Pruebas Fuente ICT 22012-140
1
PRODUCT SPECIFICATIONS Input Voltage Range 105 - 130 or 205 - 250 VAC Input Frequency Range 60 Hz Output Voltage 13.8 VDC +/- 150 mV Output Current (Continuous) 83.0 Amps Output Current (Peak) 127.0 Amps Current Limiting 145.0 Amps +/- 5% Line Regulation 1.00% Load Regulation 1.00% Output Ripple (Max) 40 mV RMS Output Current (Redundant) 100 Amps Efficiency (Min) 80% Fuse 15/12 Amp Operating Temperature -50°F to 125°F -46°C to 52°C Size (L x W x H) 14.3" x 19" x 3.5" Weight 17.3 lbs. Pruebas en Laboratorio Sin Carga Voltaje AC: 121.8 VoltajeDC: 14v Pruebas con Carga: Voltaje Corriente 13.89 25.5 13.89 26.4 13.88 29.6 13.86 33.7 13.83 39.8 13.80 48.8 13.72 68.8 13.5 107.6 13.1 114.5
-
Upload
oscar-portela -
Category
Documents
-
view
226 -
download
3
description
pruebas de laboratorio
Transcript of Pruebas Fuente ICT 22012-140
-
PRODUCT SPECIFICATIONS
Input Voltage Range 105 - 130 or 205 - 250 VAC
Input Frequency Range 60 Hz
Output Voltage 13.8 VDC +/- 150 mV
Output Current (Continuous)
83.0 Amps
Output Current (Peak) 127.0 Amps
Current Limiting 145.0 Amps +/- 5%
Line Regulation 1.00%
Load Regulation 1.00%
Output Ripple (Max) 40 mV RMS
Output Current (Redundant) 100 Amps
Efficiency (Min) 80%
Fuse 15/12 Amp
Operating Temperature -50F to 125F -46C to 52C
Size (L x W x H) 14.3" x 19" x 3.5"
Weight 17.3 lbs.
Pruebas en Laboratorio
Sin Carga
Voltaje AC: 121.8 VoltajeDC: 14v
Pruebas con Carga:
Voltaje Corriente
13.89 25.5
13.89 26.4
13.88 29.6
13.86 33.7
13.83 39.8
13.80 48.8
13.72 68.8
13.5 107.6
13.1 114.5