL11A1
KN11A1
KT11A1
KU11A1
CatalogNo.
KB11A4
KD11A4
KF11A4
KJ11A4
KL11A4
KN11A4
KT11A4
KU11A4
CatalogNo.
Copper
12’ Capillary and Bulb6’ Capillary and BulbDirect Mount
KB10A1
KD10A1
KF10A1
KJ10A1
KL10A1
---
---
---
KB11A1D
KD11A1D
KF11A1D
KJ11A1D
KL11A1D
KN11A1D
KT11A1D
KU11A1D
KB11A4D
KD11A4D
KF11A4D
KJ11A4D
KL11A4D
KN11A4D
KT11A4D
KU11A4D
-30 - 60
0 - 90
50 - 160
100 - 220
160 - 260
225 - 340
300 - 450
350 - 510
Two-Stage Fixed Deadband units consist oftwo separate snap-action switches, each with anindependently adjustable set point and non-adjustable reset point. The difference between theset and reset points of each switch isthe deadband listed below;the minimum differencebetween the set pointsof the two switchesis the separation.
Open Frame
Select transducer unit below
Transducer Unit
The temperature transducer works on the vapor principle wherethe internal pressure within the system is generated by the vaporpressure of a chemical within a sealed system. The temperaturesensed by the bulb is related uniquely to an internal pressurewithin the system. The pressure acts on a diaphragm/piston tocreate the force output from the transducer into the switch unit.Temperature transducers are available in two constructions. Thedirect mount (local) unit includes a 1/2” NPT connection fordirect application to the process. The capillary and bulb-typeconstruction allows for remote mounting from the process.
Direct Mount1/2” NPT
Capillaryand Bulb
4 123
°C = (°F -32) x 5/9
Capillary
Watertight Enclosure
General Purpose Enclosure
Select P-Series temperature switch PA, PB, or PC unit below
28
P-SERIES Temperature Switches
How to Select1. Select the adjustable operating range basedon desired actuation temperature.2. Check that rated overrange temperature issufficient.3. Read across and select the desiredP-Series switch unit with the proper enclosure.4. Continue across and select a matchingtransducer unit.
How to Select and OrderASCO P-Series switches consist of two components, the switch unit and the transducer unit.
How to OrderFactory assembled – Simply order the switch and transducer unit bycatalog number joined by a slash (/), e.g., PG16A/KA10A1.Field assembled – Simply order the switch and transducer units separatelyby individual catalog number, e.g., one PG16A and one KA10A1.Options – Add appropriate suffix for desired option (see pages 34-35).Important Note: The third digit of each of the catalog numbers must beidentical, e.g., PG 1 6A and KA 1 0A1.
Limited Adjustable Deadband unitshave an adjustable set point and usea special snap-action switchthat varies thedeadbandwithin thelimits listedbelow.
The temperature transducer works on thevapor principle where the internal pressurewithin the system is generated by the vaporpressure of a chemical within a sealed sys-tem. The temperature sensed by the bulbis related uniquely to an internal pressurewithin the system. The pressure acts on adiaphragm/piston to create the force outputfrom the transducer into the switch unit.
PG Switch Unit Transducer Unit
Open FrameDirect Mount1/2” NPT
Capillaryand Bulb
Specifications Limited Adjustable Deadband Temperature Transducer Units
All switch units and transducer units above are in stock for immediate delivery.
Values shown are nominal.1
AdjustableOperating
Range(°F)
RatedOverrange
Temperature (°F)
Minimum AtMid-Range
(°F)
AdjustableDeadband
MaximumFull Scale
CatalogNo.
DirectMount Copper SS
OpenFrame
WatertightEnclosure
GeneralPurpose
CatalogNo.
CatalogNo.1
250
260
260
260
260
---
---
---
250
300
350
400
500
550
550
550
250
300
350
450
500
600
700
800
6 - 12
6 - 12
6 - 12
6 - 12
6 - 12
6 - 12
6 - 12
6 - 12
KB11A1
KD11A1
KF11A1
KJ11A1
KL11A1
KN11A1
KT11A1
KU11A1
KB10A4
KD10A4
KF10A4
KJ10A4
KL10A4
---
---
---
KB10A1
KD10A1
KF10A1
KJ10A1
KL10A1
---
---
---
PG16A
PG16A
PG16A
PG16A
PG16A
PG16A
PG16A
PG16A
PG10A
PG10A
PG10A
PG10A
PG10A
PG10A
PG10A
PG10A
PG11B
PG11B
PG11B
PG11B
PG11B
PG11B
PG11B
PG11B
KB11A4
KD11A4
KF11A4
KJ11A4
KL11A4
KN11A4
KT11A4
KU11A4
KB11A1D
KD11A1D
KF11A1D
KJ11A1D
KL11A1D
KN11A1D
KT11A1D
KU11A1D
KB11A4D
KD11A4D
KF11A4D
KJ11A4D
KL11A4D
KN11A4D
KT11A4D
KU11A4D
-30 - 60
0 - 90
50 - 160
100 - 220
160 - 260
225 - 340
300 - 450
350 - 510
°C = (°F -32) x 5/9
CapillaryCatalog
No.
316 SS 316 SSCopper Copper 316 SS
CatalogNo.
CatalogNo.
CatalogNo.
CatalogNo.
CatalogNo.
Copper
12’ Capillaryand Bulb
6’ Capillaryand BulbDirect Mount
Select P-Series switch unit and transducer unit below
29
Every ASCO P-Series temperature switchis available in a corrosion-resistant, stain-less steel enclosure. Typical applicationsinclude:• Offshore platforms• Hydrocarbon processing plants• Oil & gas fields• Oil & gas transmission lines• Chemical plants• Breweries• Paper pulp mills• Salt spray locations
Stainless Steel EnclosureASCO Type 4X watertight enclosure isdesigned to provide protection againstwindblown dust, rain, sleet or external iceformation. The switch and transducer unitare available only as factory-assembledunits.
How to Select and OrderASCO P-Series switches with 316 SSenclosure consist of two factory-assembledcomponents, the switch unit and thetransducer unit.
How to Select (use tables on pages 26-28)1. Select the adjustable operating range basedon desired actuation temperature.2. Check that rated overrange temperature issufficient.3. Read across and select the desired P-Seriesswitch unit with open frame construction.4. To add a 316 SS enclosure, change the fourthdigit of the open frame catalog number from “6”to “5”, e.g., PG1 6 A becomes PG5 5 A.5. Continue across and select a matching directmount or capillary and bulb transducer unit com-patible with the fluid. For direct mount unit addsuffix “D” to switch catalog number, e.g., PG15Abecomes PG15AD; for capillary and bulb unitadd suffix “C”, e.g., PG15A becomes PG15AC.
How to OrderFactory assembled only – Simply order theswitch and transducer unit by catalog numberjoined by a slash (/), e.g., PG15AD/KA10A4 fordirect mount and PG15AC/KA11A4 for capillaryand bulb unit.Options – Add appropriate suffix for desiredoption (see pages 34-35).
Dimensions (inches)
3/8 DIA.
1/2 NPTCONDUITCONNECTION
4.94.94.5 4.5
.27 DIA.2 HOLESFORMOUNTING*
*MOUNTING BRACKET OPTIONAL
1/2 NPTCONDUITCONNECTION
WRENCHTIGHTDIMS. FOR1/2 PIPETHREADS
.27 DIA2 HOLESFORMOUNTING*
5.6
2.31.7
9.54
3/8 DIA.
5.35
1/2 NPTCONDUITCONNECTION1.7
.42.3
4.0
4.3
1/2 NPT
1.7
6.9
1.8
1.8
P-Series Temperature with Optional 316 SS Enclosure
Switches with Optional 316 Stainless Steel Enclosure
4 123
30
S-SERIES Temperature Switches
Features:• Set point repeatability, +1°F (1/2°C).• All wiring terminals, adjustments and visual scales
are accessible from the front of the switch.• Choice of general purpose, watertight or
explosion-proof enclosures.• Choice of fixed or full-range adjustable deadband.• Choice of single or two-stage units.• Manual reset units available.• Mounts in any position.• Rugged and vibration resistant.• Visual adjustment scales in °F and °C.• External adjusting nuts.• Separate temperature, electrical and adjusting
chambers.• Direct mount (local) or capillary and bulb (remote)
sensors.• Temperature transducers available with copper or
316 stainless steel wetted material.• Withstands high overrange temperatures.• Mix and match switch and transducer components for
increased stock flexibility or to change pressure ranges in field.
General Description:ASCO S-Series temperature switches consist of aswitch unit and a transducer unit. They can be ordered separately for customer stocking and/or field assemblyor as a complete factory-assembled unit.
SwitchS-Series temperature switch units incorporate theunique ASCO TRI-POINT alternating fulcrum balanceplate to control the operation of one or more electricalsnap-action swtiches. The electrical snap-action switchtogether with the adjusting mechanism is a fully-tested,self-contained subassembly.
TransducerThe temperature transducer unit uses a vapor pressureprinciple where the internal pressure within the unit isgenerated by the vapor pressure of a chemical within asealed system. Temperature transducers are availablein two constructions, a direct mount or capillary andbulb construction. The direct mount unit includes a 1/2”NPT connection for direct mounting to the process. Thecapillary and bulb construction allows remote mounting
Standard Electrical Ratings
Switches for -60 through 640°F with Adjustable Set Points,Fixed or Adjustable Deadband and General Purpose,Watertight or Explosion-Proof Enclosures
SA, SB, SC, SD and SE Series15 Amp Res., 125 VAC10 Amp Res., 250 VAC1/8 HP, 125 VAC1/4 HP, 250 VAC1/2 Amp Res., 125 VDC1/4 Amp Res., 250 VDC
^ %SPDT
NO
NC
C
Standard Temperature Ratings
Ambient: -4°F (-20°C) to 140°F (60°C)Fluid: See specification table on page 32
for rated overrange temperature.
from the process. The transducer unit (like the switchunit) is a fully-tested, self-contained subassembly.
OperationTemperature sensed by the bulb creates an internalpressure within the transducer. This pressure is thenconverted into movement of the piston. This pistonmovement is then used to control the operation of the electrical snap-action switch in the switch unit.
Options (See pages 34-35)
4 123
EnclosuresASCO TRI-POINT S-Series switches are available inthree standard enclosures. All of these enclosed unitsare made in accordance with NEMA and UL standards.
General Purpose – Type 1. These enclosures aredesigned for indoor use to protect personnel fromaccidental contact with the equipment. S-Series general purpose switch units consist of a copper-free*aluminum die-cast body with a formed copper-free* aluminum cover; two 3/4” conduit hubs with one plugare provided.
Watertight – Type 4. Watertight and dust-tight enclo-sures are intended for use indoors and outdoors to protect the enclosed equipment against splashing orfalling water, windblown dust and water, hose directedwater, and severe external condensation. S-Serieswatertight switch units have a copper-free* aluminumdie-cast body and a formed copper-free* aluminumcover with Buna “N” gaskets; two 3/4” conduit hubs with one plug are provided.
Explosion-Proof – Types 7 and 9. Type 7 enclosuresare intended for use in locations defined by the NationalElectrical Code as Class I. Type 9 enclosures areintended for Class II locations.
Class I locations are those in which flammable gasesare or may be present in the air in sufficient quantitiesto produce explosive or ignitable mixtures. Class Ilocations are classified by group letter, which definesparticular atmospheres. Division 1 locations are areaswhere the hazardous concentration exists continuously,intermittently or periodically under normal operatingconditions. Division 2 locations are those where thehazardous vapors are present only in case of acciden-tal rupture or breakdown of equipment.
ASCO TRI-POINT explosion-proof enclosures with letter B, C or D in the fifth position are listed for Class I,Groups B, C, and D, Division 1. They are also suitablefor the less stringent Division 2 environment.
Class II locations are those which are hazardousbecause of the presence of combustible dust. All ASCO TRI-POINT explosion-proof enclosures are listed for Groups E, F, and G locations.
The switch body and cover are die-cast copper-free*aluminum with a Buna “N” gasket. Two 3/4” conduithubs with one plug are provided.
Dimensions (inches)
* Less than 0.6% copper.
2.2
1.03
4.13.5
3.2
3.8
11.6
8.9
1.0
4.0
1.6 2.3
11/32 DIA. FORMOUNTING(2PLACES)
3/4 NPT FORCONDUIT CONN.BOTH ENDS
ADDITIONAL SPACE REQUIREDFOR REMOVAL OF COVER
1/2 NPT
3.8DIA.
S-SeriesTemperature
With Direct Mount Transducer With Capillary and Bulb Transducer
31
32 33
Two-Stage Fixed Deadband Transducer Units
S-SERIES Temperature Switches
How to OrderFactory assembled – Simplyorder the switch and transducerunit by catalog number joined by a slash (/), e.g., SA10D/QA10A1.Field assembled – Simply order the switch and transducerunits separately by individual catalog number, e.g., one SA10D and one QA10A1.Options – Add appropriatesuffix for desired option(see pages 34-35).
Important Note: The third digitof each of the catalog numbersmust be identical,e.g., SA 1 0D and QA 1 0A1.
How to Select and OrderASCO S-Series switches consist of two components, the switch unit and the transducer unit.
How to Select1. Select the adjustable operating range based on desired actuation temperature.2. Check that rated overrange temperature is sufficient.3. Read across and select the desired S-Series switch unit with the proper enclosure.4. Continue across and select a matching transducer unit compatible with the fluid.
Single-Stage Adjustable Deadbandunits allow independent adjustment ofthe set and reset points over the fulloperating range of the switch. Theminimum difference between set andreset points is thedeadband listedbelow; themaximumdifference is thefull range of theswitch .
SB Switch Unit: Single-Stage FixedDeadband units have an adjustable set pointand a non-adjustable automatic reset point.SD Switch Unit: Manual reset on decreasingtemperature units operate automatically onincreasing temperature and must be reset manually on decreasing temperature.(To order, change second digit to letter “D”,e.g., S B 40D becomes S D 40D).SE Switch Unit: Manual reset on increasingtemperature units operate automatically ondecreasing temperature and must be resetmanually on increasing temperature.(To order, change second digit to letter “E”,e.g., S B 40D becomes S E 40D).
SA Switch Unit SB, SD or SE Switch Unit SC Switch Unit
General Purpose
Specifications Adjustable Deadband Fixed Deadband or Manual Reset
All switch units above are in stock for immediate delivery.
Values shown are nominal.1
All switch units and transducer units above are in stock for immediate delivery.
AdjustableOperating
Range(°F)
RatedOverrange
Temperature (°F)
Minimum AtMid-Range
(°F)
AdjustableDeadband
MaximumFull Scale
CatalogNo.
DirectMount Copper SS
GeneralPurpose
WatertightEnclosure
Explosion-Proof
CatalogNo.
CatalogNo.1
FixedDeadband
AtMid-Range
(°F) 1
FixedDeadband
AtMid-Range
(°F) 1
Minimum AtMid-Range
(°F)
Separation
MaximumFull Scale
1
CatalogNo.
GeneralPurpose
WatertightEnclosure
Explosion-Proof
CatalogNo.
CatalogNo.
CatalogNo.
GeneralPurpose
WatertightEnclosure
Explosion-Proof
CatalogNo.
CatalogNo.
250260260260260------------
250300350450500550550550550
250300350450500600700800890
88889
12121832
33333667
20
4444488
1027
88889
12121832
SA10DSA10DSA10DSA10DSA10DSA10DSA10DSA10DSA10D
SA11DSA11DSA11DSA11DSA11DSA11DSA11DSA11DSA11D
SA12DSA12DSA12DSA12DSA12DSA12DSA12DSA12DSA12D
SC10DSC10DSC10DSC10DSC10DSC10DSC10DSC10DSC10D
SC11DSC11DSC11DSC11DSC11DSC11DSC11DSC11DSC11D
SC12DSC12DSC12DSC12DSC12DSC12DSC12DSC12DSC12D
SB10DSB10DSB10DSB10DSB10DSB10DSB10DSB10DSB10D
SB11DSB11DSB11DSB11DSB11DSB11DSB11DSB11DSB11D
SB12DSB12DSB12DSB12DSB12DSB12DSB12DSB12DSB12D
CatalogNo.
316 SS
316 SS(Plain
Capillary)
Copper(ArmoredCapillary)
Copper(ArmoredCapillary)
316 SS &(Plain
Capillary)
CatalogNo.
CatalogNo.
QB10A4QD10A4QF10A4QJ10A4QL10A4
------------
CatalogNo.
QB11A1QD11A1QF11A1QJ11A1QL11A1QN11A1QT11A1QU11A1
---
CatalogNo.
QB11A4QD11A4QF11A4QJ11A4QL11A4QN11A4QT11A4QU11A4QW11A4
CatalogNo.
Copper
12’ Capillary and Bulb6’ Capillary and BulbDirect Mount
QB10A1QD10A1QF10A1QJ10A1QL10A1
------------
QB11A1DQD11A1DQF11A1DQJ11A1DQL11A1DQN11A1DQT11A1DQU11A1D
---
QB11A4DQD11A4DQF11A4DQJ11A4DQL11A4DQN11A4DQT11A4DQU11A4DQW11A4D
-30 - 600 - 90
50 - 160100 - 220160 - 260225 - 340300 - 450350 - 510425 - 640
Two-Stage Fixed Deadband units consist of twoseparate snap-action switches, each with anindependently adjustable set point and non-adjustablereset point. The difference between the set and resetpoints of each switch is thedeadband listed below; theminimum difference betweenthe set points of the twoswitches is the separation.
Explosion Proof
Select transducer unit below
Transducer Unit
The temperature transducer works on the vapor principle wherethe internal pressure within the system is generated by the vaporpressure of a chemical within a sealed system. The temperaturesensed by the bulb is related uniquely to an internal pressurewithin the system. The pressure acts on a diaphragm/piston tocreate the force output from the transducer into the switch unit.Temperature transducers are available in two constructions. Thedirect mount (local) unit includes a 1/2” NPT connection fordirect application to the process. The capillary and bulb-typeconstruction allows for remote mounting from the process.
Direct Mount1/2” NPT
Capillaryand Bulb
4 123
°C = (°F -32) x 5/9
Capillary
Select S-Series temperature switch SA, SB, SC, SD or SE unit below
32 33
Two-Stage Fixed Deadband Transducer Units
S-SERIES Temperature Switches
How to OrderFactory assembled – Simplyorder the switch and transducerunit by catalog number joined by a slash (/), e.g., SA10D/QA10A1.Field assembled – Simply order the switch and transducerunits separately by individual catalog number, e.g., one SA10D and one QA10A1.Options – Add appropriatesuffix for desired option(see pages 34-35).
Important Note: The third digitof each of the catalog numbersmust be identical,e.g., SA 1 0D and QA 1 0A1.
How to Select and OrderASCO S-Series switches consist of two components, the switch unit and the transducer unit.
How to Select1. Select the adjustable operating range based on desired actuation temperature.2. Check that rated overrange temperature is sufficient.3. Read across and select the desired S-Series switch unit with the proper enclosure.4. Continue across and select a matching transducer unit compatible with the fluid.
Single-Stage Adjustable Deadbandunits allow independent adjustment ofthe set and reset points over the fulloperating range of the switch. Theminimum difference between set andreset points is thedeadband listedbelow; themaximumdifference is thefull range of theswitch .
SB Switch Unit: Single-Stage FixedDeadband units have an adjustable set pointand a non-adjustable automatic reset point.SD Switch Unit: Manual reset on decreasingtemperature units operate automatically onincreasing temperature and must be reset manually on decreasing temperature.(To order, change second digit to letter “D”,e.g., S B 40D becomes S D 40D).SE Switch Unit: Manual reset on increasingtemperature units operate automatically ondecreasing temperature and must be resetmanually on increasing temperature.(To order, change second digit to letter “E”,e.g., S B 40D becomes S E 40D).
SA Switch Unit SB, SD or SE Switch Unit SC Switch Unit
General Purpose
Specifications Adjustable Deadband Fixed Deadband or Manual Reset
All switch units above are in stock for immediate delivery.
Values shown are nominal.1
All switch units and transducer units above are in stock for immediate delivery.
AdjustableOperating
Range(°F)
RatedOverrange
Temperature (°F)
Minimum AtMid-Range
(°F)
AdjustableDeadband
MaximumFull Scale
CatalogNo.
DirectMount Copper SS
GeneralPurpose
WatertightEnclosure
Explosion-Proof
CatalogNo.
CatalogNo.1
FixedDeadband
AtMid-Range
(°F) 1
FixedDeadband
AtMid-Range
(°F) 1
Minimum AtMid-Range
(°F)
Separation
MaximumFull Scale
1
CatalogNo.
GeneralPurpose
WatertightEnclosure
Explosion-Proof
CatalogNo.
CatalogNo.
CatalogNo.
GeneralPurpose
WatertightEnclosure
Explosion-Proof
CatalogNo.
CatalogNo.
250260260260260------------
250300350450500550550550550
250300350450500600700800890
88889
12121832
33333667
20
4444488
1027
88889
12121832
SA10DSA10DSA10DSA10DSA10DSA10DSA10DSA10DSA10D
SA11DSA11DSA11DSA11DSA11DSA11DSA11DSA11DSA11D
SA12DSA12DSA12DSA12DSA12DSA12DSA12DSA12DSA12D
SC10DSC10DSC10DSC10DSC10DSC10DSC10DSC10DSC10D
SC11DSC11DSC11DSC11DSC11DSC11DSC11DSC11DSC11D
SC12DSC12DSC12DSC12DSC12DSC12DSC12DSC12DSC12D
SB10DSB10DSB10DSB10DSB10DSB10DSB10DSB10DSB10D
SB11DSB11DSB11DSB11DSB11DSB11DSB11DSB11DSB11D
SB12DSB12DSB12DSB12DSB12DSB12DSB12DSB12DSB12D
CatalogNo.
316 SS
316 SS(Plain
Capillary)
Copper(ArmoredCapillary)
Copper(ArmoredCapillary)
316 SS &(Plain
Capillary)
CatalogNo.
CatalogNo.
QB10A4QD10A4QF10A4QJ10A4QL10A4
------------
CatalogNo.
QB11A1QD11A1QF11A1QJ11A1QL11A1QN11A1QT11A1QU11A1
---
CatalogNo.
QB11A4QD11A4QF11A4QJ11A4QL11A4QN11A4QT11A4QU11A4QW11A4
CatalogNo.
Copper
12’ Capillary and Bulb6’ Capillary and BulbDirect Mount
QB10A1QD10A1QF10A1QJ10A1QL10A1
------------
QB11A1DQD11A1DQF11A1DQJ11A1DQL11A1DQN11A1DQT11A1DQU11A1D
---
QB11A4DQD11A4DQF11A4DQJ11A4DQL11A4DQN11A4DQT11A4DQU11A4DQW11A4D
-30 - 600 - 90
50 - 160100 - 220160 - 260225 - 340300 - 450350 - 510425 - 640
Two-Stage Fixed Deadband units consist of twoseparate snap-action switches, each with anindependently adjustable set point and non-adjustablereset point. The difference between the set and resetpoints of each switch is thedeadband listed below; theminimum difference betweenthe set points of the twoswitches is the separation.
Explosion Proof
Select transducer unit below
Transducer Unit
The temperature transducer works on the vapor principle wherethe internal pressure within the system is generated by the vaporpressure of a chemical within a sealed system. The temperaturesensed by the bulb is related uniquely to an internal pressurewithin the system. The pressure acts on a diaphragm/piston tocreate the force output from the transducer into the switch unit.Temperature transducers are available in two constructions. Thedirect mount (local) unit includes a 1/2” NPT connection fordirect application to the process. The capillary and bulb-typeconstruction allows for remote mounting from the process.
Direct Mount1/2” NPT
Capillaryand Bulb
4 123
°C = (°F -32) x 5/9
Capillary
Select S-Series temperature switch SA, SB, SC, SD or SE unit below
34
OPTIONS Pressure/Temperature Switches
H-Series, P-Series and S-SeriesSnap-Action Switch OptionsOptional snap-action switches to meet specific electrical loadsor application conditions are available on most ASCO TRI-POINTswitch units. Generally, the construction of a switch unit withoptional snap-action switches contains other specific parts andmay be ordered only as a factory-built unit. To specify a particularoptional construction, add the appropriate suffix to the switch unitcatalog number, e.g., SA10D with optional gold contact snap-action switch (suffix “P”) would become SA10D P .
P-SeriesSwitch OptionsPanel Mount – Open frame P-Series compact switch units areavailable for panel mounting with the switch unit inside and thetransducer outside. The panel separates the fluid sensing portionfrom the electromechanical portion. Five holes for bolts andoperating stem must be drilled or punched through the panel.Three constructions are available: add the suffix listed below tothe switch unit catalog number for the desired thickness.
S-SeriesSwitch OptionsIndustrial Adjusting Nut Covers –Available in clear plastic or metal toprevent tampering with set pointadjusting nuts.Clear plastic cover: To order, addsuffix “1” to the switch unit catalognumber, or order separately as SP01.Metal cover: To order, add suffix “2” tothe switch unit catalog number, ororder separately as SP02.JIC Construction – A switch unithaving the electrical and adjusting nutcovers attached to the switch body bya chain. Also designed to Type 13specifications. To order, add suffix “3”to the switch unit catalog number, ororder separately as SP03.Terminal Block – Applicable to switchunits with one single-poledouble-throwswitch. The terminal strip is prewiredto the snap-action switch. To order, addsuffix “4” to the switch unit catalognumber, or order separately as SP04.Factory Sealed – Explosion-proofunits may be ordered with a factoryseal separating the electrical chamberfrom the conduit hubs and 24” long#14 AWG 105°C. rated lead wires. Toorder, change the fourth digit of theswitch unit catalog number from “2” to“3”, e.g., SA1 2 D becomes SA1 3 D.
CatalogSuffix
Deadband VariationFrom ListingElectrical RatingDescription
SuffixPanel Thickness
10 Ga (.135+.005)14 Ga (.075+.005)16 Ga (.060+.005)
101112
5 Amp, 125, 250 VAC1/4 HP, 125 VAC1/2 HP, 250 VAC1 Amp, 125 VDC1/2 Amp, 250 VDC
10 Amp, 125 VAC, VDC1/8 HP, 125 VAC, VDC
5 Amp, 125, 250 VAC1/8 HP, 125 VAC1/4 HP, 250 VAC1/2 Amp, 125 VDC1/4 Amp, 250 VDC1 Amp, 28 VAC1 Amp, 28 VDC25 Amp Res, 28 VDC10 Amp Ind, 28 VDC5 Amp Motor, 28 VDC3 Amp Lamp, 28 VDC1 Amp, 125 VAC5 Amp, 125, 250 VAC1/8 HP, 125 VAC1/4 HP, 250 VAC1/2 Amp, 125 VDC1/4 Amp, 250 VDC20 Amp, 125, 250 VAC1 HP, 125 VAC2 HP, 250 VAC1/2 Amp, 125 VDC1/4 Amp, 250 VDC5 Amp, 125, 250 VAC1/8 HP, 125 VAC1/4 HP, 250 VAC1/2 Amp, 125 VDC1/4 Amp, 250 VDC5 Amp, 125, 250 VAC1/8 HP, 125 VAC1/4 HP, 250 VAC1/2 Amp, 125 VDC
SA: +50%SB, SC, PA: +100%
H: +200%PB: +400%SA: +50%
SB, SC, PA: +100%H: +120%
PB: +400%
SA, SB, SD, SE, PB: +50%
SA, SB, SC, PA: +25%H: +50%
PB, PC: +100% SA, PA: +100%
H: +200%PB: +600%
SA, SB, SC: +25%
SA: +50%SB, SC: +100%
PB: +400%
SA: NoneSB, SC, PA: +25%
PB, H: +50%
SB, SC: -50%
DC Rating1 Amp
Double Break
DC Rating10 Amps, SPDT
Double-poleDouble-throw(Two SPDT
Switches withCommon Lever)
Gold ContactDry Circuit SPDT
HermeticallySealedSPDT
High Ambient250°FSPDT
High Power1 HPSPDT
MoistureResistant
Sealed SwitchSPDT
TightFixed
DeadbandSPDT
G
M
K
P
H
F
W
J
T
35
4 123
Pressure Transducer Options
P-Series and S-Series Temperature Transducer Options
Special Wetted Materials – The following diaphragms maybe substituted on transducer body materials of aluminum,
material code below in the seventh digit of the transducer
becomes a TF10A1 2 .
Oxygen Cleaning – Pressure transducers for oxygen serviceshould be specially cleaned. They are degreased and blacklightinspected, then assembled in a clean area and tested with
neoprene diaphragm and add suffix “H” to transducer catalognumber, e.g., TA40A13 becomes TA40A13 H .
Pressure Snubbers – A pressure snubber (1/4” NPTF by1/4” NPTM) installed in the transducer pressure connectionwill dampen the pressure spikes to a value which will notcause damage. It consists of a body with a porous metal discof stainless steel through which the fluid passes. To order,select a snubber compatible with the fluid. Available byseperate catalog number only (see table below).
Process Connection – A female process connection (1/4”NPT) is standard on all pressure transducers. A 1/2” NPT isavailable as an option on gauge pressure transducers. Toorder, add suffix “B” to transducer catalog number, e.g.,RF10A21 becomes RF10A21 B .Note: Not available on nylon transducers.
Armored Capillaries – Double braided copper armor isstandard for copper capillary units. Stainless steel spiralinterlocked armor is available for stainless steel capillaryunits. Add suffix “C” to transducer catalog number.
Thermal Well – Use with direct or remote sensors for protecting sensing bulb. This allows removal of bulb while maintaining a pressure-tight vessel. Available in 1/2” NPT or 3/4”NPT process connection in brass or 316 SS. Dimensions are inaccordance with SAMA Std. RC17-9. Standard “U” dimension(insertion length) is 2-1/2” for direct mount and 6’ capillary unitsand is 4-1/2” for 12’ capillary units.
Longer Capillaries – Standard copper and stainless steelcapillary units can be furnished in 12’ lengths. To order, addsuffix “D” to transducer catalog number. Consult ASCO for longer length capillaries.
Union Connector – For use with remote units for mountingof bulb in fluid being controlled. Available in 1/2” NPT and3/4” NPT process connections in brass or 316 SS.
MaterialCodeDiaphragm Temperature Range
Buna “N”Ethylene Propylene
NeopreneFluorosilicone
-4°F (-20°C) to 180°F (82°C)-4°F (-20°C) to 250°F (121°C)-4°F (-20°C) to 180°F (82°C)-40°F (-40°C) to 250°F (121°C)-4°F (-20°C) to 250°F (121°C)
16372
BrassCatalog No.
303 SSCatalog No.Fluid
Air, Non-Hazardous GasesWater, Light Oil (under 225 SSU)
Oil (Heavy, (over 225 SSU)Pressure Rating (psig)
TP04G3TP04E3TP04D3
5000
TP04G2TP04E2TP04D2
2000
BulbLength(Inches)
TransducerSuffix
“U” DimensionRequired(Inches)
CapillaryLength(Feet)
612
13 - 2021 - 5051 - 80
3-1/25-1/25-1/28-1/2
11-1/2
2-1/24-1/24-1/27-1/2
10-1/2
---DEFG
PressureRating(psig) Catalog No. Catalog No.
3/4” NPT1/2” NPT
Process Connection
Material
Brass316 SS
QP01QP05
QP02---
5001500
PressureRating(psig)
“U”Dimensions
(Inches) Catalog No. Catalog No.
3/4” NPT1/2” NPT
Process Connection
Material
Brass
316 SS
QP03QP13QP23QP33QP07QP17QP27QP37
QP04QP14QP24QP34QP08QP18QP28QP38
1000
6000
2-1/24-1/27-1/2
10-1/22-1/24-1/27-1/2
10-1/2
Thermal Well
Jam nuts provided with thermal wells.1
1
FKM
brass, polyester and stainless steel. To order, substitute the
catalog number, e.g., a TF10A1 1 with optional FKM diaphragm
oil-free air or nitrogen. Use metal body transducer with FKM or
Switch Unit – ASCO uses the term “switch unit” to describethe electromechanical portion of a pressure or temperatureswitch. This is used in conjunction with a transducer unit toform a complete pressure or temperature switch.
Transducer Unit – ASCO uses the term “transducer unit” todescribe that portion of a pressure or temperature switch towhich a pressure or temperature is applied which convertsthe input signal to another form of energy to operate theswitch unit.
Two-Stage (Dual) – ASCO uses the term “two stage” todescribe a pressure or temperature switch which is equivalentto two pressure or temperature switches which areindependently adjustable. This switch is equivalent to twofixed deadband switches.
Deadbands – The deadband is the difference between theset point and reset point readings. Deadbands are listedin the specification tables at nominal values. They are representative of the deadbands of the units at the middleof the range.
The deadband values for the full range adjustable deadbandswitches and limited adjustable deadband switches indicatethe values through which the deadband may be adjusted.
Generally, as the set point is adjusted through the operatingrange, the deadband will vary. Normally, it will becomenarrower as the set point is towards the bottom of the range,and will become wider when the set point is towards the topof the range. The graph shown below indicates representativetrends of this type of deadband variation.
Temperature switch deadbands are a result of the characteris-tics of the vapor pressure curve as well as other factors.Normally, this results in a deadband which is narrower in thetop third of the range than in the bottom third of the range.The values published are nominal and representative of mid-range set points.
36
Definitions and Fluid Compatibility Guide
Accuracy – The maximum deviation from the set pointunder specified operating condition (ambient temperature,barometric pressure, etc.).
Adjustable Deadband – Refers to the capability of apressure or temperature switch to allow the deadband to beadjusted over a given range. Certain ASCO TRI-POINTswitches have an adjustable deadband which can beadjusted over the total operating range of the switch.
Adjustable Operating Range – The pressure or tempera-ture range of the switch within which the set point may beadjusted.
Differential Pressure – The difference between twopressures. A differential pressure switch senses two pressuresources and can be adjusted to actuate on a desireddifference between them.
Guage Pressure – The actual reading of a typical pressureguage and is the difference between the pressure within avessel and the atmospheric pressure surrounding it. It isnormally measured in pounds per square inch (psig).
Manual Reset – The switch is a semi-automatic devicewhich operates automatically with a signal change in onedirection but must be manually reset once the signal returnsto its original position.
Proof Pressure – A pressure which a device can besubjected to for extended periods of time without changesin its operating characteristics.
Rated Overrange Temperature – A temperature which adevice can be subjected to for extended periods of timewithout changes in its operating characteristics.
Repeatability – The closeness of agreement among anumber of consecutive measurements of the output for thesame value of input under the same operating conditionsapproaching from the same direction. Repeatability isnormally specified as a percentage of the upper limit of theoperating range.
Example: Operating range 5-100 psig with +1%repeatability; equals +1% of 100 psig or +1 psig.
Reset Point – After a pressure or temperature switch hasreached its set point and operated the electrical switch, itmust return to a point called the reset point before theelectrical switch can return to its original position.
Set Point – The pressure reading at which the electricalswitch element changes contact position (it can be specifiedeither increasing or decreasing).
Definitions
Deadbands
1.5 x CatalogValue
CatalogValue
Half CatalogValue
Bottom Mid Top
Position of Set Point in Range
37
4 123
These recommendations are to be used as a guide only, as servicelife of material is dependent on temperature, concentrations, orcatalysts that may be added and other conditions which arebeyond our control.Consult ASCO for specific service applications.
Note: Items in black circles are standard catalog units.All others available on factory order.
P - Indicates preferred construction. S - Indicates satisfactory construction.
Transducer Material Code of Two Digits represents process connectionmaterial and diaphragm material, respectively; these are the sixth andseventh positions of the pressure transducer catalog number.
Process Connection: 6th Position Diaphragm: 7th Position
1 Aluminum 4 316 S.S. 1 Buna “N” 4 316 S.S.2 Brass 7 Nylon/Brass 6 Ethylene Propylene3 303 S.S. 3 Neoprene 7 Fluorosilicone
Fluid Compatibility Guide
Acetic Acid
Acetylene
Air
Ammonia
Argon-Welding
Benzene-Benzol
Butane
Carbon Tetrachloride
Cellulube
Coke Oven Gas
Ethyl Alcohol (denatured)
Ethylene Glycol
Freon Refrigerants
Freon Solvents
(“MF”, “TF”, “BF”)
Fuel Oils and Diesel
Gasoline
Gas, Inert
Gas (natural and
manufactured)
Helium
Hydrogen
Jet Fuel (JP1 to JP6)
Kerosene
Methyl Alcohol (Methanol)
Naphtha
Nitrogen
Oils (coolant, hydraulic,
lubricating and motor)
Oxygen, Gaseous
Potassium Sulfate
Propane Gas and Liquid
“Pydraul” (“Monsanto”)
Steam
Steam Condensate
Stoddard Solvent
Toluene (Tolulo)
Vacuum
Vegetable Oil
Vinegar
Water, Fresh, Boiler Feed
Water (Distilled, Deionized,
Demineralized)
Water, Sea
Material Code 11YesYes400
12YesYes400
13YesYes400
16YesYes400
17YesYes400
21YesNo
3500
22YesNo
3500
23YesNo
3500
26YesNo
3500
27YesNo
3500
31YesYes8000
32YesYes8000
33YesYes8000
36YesYes8000
37YesYes8000
42YesYes8000
44NoNo400
71NoNo200
VacuumInches of WaterP.S.I.G. to R
ang
esA
vaila
ble
For high purity applications use stainless steel transducers.Notes: 1 Oxygen service requires special cleaning, specify suffix “H”.2 For steam service a condensate loop (pigtail) is required.3
For pressure transducers for combustion service see pages 20-23.4 Material availability refers to standard gauge pressure constructions only.5
5
1
2
3
4
4
PP
P
P
PP
P
P
P
PP
PPPP
P
PP
P
PP
S
S
S
SS
P
S
S
S
SS
SSSS
S
SS
PPS
S
P
SS
SPS
P
SS
S
S
S
SSPS
SS
S
SSSP
SPSS
S
S
SS
S
S
SS
S
S
PSS
SS
SS
S
S
SS
S
SS
S
S
S
S
S
S
S
S
S
S
S
S
S
SS
S
SS
S
SSS
S
SS
S
S
S
S
SSSS
SS
S
SSSSSSSSS
S
S
S
SS
S
S
SS
S
S
SSS
S
S
S
S
SS
S
SS
S
S
S
SS
S
S
S
S
S
S
S
S
S
S
S
SS
SSS
S
S
S
S
S
SS
S
S
S
S
SS
SSSS
S
SS
SSS
SS
S
P
SS
SSSPSPSS
S
S
S
S
SSSS
SS
S
SSSSSSSSSSSS
S
SS
S
SS
S
S
SS
S
S
SSS
SS
S
S SSS
S
S
SS
S
SS
S
S
S
SS
S
SS
S
S
S
S
S
S
S
S
S
S
SS
SSS
SSSS
S
SS
SSSPSPSS
S
S
S
S
SSS
SSS
S
SSSSSSSSSSSS
S
SP
SPSSSSSSSSP
S
SPS
S
SSSSSSS
S
SSSSSSSS
SPS
S
S
P
P
P
P
P
P
P
P
2 FKM
Desde1963
Proveedor Integral de Soluciones para
la Industria
INTERRUPTORES Y SENSORES DE PRESION Y
TEMPERATURA
INTERRUPTORES Y SENSORES DE PRESION Y TEMPERATURA
Los interruptores ASCO Tripoint, utilizan la tecnología de diafragma/pistón para un sensado preciso de presión y temperatura, garantizado un excelente tiempo de vida. Los materiales de fabricación son diversos y dependen de fluido a manejar.
Los SENSORES ASCO son maquinados en una sola pieza (cuerpo y diafragma) para eliminar los problemas ocasionados por el desgaste de partes internas, garantizando así el tiempo más largo del mercado.
Sensores ASCO
Sensors4
Stainless steel
Leak proof, one piece cavity design
Available for hazardous locations
Broad industrial pressure range
Series 40 Isolated Pressure Sensor 1
Series 42 Panel Mount Isolated Pressure Sensor 3
Series 43 Hazardous Locations Isolated Pressure Sensor 5
Series 44 Intrinsically Safe Isolated Pressure Sensor 7
Series 45 Tank Level Sensor 9
Series 46 Explosionproof Pressure Sensor 11
Series 47 High Accuracy Pressure Sensor 13
Series 50 Wet/Wet Differential Pressure Sensor 15
No Leak Path Design• Pressure cavity is one piece
(17.4 PH stainless steel) construction
• Pressure sensing surface is integral to body – no separate diaphragm
• Excellent isolation, over-pressure, and burst characteristics
• No fill fluids utilized
Sensing Element• Sensor elements are bonded with inorganic
material to provide low drift repeatable signal
• Sensor technology provides high sensitivity permitting thicker cavities
• MEM's technology
• Wide operating temperature range
• Ranges up to 10,000 psig
• Rugged construction for harsh environments
ASCO, the leader in the design and manufacture of
solenoid valves, now offers a complete line of Pressure
Sensors. With pressure ratings up to 10,000 psig and the
ability to handle difficult applications like steam and
refrigeration, ASCO Pressure Sensors will meet your
most demanding needs. The ASCO Pressure
Sensor line is ideal for accurately measuring
many process fluids in the most demanding,
pulsating, and vibrating environments.
The one piece pressure cavity is machined from
17.4 PH stainless steel, which offers no source for
contamination of the process fluid or the sensor.
This design provides the stability, accuracy, flexi-
bility, and EMI resistance that your process
needs. This single, machined, pressure cavity
will also allow you to handle a wide variety of
applications, thus standardizing on fewer
sensors, as well as reducing your inventory.
ASCO Pressure Sensors demonstrate
ASCO's commitment to the most reliable
flow control solutions.
Sensors4
INDEX PAGE
1
Series40
Features
• High strength stainless steel construction
• No silicone oil, no internal o-rings, no welds
• Wide operating temperature range
• Ranges up to 10,000 psig
• Rugged design survives harsh environments
• Compatible with wide range of gases and liquids
• Suitable for high shock and vibration applications
Specifications
1 Accuracy includes: Non-linearity, Hysteresis, and Non-repeatability
* Typical Ranges. All ranges between 0-25 psig and 0-10,000 psig are available. Please consult factory.
+ Vacuum calibration available. Please consult factory.Specifications are subject to change without notice.
Performance @ 25˚C (77˚F)
Accuracy1 <±0.5% BFSL
Stability (1 year) ±0.25% FS, typ.
Proof Pressure 2X Rated Pressure
Burst Pressure 5X or 20,000 psig, whichever is less
Pressure Cycles > 100 Million
Environmental Data Temperature
Operating -40 to 85˚C (-40 to 185˚ F)
Storage -40 to 100˚C (-40 to 212˚ F)
Thermal Limits
Compensated Range 0 to 55˚C (30 to 130˚ F)
TC Zero <±1.5% of FS (<±3.0% for 0-25 psig)
TC Span <±1.5% of FS
Other
Shock 100G, 11msec, 1/2 sine
Vibration 20G Peak, 20 to 2400 Hz
Rating IP-66
EMI/RFI Protection Yes
Pressure Ranges*+
Gage psig
Proofpsig
Burstpsig
PressureRange Code
0-25 50 250 00025
0-50 100 250 00050
0-100 200 500 00100
0-200 400 1,000 00200
0-500 1,000 2,500 00500
0-1,000 2,000 5,000 01000
0-2,500 5,000 12,500 02500
0-5,000 10,000 20,000 05000
0-7,500 15,000 20,000 07500
0-10,000 20,000 20,000 10000
4
Electrical Data Output 4-20mA 1-5VDC, 1-6VDC 0.5-4.5 V ratiometric
Excitation 10-28VDC 10-28VDC 5VDC, reg
Output Impedance
>10k Ohms <100 Ohms, nom. <100 Ohms, nom.
Current Consumption
20mA, typ. <10mA <10mA
Bandwith (-3dB): DC to 250 Hz DC to 1kHz DC to 1kHz
Output Noise: - <2mV RMS <2mV RMS
Zero Offset <±1% of FS <±1% of FS <±1% of FS
Span Tolerance <±2.0% of FS <±1.5% of FS <±1.5% of FS
Output LoadSee load line curve below
10k Ohms, min. 10k Ohms, min.
Reverse Polarity Protection
Yes Yes No
Physical Description Case 304 stainless steel
Electrical Connection Refer to Ordering Information
Wetted Material Refer to Ordering Information
Series 40Stainless Steel Media Isolated Pressure Sensor
2
4 0 - A - 0 0 5 0 0 - B - 3 - E - 0 - 0 0 0
Ordering InformationConstruct a product code using the chart below. (Consult factory for other options)
SeriesType
40Standard
ProcessConnection
X= Special
A= 1/4" MNPT
B= 1/8" MNPT
C= 1/4" BSPP Male
E= 1/2" MNPT
F= 7/16" -20 UNF Male
H= 1/8" FNPT
J= 1/4" FNPT
S= 1/2" FNPT
Pressure Range
XXXXX=Special
Insert pressurerange code from pressurerange chart.
Vacuum = V0000 -14.7psig/-1.01bar
For vacuum replacefirst zero with (V) inpressure code.(Ex. V0500 =Vacuum to 500 psig)
Pressure Unit
X= Special
B= BAR
K= kg/cm2
P= psig
W= Inches of H2Ocolumn
Outputs
X= Special
A= 0-50mV/V
B= 20mV/V
G= 1-10V
T= 3mV/V
1= 10mV/V
2= 0.5-4.5V ratiometric
3= 1-5V
4= 4-20mA
5= 5mV/V
6= 1-6V
ElectricalInterface
X= Special
A= 2ft. cable
B= 4ft. cable
C= 6ft. cable
D= 10ft. cable
E= Mini DIN 43650
F= Packard Metripack 150 3 pin connector
G= 4 pin Molex connector
H= Flex strip 3"
J= 15ft. cable
K= 8ft. cable
M= Bendix military conn.
R= 6 pin Bendix
T= 25ft. cable
WettedMaterial
X= Special
0= 17.4 PH
1= 316 L
2= Inconel
Options
XXX= Special
000= No options
A10= ±0.10 accuracy
A25= ±0.25 accuracy
C01 Calibration 1-9
C10 Calibration 10-49
C50 Calibration 50-up
C0S Cleaned for O2
service
Dimensional Information
Table 1
Output Pin 3 Pin 2 Pin 1
1-5V +V Supply+V Supply
-V Supply-V Supply4-20mA
OutputN/C
Series40
4
3
Features
• High strength stainless steel construction
• No silicone oil, no internal o-rings, no welds
• Wide operating temperature range
• Pressure ranges up to 10,000 psig
• Rugged design survives harsh environments
• Compatible with wide range of gases and liquids
• Suitable for high shock and vibration applications
• Panel up to .3" thick
Performance @ 25˚C (77˚F)
Accuracy1 <±0.5% BFSL
Stability (1 year) ±0.25% FS, typ.
Proof Pressure 2X Rated Pressure
Burst Pressure 5X or 20,000 psig, whichever is less
Pressure Cycles > 100 Million
Environmental Data
Temperature
Operating -40 to 85˚C (-40 to 185˚ F)
Storage -40 to 100˚C (-40 to 212˚ F)
Thermal Limits
Compensated Range 0 to 55˚C (30 to 130˚ F)
TC Zero <±1.5% of FS (<±3.0 % for 25 psig)
TC Span <±1.5% of FS
Other
Shock 100G, 11msec, 1/2 sine
Vibration 10G Peak, 20 to 2000 Hz
EMI/RFI Protection Yes
Rating IP-66 with housing and cable sealonly. IP-54 w/o housing
Pressure Ranges*
Gage psig
Proofpsig
Burstpsig
PressureRange Code
0-25* 50 250 00025
0-50 100 250 00050
0-100 200 500 00100
0-200 400 1,000 00200
0-500 1,000 2,500 00500
0-1,000 2,000 5,000 01000
0-2,500 5,000 12,500 02500
0-5,000 10,000 20,000 05000
0-7,500 15,000 20,000 07500
0-10,000 20,000 20,000 10000
Specifications
1 Accuracy includes: Non-linearity, Hysteresis, and Non-repeatability
Other ranges available, please consult factory. *Output = 5mV/VSpecifications are subject to change without notice.
Series42
4
Physical Description Case 304 stainless steel
Electrical Connection Refer to Ordering Information
Wetted Material Refer to Ordering Information
Electrical Data Output 4-20mA 1-5VDC, 1-6VDC 0.5-4.5 V ratiometric
Excitation 10-28VDC 10-28VDC 5VDC, reg
Output Impedance
>10k Ohms <100 Ohms, nom. <100 Ohms, nom.
Current Consumption
20mA, typ. <10mA <10mA
Bandwith (-3dB): DC to 250 Hz DC to 1kHz DC to 1kHz
Output Noise: - <2mV RMS <2mV RMS
Zero Offset <±1% of FS <±1% of FS <±1% of FS
Span Tolerance <±2.0% of FS <±1.5% of FS <±1.5% of FS
Output LoadSee load line curve below
10k Ohms, min. 10k Ohms, min.
Reverse Polarity Protection
Yes Yes No
Series 42 Panel MountStainless Steel Media Isolated Pressure Sensor
4
Ordering InformationConstruct a product code using the chart below. (Consult factory for other options)
Dimensional Information
NOTE:1. Use Greenlee Punch Unit #60086 to prepare the panel hole. Also available from McMaster-Carr as #3449A65.
Jacketed Cable,2 ft. long, 0.177" dia.
Configuration allows epoxied orTIG welded housing attachment(0.810" ID / 0.875" OD)
4-pin Molex Connector(Mating connector is -Molex p/n 22-01-3047with pins p/n 08-50-0114)
(V+) Supply
(S+) Output
(S-) Output
(V-) Supply
Table 1
Output Pin 3 Pin 2 Pin 1
1-5V +V Supply+V Supply
-V Supply-V Supply4-20mA
OutputN/C
4 2 - H - 0 0 5 0 0 - B - 3 - B - 0 - 0 0 0
SeriesType
42Panel Mount
ProcessConnection
X= Special
H= 1/8" FNPT
S= 1/2" FNPT
Pressure Range
XXXXX=Special
Insert pressure range code from pressurerange chart.
Vacuum = V0000 -14.7psig/-1.01bar
For vacuum replacefirst zero with (V) inpressure code.(Ex. V0500 =Vacuum to 500 psig)
Pressure Unit
X= Special
B= BAR
K= kg/cm2
P= psig
W= Inchesof H2Ocolumn
Outputs
X= Special
A= 0-50mV/V
B= 20mV/V
G= 1-10V
1= 10mV/V
3= 1-5V
4= 4-20mA
5= 5mV/V
6= 1-6V
ElectricalInterface
X= Special
A= 2ft. cable
B= 4ft. cable
C= 6ft. cable
D= 10ft. cable
G= 4 pin Molex connector
H= Flex strip 3"
J= 15ft. cable
K= 8ft. cable
T= 25ft. cable
WettedMaterial
X= Special
0= 17.4 PH
1= 316 L
2= Inconel
Options
XXX= Special
000= No options
A10= ±0.10 accuracy
A25= ±0.25 accuracy
C01 Calibration 1-9
C10 Calibration 10-49
C50 Calibration 50-up
C0S Cleaned for O2
service
Series42
4
5
Features• Class I Div. 2, Groups A, B, C, and D for use
in hazardous locations
• High strength stainless steel construction
• No silicone oil, no internal o-rings, no welds
• Wide operating temperature range
• Ranges up to 10,000 psig
• Rugged design survives harsh environments
• Compatible with wide range of gases and liquids
• Suitable for high shock and vibration applications
Specifications
1 Accuracy includes: Non-linearity, Hysteresis, and Non-repeatability
* Typical Ranges. All ranges between 0-25 psig and 0-10,000 psigare available. Please consult factory.
+ Vacuum calibration available. Please consult factory.Specifications are subject to change without notice.
Performance @ 25˚C (77˚F)
Accuracy1 <±0.25% BFSL
Stability (1 year) ±0.25% FS, typ.
Proof Pressure 2X Rated Pressure
Burst Pressure 5X or 20,000 psig, whichever is less
Pressure Cycles > 100 Million
Environmental Data Temperature
Operating -40 to 85˚C (-40 to 185˚ F)
Storage -40 to 100˚C (-40 to 212˚ F)
Thermal Limits
Compensated Range 0 to 55˚C (30 to 130˚ F)
TC Zero <±1.5% of FS (2.0% for 316L)
TC Span <±1.5% of FS (2.0% for 316L)
Other
Shock 100G, 11msec, 1/2 sine
Vibration 10G Peak, 20 to 2000 Hz
EMI/RFI Protection Yes
Rating IP-66
Physical Description Case 304 stainless steel
Electrical Connection Refer to Ordering Information
Wetted Material Refer to Ordering Information
Pressure Ranges*+
Gage psig
Proofpsig
Burstpsig
PressureRange Code
0-25 50 250 00025
0-50 100 250 00050
0-100 200 500 00100
0-200 400 1,000 00200
0-500 1,000 2,500 00500
0-1,000 2,000 5,000 01000
0-2,500 5,000 12,500 02500
0-5,000 10,000 20,000 05000
0-7,500 15,000 20,000 07500
0-10,000 20,000 20,000 10000
Series43
4
Electrical Data Output 4-20mA 1-5VDC, 1-6VDC 0.5-4.5 V ratiometric
Excitation 10-28VDC 10-28VDC 5VDC, reg
Output Impedance
>10k Ohms <100 Ohms, nom. <100 Ohms, nom.
Current Consumption
20mA, typ. <10mA <10mA
Bandwith (-3dB): DC to 250 Hz DC to 1kHz DC to 1kHz
Output Noise: - <2mV RMS <2mV RMS
Zero Offset <±1% of FS <±1% of FS <±1% of FS
Span Tolerance <±2% of FS <±1.5% of FS <±1.5% of FS
Output LoadSee load line curve below
10k Ohms, min. 10k Ohms, min.
Reverse Polarity Protection
Yes Yes No
Series 43 Hazardous LocationsStainless Steel Media Isolated Pressure Sensor
6
Ordering InformationConstruct a product code using the chart below. (Consult factory for other options)
4 3 - A - 0 0 5 0 0 - B - 3 - L - 0 - 0 0 0
SeriesType
43HazardousLocations
ProcessConnection
X= Special
A= 1/4" MNPT
C= 1/4" BSPP Male
E= 1/2" MNPT
J*= 1/4" FNPT
S*= 1/2" FNPT
* 316L not available for FNPT sizes
Pressure Range
XXXXX=Special
Insert pressure range code from pressurerange chart.
Vacuum = V0000 -14.7psig/-1.01bar
For vacuum replacefirst zero with (V) inpressure code.(Ex. V0500 =Vacuum to 500 psig)
Pressure Unit
X= Special
B= BAR
K= kg/cm2
P= psig
W= Inches of H2Ocolumn
ElectricalInterface
X= Special
F= 55 meter cable
J= 15ft. cable
K= 8ft. cable
L= 2ft. cable w/conduit
M= 4ft. cable w/conduit
N= 6ft. cable w/conduit
P= 10ft. cable w/conduit
T= 25ft. cable
WettedMaterial
X= Special
0= 17.4 PH
1= 316 L
2= Inconel
Options
XXX= Special
000= No options
001= Etched name plate
A10= ±0.10 Accuracy
C01 Calibration 1-9
C10 Calibration 10-49
C50 Calibration 50-up
C0S Cleaned for O2
service
Dimensional Information
Table 1
Output Red Black White
1-5V +V Supply+V Supply
-V Supply-V Supply4-20mA
OutputN/C
Table 1
Output Red Black White
1-5V +V Supply+V Supply
-V Supply-V Supply4-20mA
OutputN/C
Outputs
X= Special
B= 20mV/V
G= 1-10V
1= 10mV/V
2= 0.5-4.5V ratiometric
3= 1-5V
4= 4-20mA 2 wire
5= 5mV/V
6= 1-6V
Series43
4
7
Features
• Class I Div. 1, Groups C&D Intrinsically Safe
• High strength stainless steel construction
• No silicone oil, no internal o-rings, no welds
• Wide operating temperature range
• Ranges up to 10,000 psig
• Rugged design survives harsh environments
• Compatible with wide range of gases and liquids
• Suitable for high shock and vibration applications
Specifications
1 Accuracy includes: Non-linearity, Hysteresis, and Non-repeatability
* Typical Ranges. All ranges between 0-25 psig and 0-10,000 psig are available. Please consult factory.
+ Vacuum calibration available. Please consult factory.Specifications are subject to change without notice.
Performance @ 25˚C (77˚F)
Accuracy1 <±0.25% BFSL
Stability (1 year) ±0.25%FS, typ.
Proof Pressure 2X Rated Pressure
Burst Pressure 5X or 20,000 psig, whichever is less
Wetted Material 17.4 PH S.S. (NACE compatible)(for other material consult factory)
Pressure Cycles > 100 Million
Physical Description Case 304 stainless steel
Electrical Connection Refer to Ordering Information
Wetted Material Refer to Ordering Information
Environmental Data Temperature
Operating -40 to 85˚C (-40 to 185˚ F)
Storage -40 to 100˚C (-40 to 212˚ F)
Thermal Limits
Compensated Range 0 to 55˚C (30 to 130˚ F)
TC Zero <±1.5% of FS (2.0% for 316L)
TC Span <±1.5% of FS (2.0% for 316L)
Other
Shock 100G, 11msec, 1/2 sine
Vibration 10G Peak, 20 to 2000 Hz
EMI/RFI Protection Yes
Rating IP-66
Pressure Ranges*+
Gage psig
Proofpsig
Burstpsig
PressureRange Code
0-25 50 250 00025
0-50 100 250 00050
0-100 200 500 00100
0-200 400 1,000 00200
0-500 1,000 2,500 00500
0-1,000 2,000 5,000 01000
0-2,500 5,000 12,500 02500
0-5,000 10,000 20,000 05000
0-7,500 15,000 20,000 07500
0-10,000 20,000 20,000 10000
Electrical Data Output 4-20mA 1-5VDC, 1-6VDC 0.5-4.5 V ratiometric
Excitation 10-28VDC 10-28VDC 5VDC, reg
Output Impedance
>10k Ohms <100 Ohms, nom. <100 Ohms, nom.
Current Consumption
20mA, typ. <10mA <10mA
Bandwith (-3dB): DC to 250 Hz DC to 1kHz DC to 1kHz
Output Noise: - <2mV RMS <2mV RMS
Zero Offset <±1% of FS <±1% of FS <±1% of FS
Span Tolerance <±2% of FS <±1.5% of FS <±1.5% of FS
Output LoadSee load line curve below
10k Ohms, min. 10k Ohms, min.
Reverse Polarity Protection
Yes Yes No
Series44
4Series 44 Intrinsically Safe
Stainless Steel Media Isolated Pressure Sensor
8
Ordering InformationConstruct a product code using the chart below. (Consult factory for other options)
4 4 - A - 0 0 5 0 0 - B - 3 - B - 0 - 0 0 0
SeriesType
44IntrinsicallySafe
Process Connection
X= Special
A= 1/4" MNPT
B= 1/8" MNPT
C= 1/4" BSPP Male
E= 1/2" MNPT
F= 7/16"-20 UNF Male
H= 1/8" FNPT
J= 1/4" FNPT
S= 1/2" FNPT
Pressure Range
XXXXX=Special
Insert pressurerange code from pressurerange chart.
Vacuum = V0000 -14.7psig/-1.01bar
For vacuum replacefirst zero with (V) inpressure code.(Ex. V0500 =Vacuum to 500 psig)
Pressure Unit
X= Special
B= BAR
K= kg/cm2
P= psig
W= Inches of H2Ocolumn
WettedMaterial
X= Special
0= 17.4 PH
1= 316 L
2= Inconel
Options
XXX= Special
000= No options
A10= ±0.10 accuracy
C01 Calibration 1-9
C10 Calibration 10-49
C50 Calibration 50-up
C0S Cleaned for O2service
Table 1
Output Pin 3 Pin 2 Pin 1
1-5V +V Supply+V Supply
-V Supply-V Supply4-20mA
OutputN/C
Outputs
X= Special
A= 0-50mV/V
B= 20mV/V
G= 1-10V
1= 10mV/V
2= 0.5-4.5V ratiometric
3= 1-5V
4= 4-20mA 2 wire
5= 5mV/V
6= 1-6V
7= 1-5V adj.
8= 4-20mA adj.
9= 1-6V adj.
ElectricalInterface
X= Special
A= 2ft. cable
B= 4ft. cable
C= 6ft. cable
D= 10ft. cable
E= Mini DIN 43650
F= Packard Metripack
J= 15ft. cable
K= 8ft. cable
T= 25ft. cable
Red
Black
Green
White
Red
Red
Black
Black
White
44X0 mV output
44X0 4-20 mA output
44X0 Voltage output
excitation +excitation -
signal +signal -
supply voltagesignalcommon
supply voltage
supply common
common
analog input
Entity Parameters Vmax = 28Vdc Imax = 175mA Imax is the total current available from the Associated C1 = 0.44uf Apparatus under any condition. L1 = 0
Notes:1. Associated Apparatus shall provide intrinsically safe connections which meet the following parameters. Voc or Vt £ Vmax Ca ≥ C1 + Cleads Isc or It £ Imax La ≥ L1 + Lleads
2. Control Room aparatus shall not generate in excess of 250V (Umax).
3. Installation should be in accordance with Article 504 in the National Electrical Code, ANSI/NFPA 70.
Intrinsic SafetyBarrier
3
4
/PA
2
PA/
PA/ /PA
4
3
2
PA/ /PA
4
3
2
PA/ /PA
4
3
2
Intrinsic SafetyBarrier
Intrinsic SafetyBarrier
Intrinsic SafetyBarrier
Ground Bus
I. S. groundconductor
Nonhazardous Location
Ground Bus
I. S. groundconductor
Ground Bus
I. S. groundconductor
Figure 1: Wiring diagram for 4-wire, mV output
Figure 2: Wiring diagram for 2-wire, 4-20mA output
Figure 3: Wiring diagram for 3-wire, Voltage output
Hazardous Location
Hazardous Location
Hazardous Location
Class I, Div. 1, Groups C, DHazardous Location
Nonhazardous Location
Nonhazardous Location
RL
The transducers listed below are designed for installation in a Class I, Division 1, Groups C and D, Division 1 hazardous location when connected to Associated Apparatus as described in note 1.
Dimensional Information
Series44
4
9
4Series
45
Specifications
1 Accuracy includes: Non-linearity, Hysteresis, and Non-repeatability
* Typical Ranges. All ranges between 0-15 psig and 0-100 psig are available. Please consult factory.
Performance @ 25˚C (77˚F)
Accuracy1 <±0.5% BFSL (for higher accuracy, please consult factory)
Stability (1 year) ±0.25%FS, typ.
Over Range Pressure 2X Rated Pressure
Burst Pressure 5X or 1250 psig, whichever is less
Pressure Cycles > 50 Million
Agency Approval UL 508
Environmental Data Temperature
Operating -40 to 85˚C (-40 to 185˚ F)
Storage -40 to 100˚C (-40 to 212˚ F)
Thermal Limits
Compensated Range 0 to 55˚C (-30 to 130˚ F)
Temp. Comp. Zero <±1.5% of FS (<±2.0% for 316L)
Temp. Comp. Span <±1.5% of FS (<±2.0% for 316L)
Other
Shock 100G, 11msec, 1/2 sine
Vibration 10G Peak, 20 to 2000 Hz
Rating IP-68
EMI/RFI Protection Yes
Electrical Data Output 4-20mA 1-5VDC
Excitation 10-28VDC, typ. 10-28VDC, typ.
Output Impedance <10k Ohms <100 Ohms, nom.
Current Consumption 20mA, typ. <10mA
Bandwidth (-3dB) DC to 250Hz DC to 1kHz
Output Noise - <2mV RMS
Zero Offset <±1% of FS <±1% of FS
Span Tolerance <±2% of FS <±1.5% of FS
Output Load See load linecurve below 10k Ohms, min.
Reverse Polarity Yes Yes
Pressure Ranges* Gage
psigProofpsig
Burstpsig
PressureRange Code
0-15 30 125 00015
0-25 50 125 00025
0-30 60 150 00030
0-100 200 500 00100
Physical Description Case 304 stainless steel
Electrical Connection Refer to Ordering Information
Wetted Material Refer to Ordering Information
Features
• High strength stainless steel construction
• No silicone oil, no internal o-rings, no welds
• Wide operating temperature range
• Ranges up to 100 psig
• Rugged design survives harsh environments
• Compatible with wide range of gases and liquids
• Suitable for high shock and vibration applications
Series 45Stainless Steel Tank Level Sensor
10
4 5 - L - 0 0 1 0 0 - B - 3 - C - 1 - 0 0 0
Ordering Information
Construct a product code using the chart below. (Consult factory for other options)
SeriesType
45Standard
ProcessConnection
X= Special
L= Cone Front
PressureRange
XXXXX=Special
Insert pressurerange code from pressurerange chart.
Pressure Unit
X= Special
B= BAR
K= kg/cm2
P= psig
Outputs
X= Special
3= 1-5V
4= 4-20mA
ElectricalInterface
X= Special
C= 6ft. cable
D= 10ft. cable
J= 20ft. cable
K= 25ft. cable
L= 35ft. cable
M= 50ft. cable
N= 100ft. cable
P= 150ft. cable
Hytrel cable available, consult ASCO
WettedMaterial
X= Special
1= 316 L
Options
XXX= Special
000= No options
Dimensional Information
Jacketed Cable,Length Specified
per Order,0.30 dia.
Red (see table 1)
White (see table 1)
Black (see table 1)
Vent Tube
4.43
0.88
Shield
Output Red
1-5V
4-20mA
+V Supply
+V Supply
Table 1
Black White
-V Supply
-V Supply
Output
N/C
4-20mA Load line Curve
Supply Voltage
Line
Impe
danc
e
Series45
4
11
Series46
Features
• High strength stainless steel construction
• No silicone oil, no internal o-rings, no welds
• Wide operating temperature range
• Ranges up to 10,000 psig
• Rugged design survives harsh environments.
• Compatible with wide range of gases and liquids
• Suitable for high shock and vibration applications
Specifications
1 Accuracy includes: Non-linearity, Hysteresis, and Non-repeatability
* Typical Ranges. All ranges between 0-50 psig and 0-10,000 psig are available. Please consult factory.
Performance @ 25˚C (77˚F) Accuracy1 <±0.25% BFSL
Stability (1 year) ±0.25% FS, typ.
Proof Pressure 2X Rated Pressure
Burst Pressure 5X or 25,000 psig, whichever is less
Pressure Cycles > 100 Million
Agency Approval CSA 30 (UL 1203) Class 1, Div. 1Explosionproof, Groups A,B,C & D
Physical Description Case 304 stainless steel
Electrical Connection Refer to Ordering Information
Wetted Material Refer to Ordering Information
Environmental Data Temperature
Operating -40 to 85˚C (-40 to 185˚F)
Storage -40 to 100˚C (-40 to 212˚F)
Thermal Limits
Compensated Range 0 to 55˚C (30 to 130˚ F)
Temp. Comp. Zero <±1.5% of FS
Temp. Comp. Span <±1.5% of FS
Other
Shock 100G, 11msec, 1/2 sine
Vibration 10G Peak, 20 to 2400 Hz
EMI/RFI Protection Yes
Rating IP-66
Electrical Data Output 4-20mA 1-5V, 1-6V
Excitation 10-28VDC, typ. 10-28VDC
Output Impedance <10k Ohms <100 Ohms, nom.
Current Consumption 20mA, typ. <10mA
Bandwidth (-3dB) DC to 250Hz DC to 1kHz
Output Noise - <2mV RMS
Zero Offset <±1% of FS <±1% of FS
Span Tolerance <±2% of FS <±1.5% of FS
Output Load See load linecurve below 10k Ohms, min.
Reverse Polarity Yes Yes
Pressure Ranges* Gage
psigProofpsig
Burstpsig
PressureRange Code
0-50 100 250 00050
0-100 200 500 00100
0-200 400 1,000 00200
0-250 500 1,250 00250
0-500 1,000 2,500 00500
0-1,000 2,000 5,000 01000
0-2,000 4,000 10,000 02000
0-2,500 5,000 12,500 02500
0-5,000 10,000 20,000 05000
0-7,500 15,000 20,000 07500
0-10,000 20,000 20,000 10000
4Series 46
Stainless Steel Explosionproof Pressure Sensor
12
4 6 - A - 0 0 5 0 0 - P - 3 - U - 0 - 0 0 0
Ordering Information
Construct a product code using the chart below. (Consult factory for other options)
SeriesType
46Standard
Process Connection
X= Special
A= 1/4" MNPT
E= 1/2" MNPT
J= 1/4" FNPT
PressureRange
XXXXX=Special
Insert pressurerange code from pressurerange chart.
Pressure Unit
X= Special
B= BAR
K= kg/cm2
P= psig
Outputs
X= Special
3= 1-5V*
4= 4-20mA**
6= 1-6V
* 3 wire caseconnection
** 2 wire 100ppowered andcase conneciton
ElectricalInterface
X= Special
T= 2ft. cable, 18AWG wire
U= 4ft. cable, 18AWG wire
WettedMaterial
X= Special
0= 17.4 PH
1= 316L
2= Inconel 718
Options
XXX= Special
000= No options
Dimensional Information
7/8" Hex
1/2 MNPT
Green, Connectedto housing(see table 1)
Black (see table 1)
White (see table 1)
Red (see table 1)
3.64
1/4 MNPT
Color CodedHookup Wires,
2 ft., 18 ga.
Plasma TIG weldsoffering
ContinuousAir Tight Seal
Output Red
1-5V
4-20mA
+V Supply
+V Supply
Table 1
Black White Green
-V Supply
-V Supply
Output
Not Used
Common
Common
4-20mA Load line Curve
Supply Voltage
Line
Impe
danc
e
Series46
4
13
4Series
47
Features• High strength stainless steel construction
• No silicone oil, no internal o-rings, no welds
• Wide operating temperature range
• Ranges up to 10,000 psig
• Low static and thermal errors
• High accuracy
• Rugged design survives harsh environments
• Compatible with wide range of gases and liquids
• Suitable for high shock and vibration applications
Specifications
1 Accuracy includes: Non-linearity, Hysteresis, and Non-repeatability
* Typical Ranges. All ranges between 0-25 psig and 0-10,000 psig are available. Please consult factory.
+ Vacuum calibration available. Please consult factory.Specifications are subject to change without notice.
Environmental Data Temperature
Operating -40 to 85˚C (-40 to 185˚F)
Storage -40 to 125˚C (-40 to 250˚F)
Thermal Limits
Compensated Range 0 to 55˚C (30 to 130˚ F)
Temp. Comp. Zero <±1.5% of FS (±2.0% for 316L)
Temp. Comp. Span <±1.5% of FS (±2.0% for 316L)
Other
Shock 100G, 11msec, 1/2 sine
Vibration 10G Peak, 20 to 2400 Hz
EMI/RFI Protection Yes
Rating IP-66
Performance @ 25˚C (77˚F) Accuracy1 <±0.25% BFSL (option of ±0.1%)
Stability (1 year) ±0.25%FS, typ.
*Over Range Protection 2X Rated Pressure
*Burst Pressure 5X or 20,000 psig, whichever is less
Pressure Cycles > 100 Million
Physical Description Case 304 stainless steel
Electrical Connection Refer to Ordering Information
Wetted Material Refer to Ordering Information
Pressure Ranges*+
Gage psig
Proofpsig
Burstpsig
PressureRange Code
0-15 30 200 00015
0-25 50 250 00025
0-50 100 250 00050
0-100 200 500 00100
0-200 400 1,000 00200
0-500 1,000 2,500 00500
0-1,000 2,000 5,000 01000
0-2,500 5,000 12,500 02500
0-5,000 10,000 20,000 05000
0-7,500 15,000 20,000 07500
0-10,000 20,000 20,000 10000
Electrical Data
Output 4-20mAVoltage(3 or 4 wire)
Frequency(1-6kHz)
5VDC
Excitation 10-28VDC 10-28VDC 10-28VDC 0-50mV
Output Impedance
-<100 Ohmsnom.
10K, pull up1100 Ohmsnom.
Current Consumption
20mA max. <10mA <15mA <5mA
Bandwidth (-3dB)
DC to 250Hz DC to 1kHz DC to 250HzDC to 5kHzmin.
Output Noise NA <2mV RMS <2mV RMS NA
Zero Offset <±1% of FS <±1% of FS <±1% of FS <±2% of FS
Span Tolerance
<±2% of FS <±1.5% of FS <±1.5% of FS <±2% of FS
Output LoadSee loadline curve
10k Ohmsmin.
10k Ohmsmin.
>1M Ohms
Reverse Polarity Protection
Yes Yes Yes NA
Series 47Stainless Steel High Accuracy Pressure Sensor
14
4 7 - A - 0 0 5 0 0 - P - 3 - B - 0 - 0 0 0
Ordering Information
Construct a product code using the chart below. (Consult factory for other options)
SeriesType
47Standard
ProcessConnection
X= Special
A= 1/4" MNPT
B= 1/8" MNPT
F= 7/16" -20 UNFMale
Pressure Range
XXXXX=Special
Insert pressurerange code from pressurerange chart.
Vacuum = V0000 -14.7psig/-1.01bar
For vacuum replacefirst zero with (V) inpressure code.(Ex. V0500 =Vacuum to 500 psig)
Pressure Unit
X= Special
B= BAR
K= kg/cm2
P= psig
Outputs
X= Special
2= 0-5V (3 wire)
3= 1-5V
4= 4-20mA
5= 0-10V (3 wire)
6= 1-6kHz
7= 0-5V (4 wire)
8= 0-10V (4 wire)
ElectricalInterface
X= Special
A= 2ft. cable
B= 4ft. cable
C= 6ft. cable
D= 10ft. cable
E= Mini DIN 43650
F= Bendix 6 pin connector
WettedMaterial
X= Special
0= 17.4 PH
1= 316L
Options
XXX= Special
000= No options
Dimensional Information
1/4" MNPT Thread
0.875" HEX
2.61
0.40
1.0
Jacketed Cable, 0.177 dia.
Shrink Tubing,3/8" dia.
Electrical Connections - Cable Only
Cable
Output Type Green Black Red White
mV, 0-5V, 0-10V +S (Output)
-V (Supply)
+V (Supply)
-S (Output)
0.5-4.5V, 1-5V,1-6V S (Output)
-V (Supply)
+V (Supply) N/C
4-20mA N/C -V (Supply)
+V (Supply) N/C
Mini DIN 43650
Output Type Pin 1 Pin 2 Pin 3 Wide Pin
mV, 0-5V (4-wire), 0-10V(4-wire)
+S (Output)
-V (Supply)
+V (Supply)
-S (Output)
0-5V (3-wire), 1-5V, 0-10V(3-wire)
S (Output)
-V (Supply)
+V (Supply) N/C
4-20mA N/C -V (Supply)
+V (Supply) N/C
4-20mA Load line Curve
Supply Voltage
Line
Impe
danc
e
6-pin Bayonet (Bendix)
Output Type Pin A Pin B Pin C Pin D Pin E Pin F
mV, 0-5V, 0-10V +V +Signal -Signal -V -V N/C
1-5V, 1-6V, 1-10V +V Output N/C -V -V N/C
4-20 mA +V -V N/C N/C N/C N/C
4-20 mA +V -V N/C N/C Shunt Shunt
Series47
4
15
Series 50Stainless Steel, Wet/Wet Differential Pressure Sensor
Features• Compact and rugged design
• High strength stainless steel construction
• No internal fluid filled cavities
• No Internal o-rings
• Wide operating temperature range
• Low static and thermal errors
• EMI/RFI protection to 100V/m
• Suitable for high shock and vibration applications
1 Accuracy includes: Non-linearity, Hysteresis, and Non-repeatability
* Typical Ranges. All ranges between 0-30 psig and 0-300 psig are available. Please consult factory.
Performance @ 25˚C (77˚F)
Line Pressure 0-100 to 1,000 psig(0-7, 0-17, 0-35 and 0-70 bar)
Measurement Range 20% of line pressure, minimum
Proof Pressure Rated line pressure on either P1 or P2
Burst Pressure 5X or 2000 psi, whichever is less
Accuracy1 <±0.3% BFSL
Pressure Cycles > 10 Million
Physical Description Case 304 stainless steel
Electrical Connection Refer to Ordering Information
Wetted Material Refer to Ordering Information
Pressure Port 1/8" NPT
Environmental Data Temperature
Operating -40 to 85˚C (-40 to 185˚F)
Storage -40 to 100˚C (-40 to 212˚F)
Thermal Limits
Compensated Range 0 to 55˚C (30 to 130˚ F)
TC Zero <±1.5% of FS
TC Span <±1.5% of FS
Other
Shock 100G, 11msec, 1/2 sine
Vibration 10G Peak, 20 to 2000 Hz
EMI/RFI Protection Yes
Rating IP-66
Electrical Data Output 4-20mA Voltage (1-5V, 1-6V) 0.5-4.5V ratiometric
Excitation 10-30VDC 10-30VDC 5VDC, reg
Output Impedance
- <100 Ohms, nom. <100 Ohms, nom.
Current Consumption
25mA <10mA <10mA
Bandwith (-3dB): DC to 250 Hz DC to 1kHz DC to 1kHz
Output Noise:0-800 Ohms@ 10-28VDC
<2mV RMS <2mV RMS
Zero Offset <±1% of FS <±1% of FS <±1% of FS
Span Tolerance <±2% of FS <±1.5% of FS <±1.5% of FS
Output LoadSee load line curve below
10k Ohms, min. 10k Ohms, min.
Reverse Polarity Protection
Yes Yes No
Pressure Ranges*
DPRange
(psig), min.
LinePressure
(psig), max.
BurstPressure
(psig)Measurement
CodeLineCode
0-30 100 500 0030 0100
0-60 250 1,250 0060 0200
0-150 500 2,000 0150 0500
0-300 1,000 2,000 0300 1000
Specifications
Series50
4
16
5 0 - H - 0 5 0 0 - P - 3 - B - 0 - 0 0 0 0
Ordering Information
Construct a product code using the chart below. (Consult factory for other options)
SeriesType
50Standard
ProcessConnection
X= Special
H= 1/8" FNPT
Line PressureRange
XXXXX=Special
Insert pressurerange code from pressurerange chart.
PressureUnit
X= Special
B= BAR
K= kg/cm2
P= psig
Outputs
X= Special
2= 0.5-4.5V ratiometric
3= 1-5V
4= 4-20mA
6= 1-6V
ElectricalInterface
X= Special
A= 2ft. cable
B= 4ft. cable
WettedMaterial
X= Special
0= 17.4 PH
1= 316L withParylene-Ccoating(no options)
Dimensional Information
2.1
2.2
3/4" (19mm) HEX
!/8 FNPTBoth Ends
Output Red
1-5V
4-20mA
+V Supply
+V Supply
Table 1
Black White Green
-V Supply
-V Supply
Output
Not Used
Common
Common
MeasurementRange
Insert 4 digitmeasurementcode from charton specificationspage.
4-20mA Load line Curve
Supply Voltage
Line
Impe
danc
eSeries50
4
Red-Hat Solenoid ValvesThe largest selection of 2, 3, and 4-way solenoid
valves, designed to handle the most demandingfluid control applications.
ASCO ScientificHighest quality micro-miniature solenoid valvesfor medical and analytical applications.
Pneumatic ControlsDirectional control valves, air preparationequipment, actuators, and accessories forfluid power applications.
Valve Monitoring SystemsIntegrated visual indication technology withnetwork communication capabilities thatrevolutionizes position indication solutions.
Next Generation SolenoidsThe Next Generation of solenoid valves provides lower operating cost, and representsand advancement in performance, reliability,and ruggedness that you have come to expect
from ASCO.
Process AutomationPilot valves and control accessories for reliable
process solutions.
Pressure and Temperature SensingDevices for pressure and temperature monitoring.
ASCO S SeriesCompact valve solutions for commercial applications.
ASCO offers a complete catalog of products and accessories to satisfy any ofyour application needs. Visit us online at www.ascovalve.com to view our fullline of products.
18ASCO Valve, Inc. • 800.972.2726 • www.ascovalve.com V7366 R5
FranceTel (33) 1-47-14-32-00
Germany Tel (49)-7237-9960
United Kingdom Tel (44) 1695-713600
AustraliaTel (61) 2-9-451-7077
ChinaTel (852) 2-343-8580
Japan Tel (81) 798-65-6361
SingaporeTel (65) 6556-1100
BrazilTel (55) 11-4208-1700
MexicoTel (52) 55-3640-0200
CanadaTel 519-758-2700
www.eci.co