Master MPS A4 - CM Comandos · CM COMANDOS LINEARES D OS A N LI M N E A O R C M E C S ISO 9001 2000...
Transcript of Master MPS A4 - CM Comandos · CM COMANDOS LINEARES D OS A N LI M N E A O R C M E C S ISO 9001 2000...
S é r i e P r e m i u m
UPSMicroprocessed
M A S T E R M P S
CM COMANDOS LINEARESCM COMANDOS LINEARES
Three Phase
CM COMANDOS LINEARES
O SD LN IA NM EAO
RC EM SC
ISO9001
2000
A P P L I C A B I L I T Y
T E C H I C A LS U P P O R T
B E N E F I T S
O SD LN IA NM EAO
RC EM SC
ISO9001
2008
Innovation, quality, technology
and reliability. Trademarks of
CM Comandos Lineares solutions
THE COMPANY With over 32 years in operation, CM Comandos is today
one of the largest UPS manufacturers in the Latin America.
Certified by ISO-9001:2008 standars, with an audited Sustainability System,
CM Comandos stresses its commitment with environment preservation, excellence
of its products and full client satisfaction
against power disturbances, such as cuts, micro cuts, noise, harmonic distortion, spikes,
transients, under and over voltage and frequency variations.
UPS of CM Comandos Lineares are suitable for critical-mission
usage in all types of corporations, providing protection
CM Comandos equipment operates with greater precision, adds more
features and are the safest ones.
Features that create high reliability and productivity in many types of applications, diminish
flaws and hence maintenance costs. In short, being a CM Comandos client means having
the return on capital invested and guarantees that only a company with wide technical
support can offer
By choosing the brand CM Comandos Lineares you can
count on the best technical support prior and post-sales
from a company that has established itself over these 32 years
as the market leader. Cutting-edge instrumentation, highly skilled workers,
with national coverage and 24-hour service, seven days a week, call center
and certified processes ensure the excellence of our support services.
T H E C O M PA N Y
High Technology in UPS Systems for Critical Mission
Aros was founded in 1935 in Milan, Italy manufacturing power supplies and stabilizers
and soon became one of the leading European manufacturers of large size UPS systems.
In the late 90´s it becomes part of the Riello Group and in 2011, Aros brand merges to Riello UPS, integrating
engineering resources, production and technology and consolidates the operations creating a global leader, Riello
Aros UPS. Riello Aros UPS has been expanding its global presence as one of the largest manufacturers in the area of
Energy Systems and present in Brazil in partnership with CM Comandos since 1996.
THE MOST MODERNCORPORATE UPS
The Master MPS and HP lines of Three-phase UPS are the result of the highest
technology in microprocessor circuits applied to static converters of the latest
generation. The Master HP line has IGBTs Rectifier with input power factor of
0.99 and is controlled by DSP microprocessor. UPSs instantly correct any voltage variation of the power grid of the
utility, all in digital sampling rate, without delays or detours. All setups and configurations are performed by software
and they have a single event log record, allowing full traceability in the event of anomalies. The battery self-test system
allows to anticipate a possible poor condition of the batteries, in time to take preventive measures. In case of internal
failure, it is possible to accurately detect the affected sector and anticipate service drastically reducing the time spent
on troubleshooting, and provide equipment history log in preventive controls. Never the change of a single UPS to
operate in redundant parallel was so simple and affordable, versatile and user friendly thanks to microprocessor
technology. The Master MPS and HP lines establish a new generation of UPSs for Mission Critical applications in Brazil.
When thinking of purchasing an UPS, you can count on the solutions of the CM Comandos to ensure the latest
technology, highest protection, digital precision and real-time processing.
Master MPS • HPThree Phase UPS
M A I N F E AT U R E S INTERFACE DEGERENCIAMENTOREMOTO
Bypass Estático de Manutenção
ONLINE TECHNOLOGY WITH STATIC MAINTENANCE BYPASS
Static Maintenance BypassIt allows transfer and return of the UPS load to analternate circuit of power supply for maintenancepurposes. In any case, the power supply is continuouswith no interruption
Static BypassProtection systemthat, in case of problems, automaticallytransfers the load to an alternate circuit without interruptingthe power supply
Present Network
Network Failure
Static Bypass
OutputInput Power Grid
RectifierConverts the energy
from the mains of the utility provider or the generator into direct
current, fixing or eliminating system input disturbances
InverterIt converts the direct current fromthe rectifier or battery into alternating current output, shaped like a pure sinewave, disturbance-free.
Battery bankStores backup power to power the UPS overa predetermined period, known as UPS runtime.
Input Alternating Current
Direct Current
Output Alternating Current
Alternating Current Static Bypass
Maintenance Alternating CurrentStatic Bypass
REDUNDANT PARALLELSYSTEM
For Mission Critical Systems,
redundant parallel operation
provides high reliability.
The Master MPS and HP lines
connect up to 8 units in par
allel with loop connection
and 100% digital control.
Another feature is the ability
to parallel a simple unit
previously field installed,
preserving your investment
and ensuring scalability, i.e.,
the expansion may be
modular according to its increase.
100% Digital Microprocessed ControlThe settings and adjustments are fully madeby the LCD panel with restricted password access.
IGBT rectifier - HP Master lineWith DSP control, PFC Power FactorCorrection provides input power factor of 0.99
Advanced Battery Management It has battery recharge control withtemperature compensation, optimizingits useful life.
Automatic Battery TestIt performs safely periodic test of batteries, i.e. reduces the rectifier voltage to the batterytake the load. In case of failure, it immediatelysends a warning.
Smart Control of Cooler speedExtend equipment life and reduce maintenance intervals.
Event Log and TraceabilityThe latest events are stored in NVRAM memory in one kind of black box. Data can be retrieved via the panel or via software for diagnostics, including remote one.
Diagnosis Event Codes Records the last 5,000 events and 128 typesof warnings and messages, allowing a precise identification of each event.
Parallelizable up to 8 UPSWith loop connection and single models previously field installed.
Input Under and Over Voltage ProtectionAutomatically turns off the rectifier, disablesBypass, protecting against out of range voltages.
Compatible with All GensetsAccuracy and full protection for operationwith generators.
They are comprised of various
tools. The software Watch & Save
allows to remotely monitor the UPS,
performs automatic server shutdown
and sends warnings via email.
But the UPSMan software is specific
for the automation of server shutdown,
it can automatically shut down
multiple servers simultaneously
and with different operating
systems
L O O P PA R A L L E L I S M C O N T R O L
A D VA N C E D M A N A G E M E N T A N D S H U T D O W N I N T E R FA C E S
NetMan 101 Plus - Externo 102 Plus - Cardslot Interno
NetMan
Adaptador SNMP - Converte a porta serialRS232 em um ponto de rede RJ45 - TCP/IP
LOOP PARALLELISM CONTROL
This system has two levels of
redundancy in sync cable connection
among the UPSs in parallel,
increasing reliability.
Another feature is that, in case
of maintenance, only the isolated
module is disconnected from
the parallel bus, while the other
modules remain feeding the
critical load
Reliability N times higher to failure.
REMOTE MANAGEMENT SNMP
Through SNMP NetMan 102
Plus adapter MPS line has
remote management via SNMP,
allowing the supervision of
multiple units, single or
parallel, through TCP / IP
local or remote connection.
Alerts Emails Broadcast Messages
Web Access Management tools
for Network administrators
Signal SplitterThis hardware adds serial portsfor shutdown interface
UPSMAN RCCMD Client
UPSMAN for Unix Tools that automate
shutdown in Enterprise Servers
Watch & SaveAdvanced Management Tool - Monitors the UPSstatus and parameters
Via Internet Remote StationThe SNMP NetMan 102 adapter allows monitoringremotely the system via the Internet.
ModelMPT - 6 pulses
PowerkVA
Physical Sizehgt x wid x dep mm
Weight (without
batteries) kg
10 10,0 1400 X 555 X 740 210 15 15,0 1400 X 555 X 740 220 20 20,0 1400 X 555 X 740 230 30 30,0 1400 X 555 X 740 292 40 40,0 1400 X 555 X 740 320 60 60,0 1400 X 800 X 740 360 80 80,0 1400 X 800 X 740 555
100 100,0 1900 X 800 X 800 640 120 120,0 1900 X 800 X 800 650 160 160,0 1900 X 800 X 800 770 200 200,0 1900 X 800 X 800 810
T E C H N I C A L S P E C I F I C AT I O N S
Input Voltage:
Three-phase: 380 / 400 / 415V ( 220V*, 440V*, 480V*) Permissible Variation:
Permissible Frequency Range: 45 a 65 Hz
Configuração do Retificador: • 6 Pulses - 10 a 200 kVA ( line Master MPS ) • 12 Pulses - 800 kVA (line Master MPS ) • IGBT - 100 a 600 kVA (line Master HP )
Power Factor: • 0.8 Master MPS - Rectifier 6 Pulses • 0,92 Filtrer THDi* • 0,99 IGBT line Master HP
OutputVoltage:
• 380 / 400 / 415V ( 220V*, 440V*, 480V* )Power Available:
• 10/15/20/30/40/60/80 kVA - Master MPS
Static Adjustment: ± 1% ratedDynamic adjustment: ± 5% ratedFrequency: 50 ou 60 Hz Frequency Variation:
Configuration:
Waveform: sine waveHarmonic Distortion THD: less than 1% with linear
load; 3% with non-linear loadCrest Factor: 3:1Overload Capacity: 110/125/150% during 60/10/1
Efficiency: 91a 94% On Line • 98% Eco-mode
BatteriesLine Voltage:
• 384VDC - 10 - 80kVA - Master MPS • 396VDC - 100 - 200kVA - Master MPS
Recharging System: smart, processor controlledwith temperature compensation
Recharge time:
Battery Test: yes, automatic or manual
Static BypassOperation: automatic, processor or manually controlled, via panelTransfer time: 0ms (zero)Retransfer to Normal Mode: Automatic or manual
Maintenance Static BypassFeature: Allows maintenance of the UPS without powering down the load
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
•
• ± 20% of rated voltageFrequency: 50 or 60 Hz
C Configuration: Three-phase: 3F + N + T
• 100/120/160/200 kVA - Master MPS • 800 kVA - Master MPS • 100/120/160/250/300/400/500/600 kVA - Master HP
• ± 0.05% in battery mode
•Three-phase: 3F +N + TPower Factor: 0,9
minutes
• 480VDC - 800 kVA - Master MPS • 480VDC - 100 - 600 kVA - Master HP
• 8 - 10 horas at 90% load
Type: sealed, maintenance - free - VRLA
Physical and Mechanical Features
Compact DimensionsLiquid Crystal Display - LCDEnclosure Structure:
Forced ventilation with digital speed control by the processor
Drive Isolation Transformer with electrostatic shieldingCommunication Port:
• 2 Serial Ports RS232C Isolated Full Duplex - DB9 Female
Management Interfaces
Mono and multi-user, client-server and multiservers
Shutdown and Management Tools
Management Softwares* • Watch & Save • PowerNETGuard
Environments and Operating Systems • Windows 7 / 2008 / Vista • Linux / Novell / Java • Unix / IBM AIX / HP-UX / SunOs
n
n
n
n
n
n
n
n
n
n
n
n
Trademarks of their respective manufacturers)
/ Solaris / OSF1/ AS-400
• HP-Open View (
• Metal Rack, monoblock • Front panel in high strength ABS • Sides and top removable covers • Finish: epoxy powder painting in graphite color with heat treatment and anti-corrosion
• Dry Contact DB15 female • Contact for EPO - Emergency Power Off
Multiple Servers on a single UPS
Protocols: • Serial RS232 • RS485 Serial * / * MODBUS / PROFIBUS * / JBUS * • SNMP / Telnet / HTTP / TCP / IP *
• Gateway • NetMan 101 Plus - External Adapter • NetMan 102 Plus - Internal Cardslot
* Optional
Sinalização: 5-inch graphic panel, multifunctionwith measurements, controls and alarms.Measurements
Voltage: Input, Output and BypassMeasurements of Phase-Phase and Phase-NeutralCurrent: Input, Output and BatteryAC Peak and RMS CurrentFrequency: Input, Output and BypassPower in KVA and kW
Internal temperature – RectifierInternal temperature - InverterInternal temperature - System Control
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
Operation: manual through circuit breaker actuation / internal switch
Reset to Normal Mode: without interruption
Redundant Parallel Operation
Parallel power and redundancy Up to 8 units in parallelAllows the installation of Parallelism Kit On SiteCommunication System in loop - Loop Connection Reliability N times higher to fault
Power ProtectionsUnder and Over Input and Output VoltageUnder and Over DC Voltage and BatteryOverload and Short CircuitLow Battery DischargeOver Temperature
n
n
n
n
n
AlarmsControlled by the Processor Types Of Alarms:
• Sound:: » Network Failure » Pre-alarm of the batteries (configurable by the
panel) » Internal Fault UPS: continuous alarm
n
n
• Liquid Crystal Display: » Liquid Crystal Display: » Software Watch & Save, local or remote » Message on e-mail, phone or pop-up
Event LogStored Records:
5000 last records in NVRAMDate, time and occurrence indicationMeasurements, Operation Status and AlarmsInternal Switch Status128 Alarm Codes and Detailed Errors
NVRAM Autonomy:5 years (with the UPS off and without batteries)
n
n
• • • • •
•
Operating CharacteristicsAudible Noise:
• 54 a 65 dBA at 1 metro - 10 a 200 kVA • 65 a 77 dBA at 1 metro - 250 a 800 kVA
MTBF (Mean Time Between Failures): 200 mil hoursMTTR (Mean Time To Repair): 30 minutesRoom Temperature:
• Batteries: 0ºC a 30ºC • UPS: 20ºC a 40ºC • Recomended: 20ºC e 25ºC
Relative Humidity: • 0% a 95% non-condensing • Recomended: 45% a 55%
Height: up to 1.000mType of Environment Recommended:
• Internal, indoor installation • Atmosphere: clean, free of conductive, toxic particles, flammable liquids and gases.
Degree of Protection: IP-20 IP-20
n
n
n
n
n
n
n
n
Technology
n
n
n
n
n
n
On Line - Double Conversion - VFIRectifier - Inverter - Batteries BankStatic Bypass - Maintenance Static BypassActive Digital Control for Microprocessors IGBT rectifier - Master HP lineHigh-Frequency PWM InverterFirmware Upgrade
Av. Eng. Alberto de Zagottis, 760 - 04675-085 - São Paulo - SPPhone: (11) 5696-5000 - Fax: (11) 5696-5055
www.cmcomandos.com.br
CM COMANDOS LINEARES
O SD N L IA NM EO A
C R EM SC
ISO9001
2008
800 800,0 1900 X 3200 X 1000 3950
ModelMPT - 12 pulses
PowerkVA
Physical Sizehgt x wid x dep mm
Weight (without
batteries) kg
100 100,0 1900 X 800 X 850 730 120 120,0 1900 X 800 X 850 785 160 160,0 1900 X 1000 X 850 865 200 200,0 1900 X 1000 X 850 990 250 250,0 1900 X 1000 X 850 1090 300 300,0 1900 X 1500 X 1000 1550 400 400,0 1900 X 1500 X 1000 1750 500 500,0 1900 X 2100 X 1000 2450 600 600,0 1900 X 2100 X 1000 2650
ModeloMHT
PotênciakVA
Dimensões Físicasalt x larg x prof mm
Peso sem baterias kg
ModelMHT - IGBT
PowerkVA
Physical Sizehgt x wid x dep mm
Weight (without
batteries) kgC
M.M
KT 1
07 R
ev.2
- Sp
ecifi
catio
ns a
re s
ubje
ct to
cha
nge
with
out n
otic
e.W
e en
cour
age
recy
clin
g
Audited Sustainability System