Doble Engineering Company
Troubles & Failures Report8/1/2004 To 9/30/2004
Arrester - TroubleIncident # Incident Date Report Date Photo File Name
43921 4/29/2003 10/14/2004 IID200401,02,03
Manufacturer Model Number KV Mfgr Year
Joslyn 8110D0001J096 51-100 kV
Method of Detection
Cause of Failure
No apparent trouble in the system.
Comments
(Photo was unavailable for release in this report.)
Arrester - In-Service FailureIncident # Incident Date Report Date Photo File Name
43922 11/15/2003 10/14/2004
Manufacturer Model Number KV Mfgr Year Joslyn ZE 51-100 kV NONE
Method of Detection
Cause of Failure
Line down.
Comments
B/O lightning arrester on RNO breaker.
Arrester - In-Service FailureIncident # Incident Date Report Date Photo File Name
43961 12/25/2003 2/23/2004 SNPD2004_Rept04
Manufacturer Model Number KV Mfgr Year
Ohio Brass 219576 101-150 kV 2001
Method of Detection
Cause of Failure
Unknown - clear day, no moisture found internally.
Knowledge Is PowerSM
Apparatus Maintenance and Power Management For Energy Delivery
Troubles Failures Report Page 1 of 28
8/17/2019 Reporte Fallas 09-30-04
2/28
Comments
Arrester failed only about 3 months after it was installed as a replacement to an old SiC
arrester. O.B. had identified arresters that had a problem with moisture ingress,
but this S/N was not part of their recall. O.B. performed an analysis, but no cause
was identified. (Photo was unavailable for release in this report.)
Bushing-Condenser (oip) - TroubleIncident # Incident Date Report Date Photo File Name
43924 5/2/2003 10/14/2004
Manufacturer Model Number KV Mfgr Year
General Electric PVDB1155202 11-15 kV 2002
Method of Detection
Cause of Failure
Comments
Bushing-Condenser (oip) - TroubleIncident # Incident Date Report Date Photo File Name
43969 8/19/2003 3/25/2004
Manufacturer Model Number KV Mfgr Year
General Electric 550W1600UG 451-500 kV 1981
Method of Detection
Failed Doble power factor test.
Cause of Failure
Comments
Type U 500KV Bushing - evidence of water entering at top terminal gasket.
Bushing-Condenser (oip) - TroubleIncident # Incident Date Report Date Photo File Name
43942 3/8/2004 3/23/2004 sce2004_rept01a,b
Manufacturer Model Number KV Mfgr Year
General Electric FK69-3500-1 51-100 kV 1962
Method of Detection
Cause of Failure
Comments
Type U bushing on circuit breaker failed. (Picture was unavailable for release in this report.)
Troubles Failures Report Page 2 of 28
8/17/2019 Reporte Fallas 09-30-04
3/28
Bushing-Condenser (oip) - Failure at TestIncident # Incident Date Report Date Photo File Name
43891 8/13/2004 8/16/2004
Manufacturer Model Number KV Mfgr Year
Lapp POC 101-150 kV
Method of Detection
Bushings: C1 Power Factor
Cause of Failure
Bushing
Comments
Cable - TroubleIncident # Incident Date Report Date Photo File Name
43934 6/4/2003 3/18/2004 MWD2004_Rept01A(thru C).JPGManufacturer Model Number KV Mfgr Year
Rome 0-5 kV 1982
Method of Detection
Cause of Failure
Insulation failure due to old manufacturing formulation.
Comments
The hydro plant tripped due to utility excursion. After receiving permission from the utility for
restart, the unit tripped as soon as the breaker closed. A Megger test revealed a problem
with one of the conductors from the unit circuit breaker to transformer. A hole slightly larger
than a quarter was found in the failed cable. (Photos were unavailable for release in this
report.) As preventative measures, the asset owner will survey other 14 hydro plants
for similar old XLP cables and continue cable testing every 5 years; they may also consider
a shorter interval between cable tests, particularly for older cables.
Capacitor - In-Service FailureIncident # Incident Date Report Date Photo File Name
43926 1/5/2004 4/1/2004
Manufacturer Model Number KV Mfgr Year
Westinghouse Electric series caps 201-250 kV 1966
Method of Detection
Cause of Failure
Comments
Cap bank was called to bypass. Bypass switch got part way closed causing extended arcing (blowing
up glass & burning up contacts). Bank was installed in 1966. Parts are wearing out and getting hard to get.
Troubles Failures Report Page 3 of 28
8/17/2019 Reporte Fallas 09-30-04
4/28
Circuit Breaker - TroubleIncident # Incident Date Report Date Photo File Name
43947 8/15/2001 4/15/2004
Manufacturer Model Number KV Mfgr Year
Westinghouse Electric 242-SP-50 251-300 kV 1980
Method of Detection
Cause of Failure
Failed air compressor.
Comments
AØ DID NOT CLOSE. BREAKER USED UP ENOUGH AR TO LOCK OUT AIR COMPRESSOR. BROUGHT
IN LOW AIR ALARM, AND LOCKED OUT. CLOSING CIRCUIT TO GCB. FOUND BROKEN RINGS ON
PISTON AØ MECH; ALSO FOUND BROKEN 1" ROLL PIN IN PISTON ROD. BOLTS IN OPENING
VALVE ASEMB.
Circuit Breaker - In-Service FailureIncident # Incident Date Report Date Photo File Name
43962 1/7/2003 2/23/2004
Manufacturer Model Number KV Mfgr Year
Siemens FCV-500 11-15 kV 1979
Method of Detection
Cause of Failure
Trip coil failure.
Comments
Circuit switcher operated to clear fault, interrupting service to approx 5,000 customers.
However, circuit switcher would not close again, and motor operator had to be repaired.
Circuit Breaker - TroubleIncident # Incident Date Report Date Photo File Name
43952 1/17/2003 4/15/2004
Manufacturer Model Number KV Mfgr Year
McGraw Edison AHJ-60-138-10000 151-200 kV 1973
Method of Detection
Cause of Failure
Mechanism lubrication dried up.
Comments
FOUND ALL BEARING STIFF, OR NOT MOVING AT ALL IN MECH. R & R TRIP ASS.
REMOVE AND DISASSEMBLE STIFF TRIP LINKAGE, LUBE PINS
AND FREE UP STIFF BEARINGS. NOW THE BREAKER LATCHES EVERY TIME.
Troubles Failures Report Page 4 of 28
8/17/2019 Reporte Fallas 09-30-04
5/28
Circuit Breaker - TroubleIncident # Incident Date Report Date Photo File Name
43946 1/22/2003 4/16/2004
Manufacturer Model Number KV Mfgr Year
Siemens SPS2-245-40-1 201-250 kV 2001
Method of Detection
Cause of Failure
While being energized, pole 3 went phase to ground.
Comments
Removed SF6 gas & removed pole 3 cover. Found that pole 3 did flash to ground.
Looks like it flashed from the corona ring to the tank. 7 of the same voltage level
and model in the 2000/2001 mfg year were internally inspected.
Circuit Breaker - Trouble
Incident # Incident Date Report Date Photo File Name43951 2/5/2003 4/15/2004
Manufacturer Model Number KV Mfgr Year
Westinghouse Electric GO-3D 51-100 kV 1950
Method of Detection
Cause of Failure
Exhaust piston stuck.
Comments
Circuit Breaker - TroubleIncident # Incident Date Report Date Photo File Name
43916 2/24/2003 4/4/2004 BPAT200414-19
Manufacturer Model Number KV Mfgr Year
ABB 550PM 50-30 > 500 kV 2003
Method of Detection
Cause of Failure
Restrike
Comments
Breaker sent a trip command via SCADA. A & B phases interrupted approximately 320
Amps. C-phase continued to carry load current for approximately 16 cycles. Breaker
Failure Relay operated and cleared the bus. Breaker was commission tested and in
service less than 6 weeks. (Photo was unavailable for release in this report.)
Troubles Failures Report Page 5 of 28
8/17/2019 Reporte Fallas 09-30-04
6/28
Circuit Breaker - In-Service FailureIncident # Incident Date Report Date Photo File Name
43953 3/24/2003 4/15/2004
Manufacturer Model Number KV Mfgr Year
McGraw Edison CH-60A-69-3500 51-100 kV 1974
Method of Detection
Cause of Failure
Comments
FOUND CLOSE COIL OPERATOR IN PIECES AND CLOSE COIL BO, REBUILT CLOSING MEC. AND REPLACED COIL.
Circuit Breaker - TroubleIncident # Incident Date Report Date Photo File Name
43968 4/2/2003 3/25/2004
Manufacturer Model Number KV Mfgr Year Alsthom HGF-1014 201-250 kV 2002
Method of Detection
Cause of Failure
Internal contamination from factory
Comments
Internal fault B Phase to ground 15000amps
Circuit Breaker - TroubleIncident # Incident Date Report Date Photo File Name43950 4/15/2003 4/15/2004
Manufacturer Model Number KV Mfgr Year
Mitsubishi 101-150 kV 2001
Method of Detection
Cause of Failure
B/O closing coil.
Comments
Circuit Breaker - TroubleIncident # Incident Date Report Date Photo File Name
43954 5/22/2003 4/15/2004
Manufacturer Model Number KV Mfgr Year
McGraw Edison AHJ-60-138-1000 101-150 kV 1973
Method of Detection
Troubles Failures Report Page 6 of 28
8/17/2019 Reporte Fallas 09-30-04
7/28
Cause of Failure
Mechanism lubricants dried out.
Comments
Breaker had problems closing.
Circuit Breaker - TroubleIncident # Incident Date Report Date Photo File Name
43939 7/1/2003 10/14/2004 PAC200402
Manufacturer Model Number KV Mfgr Year
ABB 145PMI 101-150 kV
Method of Detection
Cause of Failure
Broken stud that mounts the stationary arcing contact inside the stationary contact assem
CommentsThis was likely caused by a stress concentration due to a surface defect such as a crack at
the root of the threads. (Photo was unavailable for release in this report.)
Circuit Breaker - TroubleIncident # Incident Date Report Date Photo File Name
43948 7/7/2003 4/15/2004
Manufacturer Model Number KV Mfgr Year
Westinghouse Electric 242-SP-50 251-300 kV 1980
Method of Detection
Cause of Failure
Comments
07/07/03 Breaker timing problem. Timed breaker, found out by 15 ms, will need to come
back to adjust. 07/10/03 Adjusted phase-to-phase timing on breaker. Turned
screw on close pilot valve out to speed up tank 3; it is still slower than factory spec.
Circuit Breaker - In-Service FailureIncident # Incident Date Report Date Photo File Name
43973 8/2/2003 4/6/2004
Manufacturer Model Number KV Mfgr Year
General Electric FK-144-250Y 11-15 kV 1956
Method of Detection
Cause of Failure
Fault started at line arrester, breaker did not clear fault.
Troubles Failures Report Page 7 of 28
8/17/2019 Reporte Fallas 09-30-04
8/28
Comments
Breaker tank ruptured. Breaker was a total loss. (Lightning in area.)
Circuit Breaker - TroubleIncident # Incident Date Report Date Photo File Name
43937 8/10/2003 5/18/2004 MWD2004_Rept04A(and B).jpgManufacturer Model Number KV Mfgr Year
Siemens SPS-38-23-1 36-50 kV 1995
Method of Detection
Cause of Failure
Comments
This CB has been leaking since installation. Utility personnel spent a couple of days
troubleshooting this CB using conventional gas detection methods but were not successful.
The amount of leak was very minimal; about 5 pounds of SF6 gas was added once a yr.GIS came to the power plant on 10/27/03 to perform laser imaging on the breaker. The
camera detected a leak on the supply line fitting of A-Phase; no other leaks were found.
Utility personnel performed soap bubble test to confirm the leak and then adjusted the fitting.
Re-shot of the fitting showed no more SF6 leak. (Photo unavailable for release in this report.)
Circuit Breaker - TroubleIncident # Incident Date Report Date Photo File Name
43949 8/17/2003 4/15/2004
Manufacturer Model Number KV Mfgr Year
Westinghouse Electric 242-SP-50 251-300 kV 1980
Method of Detection
Cause of Failure
Comments
Circuit Breaker - TroubleIncident # Incident Date Report Date Photo File Name
43923 9/10/2003 10/14/2004 IID200304,05,06,07,08,09
Manufacturer Model Number KV Mfgr Year
Siemens BZO121406 151-200 kV 1984
Method of Detection
Tested the bushings and found variable capacitance.
Cause of Failure
Troubles Failures Report Page 8 of 28
8/17/2019 Reporte Fallas 09-30-04
9/28
Comments
Replaced the breaker. (Photos unavailable for release in this report.)
Circuit Breaker - TroubleIncident # Incident Date Report Date Photo File Name
43966 10/2/2003 2/16/2004Manufacturer Model Number KV Mfgr Year
I.T.E. 242-GA63-30C 201-250 kV 1981
Method of Detection
Cause of Failure
Deterioration of capacitor.
Comments
Replacement Capacitors not available-Pole 2 destroyed.
Circuit Breaker - TroubleIncident # Incident Date Report Date Photo File Name
43915 10/18/2003 4/4/2004 BPAT200412,13
Manufacturer Model Number KV Mfgr Year
ABB 550PM 40-30 > 500 kV 2003
Method of Detection
Cause of Failure
Comments
Breaker sent a trip command via SCADA. A & B phases interrupted approximately 250
Amps. C-phase continued to carry load current for approximately 16 cycles. Breaker
Failure Relay operated and cleared the bus. (Photos were unavailable for release in this report.)
Circuit Breaker - In-Service FailureIncident # Incident Date Report Date Photo File Name
43960 10/28/2003 2/23/2004
Manufacturer Model Number KV Mfgr Year
Siemens FCV500 11-15 kV 1979
Method of Detection
Cause of Failure
Trip coil burned, breaker did not operate, took substation off line.
Comments
Failure caused interruption of service to approx. 5000 customers.
Troubles Failures Report Page 9 of 28
8/17/2019 Reporte Fallas 09-30-04
10/28
Circuit Breaker - TroubleIncident # Incident Date Report Date Photo File Name
43943 11/10/2003 3/23/2004 sce2004rept_02
Manufacturer Model Number KV Mfgr Year
ABB 72PMI31-12 51-100 kV 2000
Method of Detection
Cause of Failure
Shorted B-phase close coil causing.
Comments
Close signal was initiated via automatic capacitor controls, B phase close coil
leads were shorted. X relay contacts welded closed causing cb to pump until A phase
interrupter failed. It appears the cb close-opened. (Photo unavailable.)
Circuit Breaker - In-Service Failure
Incident # Incident Date Report Date Photo File Name43909 11/16/2003 4/4/2004 BPAT200401, BPAT200420
Manufacturer Model Number KV Mfgr Year
Brown Boveri Company 72 PM 51-100 kV 1988
Method of Detection
Cause of Failure
Bird droppings from an overhead structure washed down onto the bushings by the rain.
Comments
2 entrance bushings failed. Repair of the breaker required an internal inspection, replacement bushings and
unknown internally damaged parts to be replaced. Time to repair was longer than replacing the breaker
from stock so bkr was replaced. Additionally, the load lost needed to be restored. (Photos unavailable.)
Circuit Breaker - TroubleIncident # Incident Date Report Date Photo File Name
43940 11/26/2003 12/1/2003
Manufacturer Model Number KV Mfgr Year
High Voltage Breakers HVB362 301-350 kV 2003
Method of Detection
Cause of Failure
Defective material in the dashpot piston.
Comments
New breaker not in service. Relay doing final trip testing. Got pole disagreement
alarm. Found bent linkages in the mechanism of one phase. HVB sent factory people
to investigate. Found damage to linkages in mechanism, the aluminum cast support
conductor that holds the puffer piston, the puffer piston, the Teflon nozzle, and
the stationary contacts. HVB removed and replaced the whole phase. Took damaged
Troubles Failures Report Page 10 of 28
8/17/2019 Reporte Fallas 09-30-04
11/28
phase to factory for investigation. HVB acted quickly and performed all repairs
at no cost to utility. Report available.
Circuit Breaker - In-Service FailureIncident # Incident Date Report Date Photo File Name
43925 12/20/2003 4/1/2004Manufacturer Model Number KV Mfgr Year
I.T.E. VRK-15-12 11-15 kV 1972
Method of Detection
Cause of Failure
Failure of mag latch and mech to keep breaker in the tripped position.
Comments
ITE VRKs have a history of mag latch failures and parts are no longer available.
Circuit Breaker - In-Service FailureIncident # Incident Date Report Date Photo File Name
43913 1/6/2004 4/4/2004
Manufacturer Model Number KV Mfgr Year
Pennsylvania Transformer RHE-84L 201-250 kV 1965
Method of Detection
Cause of Failure
Latch valve failed due to lack of lubrication.
Comments
Trouble: OCB failed to reclose. Temperature -32 degrees. Mechanism does not move.
Corrective action - Removed and cleaned latch valve. Cleaned and lubed mechanism.
Circuit Breaker - In-Service FailureIncident # Incident Date Report Date Photo File Name
43912 1/6/2004 4/4/2004
Manufacturer Model Number KV Mfgr Year
Pennsylvania Transformer RHE-84-230-15000 201-250 kV 1965
Method of Detection
Cause of Failure
Comments
Trouble: OCB failed to reclose. Temperature -32 degrees. Mechanism does not move.
Corrective action - Removed and cleaned latch valve. Cleaned and lubed mechanism.
Troubles Failures Report Page 11 of 28
8/17/2019 Reporte Fallas 09-30-04
12/28
Circuit Breaker - In-Service FailureIncident # Incident Date Report Date Photo File Name
43964 1/29/2004 2/23/2004
Manufacturer Model Number KV Mfgr Year
Siemens FCV500 11-15 kV 1979
Method of Detection
Cause of Failure
Trip coil burned, circuit breaker failed to operate on distribution circuit fault.
Comments
When the 12 kV circuit breaker failed to operate, backup relaying sensed the fault
and opened the 115 kV circuit switcher, interrupting service to approximately 5000
customers. This was the 3rd incident in 4 months where failure of a FCV-500 trip
coil caused a station to trip off line.
Circuit Breaker - In-Service FailureIncident # Incident Date Report Date Photo File Name
43956 3/19/2004 4/15/2004
Manufacturer Model Number KV Mfgr Year
Allis-Chalmers FC-500-A1 11-15 kV 1974
Method of Detection
Cause of Failure
Trip mechanism frozen; lubrication dried up.
Comments
ACB WAS OVERHAULED 2 YRS AGO. PLAN TO REVISE LUBRICATION PROCEDURES ON BREAKER
MECHANISMS. THIS ACB FAILED TO OPEN ON A FEEDER FAULT CAUSING THE
BUS OVERCURRENTS TO CLEAR AN ENTIRE BUS SECTION (5 ADDITIONAL CIRCUITS)
Circuit Breaker - TroubleIncident # Incident Date Report Date Photo File Name
43888 7/6/2004 8/4/2004 3449164710432161.JPG
Manufacturer Model Number KV Mfgr Year
ASEA-Brown Boveri 242PMG50-30 201-250 kV 2000
Method of Detection
Visual Inspection
Cause of Failure
Leak/Gasket
Comments
Moisture trapped in the mechanism housing caused massive corrosion damage and multiple
breaks on the disc springs on this AHMA-11 mechanism. The mechanism is not repairable
and is a total loss. Some water found an access into the mechanism housing, apparently
through some inadequate sealing procedures during installation. The drain hole
Troubles Failures Report Page 12 of 28
8/17/2019 Reporte Fallas 09-30-04
13/28
was removed and over one quart of water poured out from the mechanism. A new mechanism
was installed and proper installation and sealing procedures were followed.
Circuit Switcher - TroubleIncident # Incident Date Report Date Photo File Name
43971 7/3/2003 3/25/2004
Manufacturer Model Number KV Mfgr Year
S&C Electric 2040 51-100 kV 1988
Method of Detection
Cause of Failure
Voids & unmelted plastic in Delrin Spring Carrier allowing Red Target to actuate even though there was no SF6 leak.
Comments
We have had 30 or so of these Red Target-Low Gas problems and have been sending
back the Interrupters for a porcelain credit. We were told by the factory that units
between 1988 and 1991 did have manufacturing problems with the carrier, but, notrouble since 1991. Then we had several 1992 and 1995 failures and contacted them
again. Recently we had the S&C Factory research this problem thoroughly and they
have a new repair kit that we can install in the field.
Troubles Failures Report Page 13 of 28
8/17/2019 Reporte Fallas 09-30-04
14/28
Circuit Switcher - TroubleIncident # Incident Date Report Date Photo File Name
43928 7/31/2003 4/1/2004
Manufacturer Model Number KV Mfgr Year
S&C Electric Mark IV 301-350 kV 1978
Method of Detection
Cause of Failure
Unknown. Shipped failed interrupters back to S&C.
Comments
Interrupters on south pole failed to interrupt. Opened circuit with air break arms.
Circuit Switcher - In-Service FailureIncident # Incident Date Report Date Photo File Name
43927 11/1/2003 11/1/2003 IPC2004_Rept03
Manufacturer Model Number KV Mfgr Year S&C Electric S&C 2020 51-100 kV 1994
Method of Detection
Cause of Failure
Comments
Problem with this design, if the circuit switcher fails to trip, (trip coil failure)
the agastat times out and the disconnects open even though the SF6 bottles do
not. The clearances on the open 69 kv disconnects are too close and the energized
line was flashing over phase to phase. This C/S needs a redesign, or we could roll
the C/S 180 so the open disconnects would not be energized when the gas bottles
were closed. (Photo not available for release in this report.)
Circuit Switcher - TroubleIncident # Incident Date Report Date Photo File Name
43914 2/3/2004 4/4/2004 BPAT200403,04,05,
Manufacturer Model Number KV Mfgr Year
S&C Electric Mark IV > 500 kV 1979
Method of Detection
Cause of Failure
Mechanical failure of the interphase linkage.
Comments
While attempting to close circuit switcher via SCADA, the reactor and bus LOR's
operated. South bus LOR reset. Operator reported only two phases closed and linkage
between phases on the ground. (Photo unavailable.)
Troubles Failures Report Page 14 of 28
8/17/2019 Reporte Fallas 09-30-04
15/28
CT - In-Service FailureIncident # Incident Date Report Date Photo File Name
43967 11/27/2003 2/15/2004
Manufacturer Model Number KV Mfgr Year
Haefely IOSK-245 201-250 kV 1985
Method of Detection
Cause of Failure
Internal fault
Comments
CT Column caught on fire & failed due to A Phase to Ground fault. This is a free-standing
oil-filled CT.
CT - In-Service FailureIncident # Incident Date Report Date Photo File Name
43890 11/27/2003 8/16/2004 27131316710412281.ppt
Manufacturer Model Number KV Mfgr Year Trench Electric IOSK-245 201-250 kV 1984
Method of Detection
Other (See Comments), Relay Operation
Cause of Failure
Deteriorated Insulation
Comments
This is for a 230kV free standing CT that failed catastrophically while in service.
Troubles Failures Report Page 15 of 28
8/17/2019 Reporte Fallas 09-30-04
16/28
Insulator - Trouble
Incident # Incident Date Report Date Photo File Name
43936 10/21/2003 3/18/2004 MWD2004_Rept03A(thru H).JPG
Manufacturer Model Number KV Mfgr Year
Other 201-250 kV 1933
Method of Detection
Cause of Failure
Unknown cause but note age of equipment.
Comments
One insulator stack pulled completely away, littering the station floor with insulator
material. (Photo unavailable.)
PT - TroubleIncident # Incident Date Report Date Photo File Name
43935 6/10/2003 3/18/2004
Manufacturer Model Number KV Mfgr Year
General Electric JVM 0-5 kV 1979
Method of Detection
Cause of Failure
Failure attributed to age of the equipment.
Comments
Both units tripped offline. From investigation, both fuses on the primary side
were found blown. TTR revealed shorted turns in the faulty P.T. The P.T. was replaced
with an old spare; new P.T.'s were ordered and will be changed-out at the next scheduled
maintenance. As preventive measures, other hydro plants will be surveyed for
the same type and manufacture P.T., of the same vintage, and consideration given to
performing insulation resistance tests on older P.T.'s during annual shutdowns.
Reactor - In-Service FailureIncident # Incident Date Report Date Photo File Name
43899 2/21/2004 9/14/2004
Manufacturer Model Number KV Mfgr Year
Trench Electric Shunt 26-35 kV 1981
Method of Detection
Other (See Comments)
Cause of Failure
Troubles Failures Report Page 16 of 28
8/17/2019 Reporte Fallas 09-30-04
17/28
Deteriorated Insulation
Comments
After the reactor circuit breaker tripped, a lockout alarm indication was given.
A turn-to-turn failure occurred on the inside package of the reactor. Trench stated
that switching surges over long term operation can cause a shorted turn that creates
a high circulating current blowing out the winding. At 23 years old Trench stated
that it served its useful life. Inspection of other units was suggested. Reactorsof this age don't have arresters. New ones do to protect from TOVs during switching.
Consequently, we will be adding arresters to the other reactors in service.
Regulator - In-Service FailureIncident # Incident Date Report Date Photo File Name
43938 6/3/2004 3/25/2004 PAC200401a,b,c
Manufacturer Model Number KV Mfgr Year
Siemens JFR 16-20 kV 2002
Method of Detection
Cause of Failure
Spring failure - Siemens has redesigned the spring to a compression type.
Comments
We have seen several new model JFR regulators with this problem. Usually when a
drive spring breaks the operating mech jams. However this regulator tried to go
through the neutral position with only motor drive and caused an open circuit at the
reversing switch. (Photo was not available for release in this report.)
Relay - In-Service FailureIncident # Incident Date Report Date Photo File Name
43963 1/28/2004 2/23/2004
Manufacturer Model Number KV Mfgr Year
Basler BE1-51 N/A 1996
Method of Detection
Cause of Failure
Relay housing did not short CT circuit when relay was pulled for maintenance.
Comments
When the relay technician was removing a Basler BE1-51 relay for maintenance, theshorting device did not make a connection to the CT circuit. When the paddle was
removed, technician heard buzzing noise (from CT opening), then differential relay
operated, opening circuit switcher. Service interrupted to about 5000 customers
for several minutes until relay re-installed and station put back on line.
Troubles Failures Report Page 17 of 28
8/17/2019 Reporte Fallas 09-30-04
18/28
Switch - TroubleIncident # Incident Date Report Date Photo File Name
43911 5/14/2003 4/4/2004 BPAT200402
Manufacturer Model Number KV Mfgr Year
(No MFR Listed) TA-3A 251-300 kV 1964
Method of Detection
Cause of Failure
C-phase of the disconnect mechanically failed & stayed in the harp while operating the
disconnect switch. A-phase and B-phase opened normally.
Comments
This Schwager-Wood disconnect had a history of problems, likely associated to the
instability of the ground conditions at the site. The C-phase blade was found loose,
in the harp, in a rotated position. The crank arm at the hinge end was fully rotated
in the full open position. It does not appear that the blade left the harp during
operation. (Photo unavailable for release in this report.)
Switch - In-Service FailureIncident # Incident Date Report Date Photo File Name
43910 5/16/2003 4/4/2004
Manufacturer Model Number KV Mfgr Year
Allis-Chalmers Pantograph > 500 kV 1968
Method of Detection
Cause of Failure
Mechanical failure of pantograph-type blade on the disconnect.
Comments
It has been determined that this disconnect is not needed on the system anymore due
to system configuration changes. It is scheduled to be removed. Removal of this
disconnect will allow us to have spare parts for the remaining 8 pantograph disconnects
on our system pending replacement.
Switch - Failure at TestIncident # Incident Date Report Date Photo File Name
43894 7/20/2004 8/30/2004
Manufacturer Model Number KV Mfgr Year
(No MFR Listed) EV-1 > 500 kV
Method of Detection
Other (See Comments)
Cause of Failure
Other (See Comments)
Comments
The equipment was a Southern States EV-1 500-kV disconnect switch. The part that
Troubles Failures Report Page 18 of 28
8/17/2019 Reporte Fallas 09-30-04
19/28
failed was the VM-1, slave, motor operator on A-phase. When the
MOD (Motor Operated Disconnect) was operated, A-phase motor operator continued
to turn after the blade was fully open. This caused the coupling between the gear
box and the shaft connected to the rotating stack to fail. After this occurred,
the motor operator continued to spin, breaking off all open and close stops on the
motor operator. The motor operator was finally stopped when the DC control knife
switch was pulled. It was found that the 1" stainless steel gear shaft was crackedvertically.
The entire motor operator was replaced.
Transformer - In-Service FailureIncident # Incident Date Report Date Photo File Name
43917 5/17/2003 4/4/2004
Manufacturer Model Number KV Mfgr Year
Wagner Electric HAL 24 101-150 kV 1951
Method of Detection
Cause of Failure
Winding failure due to lightning.
Comments
Through Fault
Transformer - In-Service FailureIncident # Incident Date Report Date Photo File Name
43958 6/6/2003 2/23/2004
Manufacturer Model Number KV Mfgr Year
Federal Pacific Electric Transformer, LTC 101-150 kV 1968
Method of Detection
Cause of Failure
A high-current, three phase, through fault occurred and the transformer failed.
Comments
Failure caused interruption of service to 3000 customers including several large
industrials. This vintage of FPE transformer is prone to failure. We purchased
5 of these in 1968 and all five have now failed. Most of them failed during a through-fault.
Transformer - In-Service FailureIncident # Incident Date Report Date Photo File Name
43929 6/19/2003 4/1/2004
Manufacturer Model Number KV Mfgr Year
Wagner Electric 101-150 kV 1970
Method of Detection
Troubles Failures Report Page 19 of 28
8/17/2019 Reporte Fallas 09-30-04
20/28
Cause of Failure
Poor design.
Comments
Through-fault during lightning storm (windings failed).
Transformer - In-Service FailureIncident # Incident Date Report Date Photo File Name
43908 6/20/2003 4/23/2004
Manufacturer Model Number KV Mfgr Year
Westinghouse Electric 101-150 kV 1964
Method of Detection
Cause of Failure
Possibly Lightning
CommentsHoop failure (progressive turn-to-turn fault); replaced the transformer.
Transformer - TroubleIncident # Incident Date Report Date Photo File Name
43944 7/3/2003 3/23/2004 sce2004_Rept03
Manufacturer Model Number KV Mfgr Year
Westinghouse Electric Unknown 1954
Method of Detection
Cause of Failure
Probably age related.
Comments
Contact leaf spring failed. (Photo unavailable.)
Transformer - In-Service FailureIncident # Incident Date Report Date Photo File Name
43959 7/5/2003 2/23/2004 SNPD2004_Rept02a,b,c
Manufacturer Model Number KV Mfgr Year
General Electric Transf, w LTC 101-150 kV 1975
Method of Detection
Cause of Failure
Squirrel contacted 12 kV bus on source side of circuit breaker. Corroded wiring prevented
circuit switcher from tripping. Sustained fault caused much damage
Comments
Fault started when a squirrel contacted the source side of an outdoor 12 kV breaker.
Troubles Failures Report Page 20 of 28
8/17/2019 Reporte Fallas 09-30-04
21/28
The fault grew and involved all three-phases. Relays saw the fault properly, and
provided signal to circuit switcher to trip. Circuit switcher did not trip due
to corroded wiring inside conduit (not visible from ends). Fault and fire damage
was extensive. Two breakers and bus support structure were burned. Transformer
failed during the through-fault. Service interrupted to 5000 customers. (Photo unavailable.)
Transformer - In-Service FailureIncident # Incident Date Report Date Photo File Name
43972 7/10/2003 4/22/2004
Manufacturer Model Number KV Mfgr Year
Virginia Transformer 51-100 kV 1993
Method of Detection
Cause of Failure
Unknown
CommentsTurn to turn failure on the secondary winding. Performed complete rewinding of all coils,
testing and tank refurbishment, repair of load tap changer, installation of new remote
temperature gauges, new insulating oil, install tap changer filter unit, desiccant drier breather.
Transformer - In-Service FailureIncident # Incident Date Report Date Photo File Name
43931 8/4/2003 4/2/2004
Manufacturer Model Number KV Mfgr Year
General Electric 451-500 kV
Method of Detection
Cause of Failure
Comments
This transformer has Trench 287 kV high-voltage composite bushings.
A flashover occurred between the bottom plate and the tank wall of the transformer
and another fault between the upper part of the oil impregnated paper winding and
the flange of the composite insulator. All high-voltage bushings were replaced.
Transformer - In-Service FailureIncident # Incident Date Report Date Photo File Name
43970 8/19/2003 3/25/2004
Manufacturer Model Number KV Mfgr Year
General Electric 367 MVA 451-500 kV 1981
Method of Detection
Troubles Failures Report Page 21 of 28
8/17/2019 Reporte Fallas 09-30-04
22/28
Cause of Failure
Lightning strike to bushing (H S bushing)
Comments
Bushing failed due to low oil level resulting in lower BIL, water had entered bushing
on top terminal gasket. Due to internal damage, replaced transformer.
Transformer - TroubleIncident # Incident Date Report Date Photo File Name
43965 9/10/2003 3/2/2004
Manufacturer Model Number KV Mfgr Year
Ferranti, Ltd. Transformer LTC 101-150 kV 1995
Method of Detection
LTC was severely coked and producing high levels of ethylene.
Cause of Failure
Poor design and/or quality of LTC
CommentsProblems were uncovered during routine DGA of the tap changer oil. The first test
showed extremely high levels of ethylene, about 100 times normal. We suspected
the test was faulty, so a second sample was drawn, and it had 145,000 ppm ethylene.
The Doble lab reported this ethylene level was the highest they have ever recorded
in a DGA sample. The tap changer was maintained less than 2 years ago and has an
oil filtration unit installed. When opened up, the reversing switch had severe
coking. Movable and stationary contacts also required replacement.
Transformer - In-Service FailureIncident # Incident Date Report Date Photo File Name
43941 10/1/2003 10/22/2003
Manufacturer Model Number KV Mfgr Year
General Electric LRT-200-2 Unknown
Method of Detection
Cause of Failure
Bypass switch assembly misalignment on phase 3.
Comments
Transformer failed due to tap changer failure. Report available.
Transformer - TroubleIncident # Incident Date Report Date Photo File Name
43957 10/14/2003 4/15/2004
Manufacturer Model Number KV Mfgr Year
Federal Pacific Electric 51-100 1974
Method of Detection
Troubles Failures Report Page 22 of 28
8/17/2019 Reporte Fallas 09-30-04
23/28
Cause of Failure
Low side turn-to-turn failure.
Comments
DGA RESULTS - * The equipment condition code has been abnormal (2-3) since 08/13/2003.
The high CO2/CO ratio may indicate thermal decomposition of cellulose. Exercise
caution. Determine load dependence.
Transformer - TroubleIncident # Incident Date Report Date Photo File Name
43920 11/29/2003 4/4/2004 BPAT200406
Manufacturer Model Number KV Mfgr Year
Hyundai BPA001000891 101-150 kV
Method of Detection
Cause of FailureLow voltage leads flashed over to the core.
Comments
The transformer tripped by two sets of differential, the Buchholz and the pressure relief
device operated. The 115 KV breaker at Drummond and the 161 KV breaker at Goshen
(72 miles) isolated the failed transformer within 4 cycles. The quick response from the
relays and breaker may have prevented further damage to the transformer. There were
of combustible gasses in the oil including acetylene, but the transformer tested OK
electrically. The manufacturer reported to the site within one week after the failure,
inspected the transformer and found that there was a dielectric breakdown between the
X1 C-phase and X2 B-phase leads and the core clamping structure through a lead
supporting board for X1, X2 and X3 leads. The failure occurred close to the X1 bushing
after the lead makes a 90 degrees angle from vertical to horizontal. (Photo unavailable.)
Transformer - In-Service FailureIncident # Incident Date Report Date Photo File Name
43930 1/13/2004 4/2/2004
Manufacturer Model Number KV Mfgr Year
General Electric FOA 451-500 kV
Method of Detection
Cause of Failure
Bushing Failure
Comments
Trench 230kv bushing failure caused total loss of transformer. We are replacing
all of these type composite bushings.
Troubles Failures Report Page 23 of 28
8/17/2019 Reporte Fallas 09-30-04
24/28
Transformer - TroubleIncident # Incident Date Report Date Photo File Name
43907 1/15/2004 4/23/2004 AVA2004_01
Manufacturer Model Number KV Mfgr Year
Alsthom > 500 kV 2002
Method of Detection
Cause of Failure
Comments
High voltage winding insulation failed. (Photo unavailable.)
Transformer - TroubleIncident # Incident Date Report Date Photo File Name
43918 1/16/2004 4/4/2004 BPAT200407,08,09,10,11
Manufacturer Model Number KV Mfgr Year Allis-Chalmers 301-350 kV 1963
Method of Detection
Cause of Failure
Internal fault leading to winding failure.
Comments
(Photos unavailable.)
Transformer - TroubleIncident # Incident Date Report Date Photo File Name43932 2/16/2004 4/2/2004
Manufacturer Model Number KV Mfgr Year
ASEA Inc. TFTY1000 201-250 kV
Method of Detection
Cause of Failure
Internal fault caused can to split a welded seam along the lid on low-voltage side of transformer.
Comments
Unit was 8 years beyond design life, paper insulation degradation, 2300 piles driven
into ground in area for new construction, and decrease in insulation distance between
18kv internal delta bus at bottom of transformer tank.
Transformer - TroubleIncident # Incident Date Report Date Photo File Name
43933 2/17/2004 4/26/2004 MID200401,02,03
Manufacturer Model Number KV Mfgr Year
Troubles Failures Report Page 24 of 28
8/17/2019 Reporte Fallas 09-30-04
25/28
Kuhlman Electric 51-100 kV 1979
Method of Detection
Cause of Failure
Possibly due to previous over tightening of wire connection to collection ring stud.
Comments
An inspection of the LTC was made as part of the regular maintenance when the electriciannoticed the phenolic collector ring panel was burnt. The two studs passing through
the phenolic collector ring panel from the collector ring overheated causing the
board and studs to deteriorate. The 3/4" studs are reduced to 1/2" on the end connecting
to the collector ring. Solder is then sweat into the threads from the other side
(penetrating approx. 1/4"). I suspect the stud had loosened from the collector ring
(possibly due to previous over tightening) and overheated to the point the cable,
with the studs attached, came loose in the electricians hand. (Photo unavailable.)
Transformer - TroubleIncident # Incident Date Report Date Photo File Name43919 2/20/2004 4/4/2004 BPAT200421, 22
Manufacturer Model Number KV Mfgr Year
Allis-Chalmers 301-350 kV 1963
Method of Detection
Cause of Failure
Internal Fault
Comments
Winding failure. (Photo unavailable.)
Transformer - TroubleIncident # Incident Date Report Date Photo File Name
43945 3/19/2004 3/23/2004 sce2004_Rept04a,b
Manufacturer Model Number KV Mfgr Year
General Electric Unknown 1951
Method of Detection
Cause of Failure
Tracking and burning of the insulating drum on NLTC allowed the conductor contact pointsto be misaligned and become loose. Severe arcing occurred.
Comments
Uneconomical to repair unit. This station is isolated load
so a generator had to be installed to off load transformer. (Photo unavailable.)
Troubles Failures Report Page 25 of 28
8/17/2019 Reporte Fallas 09-30-04
26/28
Transformer - TroubleIncident # Incident Date Report Date Photo File Name
43955 3/30/2004 4/15/2004 Sdge2004Rept10A-G.JPG
Manufacturer Model Number KV Mfgr Year
Waukesha LTC PWR XFMR 2002
Method of Detection
Cause of Failure
High moisture.
Comments
Before we put the bank in service in April of 2003 , it failed the Doble test. When
we opened it up we found severe rust all over the core. Waukesha came out and cleaned
it up and called it good. It still Doble tested bad. It started gassing so it
was taken out of service. We Doble tested it before Waukesha reps got here to see
if it was worse than the initial test; it was. The CL watts went from 1.543 to 6.619 and the
CHL watts went up to 8.250 from 1.895. We also megger tested it again to see if that
had gotten worse and it did. Low to ground was 10.7 gig ohms and now it only got89.7 meg ohms. When Waukesha drained it and opened it up on 3-21-04, the rust and
contamination looked worse than it did back in March of 2003. In March of 2003,
Waukesha drained and processed the oil for 24 hours. This was after they got inside
and cleaned up the rust off of the top of the core. The transformer came to us from
Waukesha with oil in it. The only time it was opened up when it was originally put in
service was when the factory rep was here to supervise the installation of the bushings.
Two-Winding Transformer - In-Service FailureIncident # Incident Date Report Date Photo File Name
43898 1/4/2004 9/14/2004
Manufacturer Model Number KV Mfgr Year
General Electric L252778A 1981
Method of Detection
Relay Operation
Cause of Failure
Other (See Comments)
Comments
B phase (center) failure - could have been the winding insulation (most likely)
and/or the B phase HV bushing.
Two-Winding Transformer - In-Service FailureIncident # Incident Date Report Date Photo File Name
43889 2/4/2004 8/16/2004
Manufacturer Model Number KV Mfgr Year
General Electric GE 12/16/20 @55degC 51-100 kV 1981
Method of Detection
Troubles Failures Report Page 26 of 28
8/17/2019 Reporte Fallas 09-30-04
27/28
Power Factor, TCG
Cause of Failure
Winding
Comments
Two-Winding Transformer - In-Service FailureIncident # Incident Date Report Date Photo File Name
43895 7/2/2004 9/2/2004 5230132810442451.jpg
Manufacturer Model Number KV Mfgr Year
General Electric D
Method of Detection
Exciting Current
Cause of Failure
Through-Fault
Comments
This unit has X1-X0 winding damage that showed up in TTR and excitation tests.
INTERNAL INSPECTION RESULTS
The coil structure that contains the H1-H3/X1-XO windings shows subtle evidence
that movement occurred in the structure. There are spacers in multiple areas of
the winding that have shifted out of their normal position. The LV leads that exit
the coil structure had ripped the cloth that originally tied some bracing blocks
to the leads. On one location at the bottom of the coil structure the blocking
was out of alignment. No tipping of the HV conductors or core damage could be observed.
Troubles Failures Report Page 27 of 28
8/17/2019 Reporte Fallas 09-30-04
28/28
Two-Winding Transformer - Failure at TestIncident # Incident Date Report Date Photo File Name
43897 8/24/2004 9/9/2004
Manufacturer Model Number KV Mfgr Year
Westinghouse SL 1984
Method of Detection
Partial Discharge
Cause of Failure
Winding
Comments
Two-Winding Transformer - In-Service FailureIncident # Incident Date Report Date Photo File Name
43896 8/30/2004 9/9/2004Manufacturer Model Number KV Mfgr Year
ASEA-Brown Boveri SL 1997
Method of Detection
Relay Operation
Cause of Failure
Winding
Comments