Planos_detalle_Refugios
-
Upload
natanael-victoriano-huerta -
Category
Documents
-
view
216 -
download
0
Transcript of Planos_detalle_Refugios
-
8/13/2019 Planos_detalle_Refugios
1/32
-
8/13/2019 Planos_detalle_Refugios
2/32
-
8/13/2019 Planos_detalle_Refugios
3/32
-
8/13/2019 Planos_detalle_Refugios
4/32
-
8/13/2019 Planos_detalle_Refugios
5/32
-
8/13/2019 Planos_detalle_Refugios
6/32
-
8/13/2019 Planos_detalle_Refugios
7/32
-
8/13/2019 Planos_detalle_Refugios
8/32
-
8/13/2019 Planos_detalle_Refugios
9/32
-
8/13/2019 Planos_detalle_Refugios
10/32
-
8/13/2019 Planos_detalle_Refugios
11/32
-
8/13/2019 Planos_detalle_Refugios
12/32
-
8/13/2019 Planos_detalle_Refugios
13/32
-
8/13/2019 Planos_detalle_Refugios
14/32
-
8/13/2019 Planos_detalle_Refugios
15/32
D-4
D CASE STUDY II SCHOOL COMMUNITY SAFE ROOM
DESIGN AND CONSTRUCTION GUIDANCE FOR COMMUNITY SAFE ROOMS
SECOND EDITION
Internal Pressure Coefcients for Buildings (Table 6-7 of ASCE 7-98; Figure 6-5of ASCE 7-05)GC pipos = 0.55 for partially enclosed buildings
GC pineg = -0.55 for partially enclosed buildings
Design Wind Pressure for Rigid Buildings of All Heights (Section 6.5.12.2.1 ofASCE 7-98 and ASCE 7-05)(for positive internal pressures)
pwi = (q z)(G)(C p ) (q h)(GC pipos ) p wi = 7.68 windward wall
p lee2a = (q z)(G)(C p2a ) (q h)(GC pipos ) p lee2a = - 8.73 leeward wall (wind parallel to ridge)
p lee2b = (q z)(G)(C p2b ) (q h)(GC pipos ) p lee2b = - 32.60 leeward wall (perpendicular to ridge)
p side = (q z)(G)(C p3) (q h)(GC pipos ) p side = - 55.72 side wall
p roof = (q z)(G)(C p4) (qh)(GC pipos ) p roof = - 78.84 roof pressures (0 4 ft from windwardedge)
p roof2 = (q z)(G)(C p5) (q h)(GC pipos ) p roof2 = - 32.60 roof pressures ( 4 28 ft from windwardedge)
p roof3 = (q z)(G)(C p6) (q h)(GC pipos ) p roof3 = - 09.48 roof pressures (more than 28 ft fromwindward edge)
(for negative internal pressures)
pwi = (q z)(G)(C p ) (q h)(GC pineg ) p wi = 67.28 windward wall
p lee2a = (q z)(G)(C p2a ) (q h)(GC pineg ) p lee2a = 30.87 leeward wall (wind parallel to ridge)
p lee2b = (q z)(G)(C p2b ) (q h)(GC pineg ) p lee2b = 7.00 leeward wall (perpendicular to ridge)
ATMOSTPHERIC PRESSURE CHANGE (APC)
The internal pressure coef cient, GC pi, may be taken as 0. 8 when venting area of squarefoot per ,000 cubic feet of interior safe room volume is provided to account for APC. As analternative to calculating the effects of APC, and designing an appropriate venting systemfor the safe room, the design may be completed using an internal pressure coef cient GC pi = 0.55 as a conservative means to account for APC.
ATMOSTPHERIC PRESSURE CHANGE (APC)
The internal pressure coef cient, GC pi, may be taken as 0. 8 when venting area of squarefoot per ,000 cubic feet of interior safe room volume is provided to account for APC. As analternative to calculating the effects of APC, and designing an appropriate venting systemfor the safe room, the design may be completed using an internal pressure coef cient GC pi = 0.55 as a conservative means to account for APC.
-
8/13/2019 Planos_detalle_Refugios
16/32
-
8/13/2019 Planos_detalle_Refugios
17/32
-
8/13/2019 Planos_detalle_Refugios
18/32
-
8/13/2019 Planos_detalle_Refugios
19/32
-
8/13/2019 Planos_detalle_Refugios
20/32
-
8/13/2019 Planos_detalle_Refugios
21/32
-
8/13/2019 Planos_detalle_Refugios
22/32
-
8/13/2019 Planos_detalle_Refugios
23/32
-
8/13/2019 Planos_detalle_Refugios
24/32
-
8/13/2019 Planos_detalle_Refugios
25/32
E-
E WALL SECTIONS THAT PASSED PREVIOUS MISSILE IMPACT TESTS
DESIGN AND CONSTRUCTION GUIDANCE FOR COMMUNITY SAFE ROOMS
SECOND EDITION
-
8/13/2019 Planos_detalle_Refugios
26/32
E-3
E WALL SECTIONS THAT PASSED PREVIOUS MISSILE IMPACT TESTS
DESIGN AND CONSTRUCTION GUIDANCE FOR COMMUNITY SAFE ROOMS
SECOND EDITION
4-inch concrete block in a 2x6 studwall with 1 inches polystyrene betweenblock and two layers of -inch CDgrade plywood
Double 2x4 stud wall with 4 layers of-inch CD grade plywood and14-gauge steel on the back face
Double 2x4 stud wall with 4 layers of-inch CD grade plywood and14-gauge steel on the back face
4 layers of -inch plywood with14-gauge steel insert with spacersbetween the insert and the back face
The missile penetrated the target.There was no visible damage to theback side of the target.
The target was impacted next to a stud.Several heads of screws were poppedoff the back of the target. The steel had1 inch of deformation.
The target was impacted on the studline. The stud was cut in two. Nodeformation was visible on the backside.
The missile penetrated the target 1-2inches. A crack in the plywood on theback face caused bending, but total
separation did not occur.
2x4 stud wall with CD grade plywood,
14-gauge -inch expanded metal, andconcrete infill
2x4 stud wall with CD grade plywood,14-gauge -inch expanded metal, andconcrete infill
2x4 stud wall filled with concrete withno plywood and 14-gauge -inchexpanded metal on the non-impactface
2x4 stud wall filled with concrete withno plywood and 14-gauge -inch
expanded metal on the non-impactface
2x4 stud wall filled with concrete withno plywood and 14-gauge -inchexpanded metal on the non-impactface
The missile impacted 4 inches to the
left of a stud. No damage was visibleon the back of the target.
The missile impacted 1 inches to theleft of a stud. No damage was visibleon the back of the target.
The missile imade partial contact withthe stud. The concrete was crackedaround the impact area.
The missile imade partial contact withthe stud. The concrete was severely
damaged, and a 4-inch deflection onthe back of the target was observed.
The missile impacted the concrete. Nodamage was visible.
-
8/13/2019 Planos_detalle_Refugios
27/32
E-
E WALL SECTIONS THAT PASSED PREVIOUS MISSILE IMPACT TESTS
DESIGN AND CONSTRUCTION GUIDANCE FOR COMMUNITY SAFE ROOMS
SECOND EDITION
-
8/13/2019 Planos_detalle_Refugios
28/32
E-5
E WALL SECTIONS THAT PASSED PREVIOUS MISSILE IMPACT TESTS
DESIGN AND CONSTRUCTION GUIDANCE FOR COMMUNITY SAFE ROOMS
SECOND EDITION
-
8/13/2019 Planos_detalle_Refugios
29/32
F-3
F DOORS AND HARDWARE THAT PASSED PREVIOUS MISSILE IMPACT TESTS
DESIGN AND CONSTRUCTION GUIDANCE FOR COMMUNITY SAFE ROOMS
SECOND EDITION
-
8/13/2019 Planos_detalle_Refugios
30/32
F-4
F DOORS AND HARDWARE THAT PASSED PREVIOUS MISSILE IMPACT TESTS
DESIGN AND CONSTRUCTION GUIDANCE FOR COMMUNITY SAFE ROOMS
SECOND EDITION
-
8/13/2019 Planos_detalle_Refugios
31/32
F-5
F DOORS AND HARDWARE THAT PASSED PREVIOUS MISSILE IMPACT TESTS
DESIGN AND CONSTRUCTION GUIDANCE FOR COMMUNITY SAFE ROOMS
SECOND EDITION
-
8/13/2019 Planos_detalle_Refugios
32/32