UNIVERSIDAD NACIONAL SEDE TUMACO Revisión 27/02/12 DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC Pág. 1 de 34 1/34 SEDE TUMACO INFORME MEMORIA GENERAL DE DISEÑO APROBÓ REALIZO AIREG S.A.S ING. DIEGO GONZALO CASTRO Firma: Firma: FEBRERO DE 2017

Transcript of UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra...

Page 1: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 27/02/12

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 1 de 34

1/34

SEDE TUMACO

INFORME

MEMORIA GENERAL DE DISEÑO

APROBÓ

REALIZO AIREG S.A.S

ING. DIEGO GONZALO CASTRO Firma:

Firma:

FEBRERO DE 2017

Page 2: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 27/02/12

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 2 de 34

2/34

TABLA DE CONTENIDO

Pagina

1. DESCRIPCIÓN GENERAL 4

1.1. OBJETO DEL PROYECTO 4

1.2. DESCRIPCIÓN SISTEMAS GENERALES 4

1.3. DESCRIPCIÓN SISTEMA DE CONTROL 8

2. BASES DE DISEÑO 11

2.1. CONDICIONES EXTERIORES 11

2.2. CONDICIONES INTERIORES 11

2.3. NIVELES DE VENTILACION 11

2.4. CONDUCTOS DE AIRE 11

2.5. REJILLAS Y DIFUSORES 12

3. NORMATIVIDAD 13

4. CONDICIONES PREVIAS DE INSTALACIÓN 14

4.1. ALCANCE DEL CONTRATO 14

4.2. TRABAJOS POR OTROS CONTRATISTAS 15

4.3. REQUISITOS DE LOS MATERIALES Y LA INSTALACIÓN 16

4.4. REQUISITOS DE LOS EQUIPOS 16

5. CONDICIONES POSTERIORES A LA INSTALACION 18

5.1. MATENIMIENTO 18

5.2. PRUEBAS Y BALANCEO “PYB” 18

5.3. DOCUMENTOS PARA LA ENTREGA FINAL 19

6. MEMORIAS DE CÁLCULO 21

6.1. CARGAS TÉRMICAS 21

6.2. ELEMENTOS FINITOS 22

6.3. EXTRACCIONES MECÁNICAS 22

Page 3: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 27/02/12

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 3 de 34

3/34

6.4. VENTILACIONES MECÁNICAS 23

6.5. CALCULO DUCTOS 23

6.6. SELECCIÓN TUBERÍAS DE REFRIGERACIÓN 24

6.7. SISTEMA ELÉCTRICO 24

6.8. SISTEMA DE CONTROL 25

7. ANEXOS 26

7.1. CÁLCULOS 26

7.2. SELECCIÓN DE EQUIPOS 26

Page 4: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 27/02/12

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 4 de 34

4/34

1. DESCRIPCIÓN GENERAL 1.1. OBJETO DEL PROYECTO Es el objeto del proyecto, suministrar, instalar y poner en marcha los sistemas de aire acondicionado, ventilación y extracción mecánica, para las áreas que así lo requieran para LA UNIVERSIDAD NACIONAL SEDE TUMACO. 1.2. DESCRIPCIÓN SISTEMAS GENERALES El sistema de aire acondicionado para LA UNIVERSIDAD NACIONAL SEDE TUMACO en adelante UNT es ajustado a la normatividad de cada área en particular y contará con: Sistema de refrigerante variable que utiliza refrigerante R-410A que no daña la capa de ozono, compuesto por unidad condensadora ubicada al exterior de los diferentes bloques como se observa en los planos respectivos, y unidades interiores tipo cassette que atenderán las diversas áreas que así lo requieran en cada uno de los bloques, según la siguiente distribución: Sistema de refrigerante variable (UCRV-01 y UFCCV-01A al 24A) que atenderá las áreas de Biblioteca y Laboratorios 1 al 4 del Bloque A1. Sistema de refrigerante variable (UCRV-02 y UFCCV-01B al 12B) que atenderá las áreas de Aulas 1 al 4 del Bloque B1. Sistema de refrigerante variable (UCRV-03 y UFCCV-13B al 19B) que atenderá las áreas de Oficinas de docentes, Zona de trabajo autónomo, Rack y Cuarto técnico del Bloque B1. Sistema de refrigerante variable (UCRV-04 y UFCCV-01C al 11C) que atenderá las áreas de Centro de control, Cuarto ICE, Zona de trabajo autónomo, Salón ICI Rack y Cuarto técnico del Bloque C1.

Page 5: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 27/02/12

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 5 de 34

5/34

Una unidad minisplit consola tipo cassete de una vía (UMSC / UCMSC-01), compuesta por una unidad interna y una unidad condensadora externa, ambas del mismo fabricante y capacidad. Ubicada en el cuarto de Rack del Bloque D y en la cubierta. Como se muestra en planos y especificaciones técnicas. Una unidad minisplit consola tipo cassete de una vía (UMSC / UCMSC-02), compuesta por una unidad interna y una unidad condensadora externa, ambas del mismo fabricante y capacidad. Ubicada en el cuarto de control del bloque D del y en la cubierta. Como se muestra en planos y especificaciones técnicas. Una unidad minisplit consola tipo pared (UMSP / UCMSP-01), compuesta por una unidad interna y una unidad condensadora externa, ambas del mismo fabricante y capacidad. Ubicada en el área de atención de la portería. Como se muestra en planos y especificaciones técnicas. Sistema de filtración para aire exterior (BF-01 al 04) contará con banco de filtros acorde a la norma EN-13779 utilizando filtros categoría F5 ubicados en gabinetes en lámina galvanizada en la toma de aire de los sistemas de ventilación. Ubicados en las cubiertas de los diferentes bloques. Como se muestra en los planos y especificaciones técnicas. Una unidad de extracción, tipo hongo (VE-01). Ubicado en la cubierta. Para la extracción de olores de los baños del Bloque A. Como se muestra en planos y especificaciones técnicas. Una unidad de extracción, tipo hongo (VE-02). Ubicado en la cubierta. Para la extracción de olores de los baños del Bloque B. Como se muestra en planos y especificaciones técnicas. Una unidad de extracción, tipo hongo (VE-03). Ubicado en la cubierta. Para la extracción de olores de los baños del Bloque B.. Como se muestra en planos y especificaciones técnicas. Dos unidades de extracción, axial de pared (VE-04 y 05). Ubicadas en la pared de los Baños, para la extracción de olores de los baños del bloque D. Como se muestra en planos y especificaciones técnicas.

Page 6: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 27/02/12

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 6 de 34

6/34

Una unidad de extracción, tipo centrifuga (VE-06).Ubicado en la cubierta. Para ambientes corrosivos y/o explosivos. Para la extracción de vapores y gases nocivos de las áreas de almacén de químicos Bloque A. Como se muestra en planos y especificaciones técnicas Dos unidades de extracción, axial de pared (VE-07). Ubicadas en la pared, para la extracción de olores de los baños de la portería. Como se muestra en planos y especificaciones técnicas. Una unidad de extracción, tipo hongo (VE-08).Ubicado en la cubierta. Para la extracción de olores del cuarto de residuos de las áreas anexas. Como se muestra en planos y especificaciones técnicas. Dos unidades de extracción, axial de pared (VE-09). Ubicadas en la pared, para la extracción de olores del área de reciclables en el centro de residuos. Como se muestra en planos y especificaciones técnicas. Ventiladores de techo para mejorar las condiciones de confort en aquellas áreas donde no es exigido el sistema de aire acondicionado, extracción o ventilación mecánica. Seis unidades de ventiladora de techo. (VET-01A al 06A). Anclado a la placa. Para mejorar la sensación térmica y generar movimiento de aire en las áreas libres del Bloque A. Como se muestra en planos y especificaciones técnicas. Ocho unidades de ventiladora de techo. (VET-01B al 08B). Anclado a la placa. Para mejorar la sensación térmica y generar movimiento de aire en las áreas libres y restaurante del Bloque B. Como se muestra en planos y especificaciones técnicas. Cinco unidades de ventiladora de techo. (VET-01C al 05C). Anclado a la placa. Para mejorar la sensación térmica y generar movimiento de aire en las áreas libres Bloque C. Como se muestra en planos y especificaciones técnicas.

Page 7: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 27/02/12

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 7 de 34

7/34

Cuatro unidades de ventiladora de techo. (VET-01D al 04D). Anclado a la placa. Para mejorar la sensación térmica y generar movimiento de aire en las áreas libres Bloque D. Como se muestra en planos y especificaciones técnicas. Una Unidad tipo paquete (UPA-01) condensada por aire de expansión directa Variable, Ubicada en la cubierta. Para atender el área del Auditorio del bloque D Como se muestra en planos y especificaciones técnicas. Seis unidad recuperadoras de calor estática (URCV-01 al 06) del mismo fabrícate y totalmente compatible con las unidades de refrigerante. Ubicada en le cielorraso. Para el pre-enfriamiento del aire exterior de las áreas atendidas por al (UCRV-01) Como se muestra en planos y especificaciones técnicas. Una unidad recuperadora de calor estática (URCV-07 a 10) del mismo fabrícate y totalmente compatible con las unidades de refrigerante. Ubicada en le cielorraso. Para el pre-enfriamiento del aire exterior de las áreas atendidas por al (UCRV-02) Como se muestra en planos y especificaciones técnicas. Una unidad recuperadora de calor estática (URCV-11 y 12) del mismo fabrícate y totalmente compatible con las unidades de refrigerante. Ubicada en le cielorraso. Para el pre-enfriamiento del aire exterior de las áreas atendidas por al (UCRV-03) Como se muestra en planos y especificaciones técnicas. Una unidad recuperadora de calor estática (URCV-13 y 14) del mismo fabrícate y totalmente compatible con las unidades de refrigerante. Ubicada en le cielorraso. Para el pre-enfriamiento del aire exterior de las áreas atendidas por al (UCRV-04) Como se muestra en planos y especificaciones técnicas. Una unidad recuperadora de calor estática (URCV-15) del mismo fabrícate y totalmente compatible con la unidad tipo paquete. Ubicada en le cielorraso. Para el pre-enfriamiento del aire exterior de las áreas atendidas por la (UPA-01) Como se muestra en planos y especificaciones técnicas.

Page 8: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 27/02/12

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 8 de 34

8/34

1.3. DESCRIPCIÓN SISTEMA DE CONTROL 1.3.1 Descripción general El sistema de control implementado, se encargará del control automático de la temperatura de manera independiente de cada una de las áreas que contarán con el sistema de climatización. Contará con un tablero de fuerza y control, Un controlador central para el sistema de refrigerante variable, conectado al BMS del proyecto, de tal manera que mediante el, se pueda limitar los rangos de temperatura y establecer los horarios de operación para cada uno de los espacios, para ello en cada uno de los espacios se cuenta con termostato mediante el cual se pueda ajustar la temperatura deseada siempre dentro de los limitas de la norma y permitir el encendido y apagado del mismo y un sensor de CO2 por área para permitir el encendido de la unidad recuperadora de calor cuando alguna de las áreas requiera de aire exterior según se alcance el límite de CO2. 1.3.2 Topología de Red La topología de red planteada para el sistema, contempla el uso de un termostato digitales en cada área atendida, un control centralizado, con pantalla táctil, y la posibilidad de integrarse al sistema BMS mediante el protocolo LonWork. Contará con sensores de CO2, conectados al controlador del sistema. (Ver Diagrama) 1.3.3 Controladores Se utilizará un controlador centralizado, del mismo fabricante del sistema de Refrigerante variable. Que cuente como mínimo con las siguientes funciones. Control horario de las diferentes unidades del sistema Punto adicional de control tipo contacto seco, programable por horario para las unidades de extracción y ventilación. Display de programación y visualización de parámetros. Permitir la conexión a PC tipo web server

Page 9: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 27/02/12

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 9 de 34

9/34

1.3.4 Sensores y actuadores El sistema contará con un termostato, no programables del mismo fabricante del sistema variable, debe incluir el cable de conexión al equipo, permitirá seleccionar la temperatura de operación, siempre dentro de los límites establecidos por el controlador centralizado, y permitirá el encendido y apagado de la unidad. Para cumplir con los niveles de ventilación y ahorro energético se utilizarán sensores de CO2 El encendido, control de temperatura, y encendido de las unidades recuperadoras se realizará mediante protocolo propietario del fabricante del sistema de refrigerante variable Se contara con sensores diferenciales de presión con indicador, para el monitoreo de la saturación de los filtros de los bancos. Se contara con switch diferenciales de presión en los ventiladores tipo hongo y centrifugos para el monitoreo del estatus de encendido 1.3.5 Cableado y canalizaciones El cableado de control, incluye la conexión entre los equipos y condensadoras, siempre de acuerdo a lo solicitado por el fabricante. El cual podrá cambiar las especificaciones del diseño presentado. El cableado entre el termostato y el equipo será suministrado por el fabricante junto con el termostato. El cableado será del tipo vehicular 2x18 AWG blindado y apantallado para voltaje de 24 VAC (este cableado debe ser aprobado y/o modificado por el fabricante) Los cables de señales de los sensores será tipo vehicular 4x18 AWG blindado y apantallado para voltaje de 24 VAC. Los cables de señales de switch y control será tipo vehicular 2x22 AWG para voltaje de 24 VAC.

Page 10: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 27/02/12

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 10 de 34

10/34

La tubería será tipo EMT (para interiores) e IMC (para exteriores), incluyendo todos los accesorios de montaje, entre ellos se contempla, Conduletas, cajas de paso, terminales y coraza tipo americano para la conexión final a las unidades. Todas las terminaciones de cable, serán marquilladas, donde se indique el circuito de control el tipo de señal y las características necesarias para su identificación.

Page 11: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 27/02/12

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 11 de 34

11/34

2. BASES DE DISEÑO

Para el presente diseño se tuvieron en cuenta los siguientes parámetros: 2.1. CONDICIONES EXTERIORES Temperatura bulbo seco 85 °F (29.4°C) Temperatura de bulbo húmedo coincidente 82 °F (27.7°C) Altura sobre el nivel del mar 7 pies (2 m.) Latitud 1 Clasificación de contaminación exterior EN 13779:2007 ODA 1 2.2. CONDICIONES INTERIORES Temperatura bulbo seco verano EN-15251 2007 78,8 °F (26°C) Temperatura vulvo seco para cuartos de comunicaciones UNAL N-TIC-OM-11.006 10°C a 35°C Humedad relativa para cuartos de comunicaciones UNAL N-TIC-OM-11.006 <85% Velocidad Máxima de Aire 0.22 m/s 2.3. NIVELES DE VENTILACION Acorde a EN-15251 2007 0,7 l/s/p 0,35 l/s/m2 2.4. CONDUCTOS DE AIRE Longitud máxima de Mangueras. 2 mts Máxima perdida de presión. 0.15 ft/100ft Velocidad Máxima espacios ocupados. 1200 fpm Velocidad Máxima espacios libres. 1600 fpm

Page 12: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 27/02/12

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 12 de 34

12/34

2.5. REJILLAS Y DIFUSORES Velocidad Rejillas de Suministro. 500 fpm Velocidad Rejillas de Extracción. 500 fpm

Page 13: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 27/02/12

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 13 de 34

13/34

3. NORMATIVIDAD

Para el suministro e instalación del sistema de aire acondicionado, ventilación y Extracción mecánica se deberán cumplir y seguir los siguientes códigos y normas existentes en la industria de tal forma que garanticen seguridad al recurso humano y los bienes, garantice calidad en el montaje y funcionamiento del sistema y cumpla con los valores permitidos y considerados como aceptables respecto a la calidad de la energía, como complemento a estas especificaciones particulares. Norma Europea NF EN 15251 de 2007 Critères d’ambiance intérieure pour la conception et évaluation de la performance énergétique des bâtiments couvrant la qualité de l’air intérieur, la thermique, l’éclairage et l’acoustiqueCrStandard. Norma Europea EN 13779 de 2007 Ventilation for non-residential buildings – Performance requirements for ventilation and room-conditioning systems. American Society Heating Refrigeration air-conditioning Engineers (ASHRAE) Standard 90.1 Sheet Metal and Air Conditioning Suppliers National Association (SMACNA) HVAC Systems Duct Design HVAC Duct Construction Standards - Metal and Flexible HVAC Systems - Testing, Adjusting and Balancing. Instituto Colombiano de Normas Técnicas (ICONTEC) Código eléctrico colombiano NTC 2050 Reglamento Técnico de Instalaciones Eléctricas (RETIE), última actualización.

Page 14: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 27/02/12

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 14 de 34

14/34

4. CONDICIONES PREVIAS DE INSTALACIÓN

4.1. ALCANCE DEL CONTRATO El contratista deberá estudiar todos los documentos entregados con el presente diseño, y solicitar las aclaraciones, o información complementaria que requiera. Cualquier omisión de información del presente pliego deberá ponerla en conocimiento antes de entregar la oferta respectiva. El contratista deberá suministrar, instalar y poner en marcha todos los sistemas especificados en el presente pliego de especificaciones y en los planos complementarios. Los planos del proyecto deberán ser minuciosamente estudiados con respecto a la localización de elementos. Cualquier discrepancia, conflicto u omisión deberá ser reportada a UNT o al diseñador del proyecto con el fin de ser resuelta lo antes posible. El contratista deberá inspeccionar la obra con el fin de verificar que todos los equipos se pueden instalar donde están indicados. Cualquier discrepancia, conflicto u omisión deberá ser reportada a UNT o al diseñador del proyecto con el fin de ser resuelta antes del inicio de los trabajos. El contratista será el encargado y responsable del transporte, movilización e izada hasta puesta en sitio de los todos los equipos y partes, El contratista deberá proteger todos los materiales y el trabajo realizado por sus empleados y será el responsable de los daños que estos causen. El contratista será responsable por su trabajo y equipos hasta que hayan sido finalmente probados y recibidos. El contratista deberá proteger cualquier material que no haya sido instalado inmediatamente. Todas las conexiones eléctricas finales a los equipos y dispositivos de control, serán hechas por el contratista de aire acondicionado.

Page 15: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 27/02/12

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 15 de 34

15/34

Después de poner en marcha los equipos, el contratista deberá llevar a cabo todas las pruebas y ajustes necesarios de los equipos, redes de distribución de aire y agua, de acuerdo con el procedimiento de Prueba y Balanceo “PYB” explicado más adelante. El contratista instalará, conectará, pondrá en funcionamiento y probará todo el sistema de control especificado. El personal a emplear en este trabajo por el Contratista debe ser experimentado en su oficio y especializado en el ramo. La obra deberá contar con un Director, quien deberá ser un ingeniero matriculado y especializado en instalación de sistemas de Aire Acondicionado y Ventilación Mecánica, quien deberá supervisar el desarrollo de las diferentes fases del trabajo y será el responsable de su buena ejecución. Adicionalmente, el Contratista deberá proporcionar un Ingeniero Residente quien estará dedicado a la obra de tiempo completo durante el montaje de conductos y tuberías, el montaje de los equipos y su puesta en marcha. A la propuesta del Contratista se deberán adjuntar las hojas de vida del Ingeniero Director y del Ingeniero Residente, los cuales deberán mantenerse durante el transcurso de la obra, en caso de un cambio deberá hacerse previa autorización del Interventor, dando en la solicitud las razones para ello. 4.2. TRABAJOS POR OTROS CONTRATISTAS

El proponente deberá actualizar la información de tamaño de equipos y características eléctricas del diseño original acorde con los equipos finalmente suministrados, e informar de estos cambios a la interventoría para proceder con la coordinación necesaria con las demás especialidades. Los siguientes trabajos no corresponden a la presente especificación y son responsabilidad de las demás especialidades:

Page 16: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 27/02/12

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 16 de 34

16/34

Obras civiles: Las obras civiles de mampostería y/o carpintería en conexión con los sistemas de aire acondicionado necesarios para la correcta instalación de los equipos y accesorios tales como bases, huecos, muros, resanes, etc. Instalaciones eléctricas: Todas las acometidas eléctricas y de control hasta 0 mts de los equipos, tableros y controles según los esquemas unifilares entregados Instalaciones hidráulicas: Acometidas hidráulicas para el servicio de mantenimiento de equipos en cubierta y drenajes de las unidades de enfriamiento. 4.3. REQUISITOS DE LOS MATERIALES Y LA INSTALACIÓN Todos los materiales y equipos deben ser nuevos y producidos por fabricantes reconocidos. El montaje deberá ser realizado utilizando mano de obra calificada para este tipo de montajes. La instalación debe ser hecha de acuerdo a los planos, a las especificaciones, a los requisitos de ASHRAE (American Society of Heating Refrigerating and Air Conditioning Engineers y siguiendo estrictamente los manuales e indicaciones de los fabricantes. El contratista deberá garantizar toda la labor y los materiales suministrados por un periodo de 12 meses después de recibida la obra a satisfacción. 4.4. REQUISITOS DE LOS EQUIPOS Todos los equipos deben cumplir con las especificaciones técnicas anexas. El contratista deberá presentar a la interventoría los Submittals de los equipos ofrecidos para su aprobación, hacen parte de estos Submittals, Muestras físicas, fichas técnicas, certificados y documentos que acrediten el cumplimiento de los requisitos solicitados. Es responsabilidad de la Interventoría la revisión de los Submittals entregados por el contratista y verificar el cumplimiento de los mismos; En caso de presentarse

Page 17: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 27/02/12

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 17 de 34

17/34

diferencias o que el contratista demuestre la imposibilidad de cumplir con lo estipulado se deberá informar al Diseñador para que se modifique o amplíe la información.

Page 18: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 27/02/12

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 18 de 34

18/34

5. CONDICIONES POSTERIORES A LA INSTALACION

5.1. MATENIMIENTO Las labores de mantenimiento se deberán hacer de acuerdo a los manuales de operación y mantenimiento entregados por los fabricantes de los equipos (OBM). Para el control de la legionella en los equipos: Unidades Cassettes, Unidad interna del minisplit y Unidad tipo paquete, se deberá realizar mantenimiento mensual con lavado de la bandeja de condensados y el serpentín de enfriamiento utilizando desinfectantes.

5.2. PRUEBAS Y BALANCEO “PYB” El objetivo del procedimiento de Prueba y Balanceo “PYB”, es asegurar que todo el conjunto quede operando de acuerdo con los requerimientos del pliego de especificaciones técnicas. 5.2.1 Alcance Evaluar cuantitativa y cualitativamente el desempeño de cada uno de los equipos, y sistemas de control en las condiciones de diseño. Balancear los sistemas y equipos para que los caudales se ajusten a los requerimientos. Revisar que todos los elementos de control estén funcionando de acuerdo a los parámetros especificados. 5.2.2 Tolerancias aplicables Las tolerancias de PYB deben hacerse ±10% de los valores del diseño. 5.2.3 Instrumentos Previo al PYB se debe entregar una lista de los instrumentos a usar en el procedimiento con sus números seriales. Los instrumentos deberán estar calibrados con mínimo dos meses de anticipación.

Page 19: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 27/02/12

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 19 de 34

19/34

5.2.4 Ajustes Una vez se termine el procedimiento PYB se debe poner en su sitio los guarda poleas, cerrar todas las puertas de inspección y asegurarse que los sensores queden ajustados en el rango requerido. 5.3. DOCUMENTOS PARA LA ENTREGA FINAL Al final de la obra el contratista entregará los siguientes documentos físicos y en medio magnético (Cuando la información no se encuentre digitalizada el proponente deberá escanearla para su entrega magnética): 5.3.1 Planos record del proyecto Estos deben contener las versiones as build de todos los planos sometidos a aprobación y en formatos autorizados por UNT. (Dos copias físicas en papel bond y una copia en medio magnético en formatos .PDF y .DWG). 5.3.2 Reportes de pruebas, listas de chequeo y reporte de arranque Estos documentos corresponden a los procedimientos de arranque de equipos que solicite el fabricante y/o el proponente considere necesario. 5.3.3 Reporte del PYB final Este documento corresponde a el reporte general durante el procedimiento PYB descrito anteriormente y deberá contener como mínimo lo valores de los parámetros antes y después de efectuada la actividad. 5.3.4 Manuales de operación y mantenimiento O&M Se deberán entregar los manuales de operación y mantenimiento de todos los equipos e instalaciones. 5.3.5 Listado de repuestos recomendados Se deberá entregar un listado debidamente tabulado teniendo en cuenta los repuestos necesarios para las fallas más comunes del sistema.

Page 20: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 27/02/12

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 20 de 34

20/34

5.3.6 Cartas de garantías de todos los equipos instalados Se deberán adjuntar las cartas de garantías emitidas por los fabricantes de los equipos. 5.3.7 Manuales, fichas técnicas, catálogos, etc. Toda la documentación que provenga con el equipo deberá ser entregada como parte del mismo. Se coordinará con UNT la capacitación para el manejo, operación y mantenimiento de todos los sistemas instalados, la capacitación se dictará en los horarios y el personal designado por UNT. Los temas y tiempos de capacitación entregados deben ser avalados por el interventor previo a la capacitación.

Page 21: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 27/02/12

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 21 de 34

21/34

6. MEMORIAS DE CÁLCULO 6.1. CARGAS TÉRMICAS Los cálculos de cargas térmicas se realizaron teniendo en cuenta las condiciones arquitectónicas, ubicación geográfica, y condiciones internas de cada una de las zonas. (Ver Anexos) 6.1.1 Normatividad aplicada EN-15251 2007 REQUISITOS ENVIADOS DEL PROCESO 6.1.2 Software utilizado Referencia: ELITE Software CHVAC Comercial HVAC Loads. Versión: 8.02.15: 50 Zone Versión Software Avalado por US Green Building Council para cumplir con las directivas de LEED (Leadership in Energy and Environmental Design) 6.1.3 Metodología y Detalles del cálculo Método de cálculo: CLTD (Cooling Load Temperature Diference) Parámetros utilizados: (Ver Anexo)

Page 22: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 27/02/12

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 22 de 34

22/34

6.2. ELEMENTOS FINITOS El modelamiento por elementos finitos, permite visualizar el comportamiento de los flujos de aire, para evaluar la velocidad en las áreas de trabajo con unidades de aire acondicionado y que cumplan con los requerimientos de la norma. (Ver Anexos) 6.2.1 Normatividad aplicada EN-15251 6.2.2 Software utilizado Referencia: INTEGRATED ENVIRONMENTAL SOLUTION Versión: 6.4.10.10 6.2.3 Metodología y Detalles del cálculo Método de cálculo: CFD Parámetros utilizados: Velocidad de descarga de rejillas y equipos según

fichas técnicas de los mismos (Ver Anexo) 6.3. EXTRACCIONES MECÁNICAS Los cálculos de Extracciones Mecánicas se realizaron teniendo en cuenta los parámetros exigidos por la normatividad Internacional aplicada. (Ver Anexos) 6.3.1 Normatividad aplicada

- ASHRAE ESTÁNDAR 62.1 6.3.2 Software utilizado Referencia: Aplicación Excel 6.3.3 Metodología y Detalles del cálculo Método de cálculo: C/H (Cambios Hora) Parámetros utilizados: (Ver Anexo)

Page 23: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 27/02/12

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 23 de 34

23/34

6.4. VENTILACIONES MECÁNICAS Los cálculos de Ventilaciones Mecánicas se realizaron teniendo en cuenta los parámetros exigidos por la normatividad Internacional aplicada. (Ver Anexos) 6.4.1 Normatividad aplicada EN-15251 2007 6.4.2 Software utilizado Referencia: Aplicación Excel 6.4.3 Metodología y Detalles del cálculo Método de cálculo: C/H (Cambios Hora) Parámetros utilizados: (Ver Anexo) 6.5. CALCULO DUCTOS Se determinan las dimensiones de los ductos buscando las mejores dimensiones para los conductos. (Ver Anexos) 6.5.1 Normatividad Aplicada SMACNA 6.5.2 Software utilizado. Referencia: REVIT MEP Versión: 2015 6.5.3 Metodología y Detalles del cálculo. Método de cálculo: EQUAL FRICTION RATE, AUTO-BALANCE SYSTEM Parámetros Utilizados: (Ver Anexo)

Page 24: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 27/02/12

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 24 de 34

24/34

6.6. SELECCIÓN TUBERÍAS DE REFRIGERACIÓN Se seleccionan las tuberías de refrigeración, teniendo en cuenta el Refrigerante, la capacidad del equipo, las distancias de tuberías y los accesorios utilizados. (Ver Anexos) 6.6.1 Normatividad Aplicada 6.6.2 Software utilizado. Referencia: ENGINEERING TOOLBOX REFRIGERANT LINE SIZING Versión: 6.6.3 Metodología y Detalles del cálculo. Método de cálculo: Parámetros Utilizados: (Ver Anexo) 6.7. SISTEMA ELÉCTRICO Se determinan los consumos, ubicación en tableros eléctricos y protecciones de los diferentes equipos. (Ver Anexos) 6.7.1 Normatividad Aplicada 6.7.2 Software utilizado. Referencia: | Aplicación Excel 6.7.3 Metodología y Detalles del cálculo. Método de cálculo: Parámetros Utilizados: (Ver Anexo)

Page 25: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 27/02/12

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 25 de 34

25/34

6.8. SISTEMA DE CONTROL Se determinan los puntos de control, Algoritmos, listado de sensores y actuadores. (Ver Anexos) 6.8.1 Normatividad Aplicada 6.8.2 Software utilizado. Referencia: Aplicación Excel y Visio 6.8.3 Metodología y Detalles del cálculo. Método de cálculo: Parámetros Utilizados: (Ver Anexo)

Page 26: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 27/02/12

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 26 de 34

26/34

7. ANEXOS 7.1. CÁLCULOS Se incluyen dentro de los Anexos los resultados del software de diseño y demás información utilizada para el desarrollo de los cálculos. 7.2. SELECCIÓN DE EQUIPOS Se incluyen las selecciones de equipos mediante los Data Sheet del equipo seleccionado como base de diseño y que cumple estrictamente los parámetros de diseño. La marca y modelo de estos equipos, son únicamente una referencia de selección y no constituye obligación alguna para el proponente.

Page 27: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 27/02/12

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 27 de 34

27/34

7.2.1 Anexo MEMORIA DE CALCULO DE CARGAS TERMICAS

Page 28: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

Universidad Nacional TumacoHVAC Load Analysis

for

Universidad Nacional

Prepared By:

Ing Diego Gonzalo CastroAireg SAS

Transversal 60 # 115-58 Torre A Of 512Bogota

6247463miércoles, 14 de septiembre de 2016

Page 29: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.Aireg SAS Universidad Nacional TumacoBogota, Colombia, 11001000 Page 2

General Project Data Input

General Project InformationProject file name: AG-SC 001 P 16-71 C TERMICAS.CH8Project title: Universidad Nacional TumacoProject city, state, ZIP: TumacoDesigned by: Ing Diego Gonzalo Castro GProject date: viernes, 29 de julio de 2016Weather reference city: TUMACO, COLOMBIAClient name: Universidad NacionalCompany name: Aireg SASCompany representative: Ing Diego Gonzalo CastroCompany address: Transversal 60 # 115-58 Torre A Of 512 Company city: BogotaCompany phone: 6247463Company e-mail address: [email protected] website: www.airegsas.com

Barometric pressure: 29.913 in.Hg.Altitude: 7 feetLatitude: 1 DegreesMean daily temperature range: 10 DegreesStarting & ending time for HVAC load calculations: 1am - 12amNumber of unique rooms in this project: 22

Building Default ValuesCalculations performed: Both heating and cooling loadsLighting requirements: 1.10 Watts per square footEquipment requirements: 1.00 Watts per square footPeople sensible load multiplier: 250 Btuh per personPeople latent load multiplier: 200 Btuh per personRoom sensible safety factor: 0 %Room latent safety factor: 0 %Room heating safety factor: 0 %People diversity factor: 100 %Lighting profile number: 0Equipment profile number: 0People profile number: 0Building default ceiling height: 11.50 feetBuilding default wall height: 11.50 feet

Internal Operating Load Profiles (C = 100)hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 C C C C C C C C C C C C C C C C C C C C C C C C2 C C C C C C C C C C C C C C C C C C C C C C C C3 C C C C C C C C C C C C C C C C C C C C C C C C4 C C C C C C C C C C C C C C C C C C C C C C C C5 C C C C C C C C C C C C C C C C C C C C C C C C6 C C C C C C C C C C C C C C C C C C C C C C C C7 C C C C C C C C C C C C C C C C C C C C C C C C8 C C C C C C C C C C C C C C C C C C C C C C C C9 C C C C C C C C C C C C C C C C C C C C C C C C

10 C C C C C C C C C C C C C C C C C C C C C C C C

C:\ ...\AG-SC 001 P 16-71 C TERMICAS.CH8 miércoles, 14 de septiembre de 2016, 02:31 p. m.

Page 30: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.Aireg SAS Universidad Nacional TumacoBogota, Colombia, 11001000 Page 3

General Project Data Input (cont'd)

Building-Level Design Conditions DesignMonth

OutdoorDry Bulb

OutdoorWet Bulb

IndoorRel.Hum

IndoorDry Bulb

GrainsDiff

In/OutdoorCorrection

August 85 82 50% 79 88.11 -6Winter 0 0

Master RoofsRoofNo.

ASHRAERoof#

RoofU-Fac

DarkColor

Susp.Ceil

1 4 0.230 No NoRoof #1 Description: Flat roof, 6" heavy weight concrete deck with no insulation, suspended ceiling below with no insulation2 3 0.213 No No

Master WallsWallNo.

ASHRAEGroup

WallU-Fac

WallColor

1 C 0.250 MWall #1 Description: Block wall, 8" sand & gravel, hollow core, siding exterior, no insulation or finish

Master PartitionsPartitionNo.

PartitionU-Factor

CoolT-D

HeatT-D

1 0.469 9 9Partition #1 Description: Brick partition, 8" thick, face & common, no insulation or finish2 0.910 9 9

Master GlassGlassNo.

SummerU-Factor

WinterU-Factor

GlassShd.Coef.

InteriorShading

InteriorShd.Coef

1 0.620 0.620 0.460 2 0.000

Master Shading Devices

ShadeNo.

DistHoriz

OverhProjects

DistBeyond

RightW.Edge

DistBeyond

LeftW.Edge

DistOverhAboveWind

DistRight

FinProj

DistR-Fin

BeyondW.Edge

HtOf

RightFin

DistLeftFin

Proj

DistL-Fin

BeyondW.Edge

HtOf

LeftFin

1 6.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.002 7.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.003 5.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.004 5.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

C:\ ...\AG-SC 001 P 16-71 C TERMICAS.CH8 miércoles, 14 de septiembre de 2016, 02:31 p. m.

Page 31: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.Aireg SAS Universidad Nacional TumacoBogota, Colombia, 11001000 Page 4

Building Envelope Report

Envelope Report Using Summer U-Factors

MaterialTypes

GrossArea

GlassArea

NetArea

-U-Factor

Area xU-Factor

AverageU-Factor

Roof 1 12,739.1 0.0 12,739.1 0.230 2,931.268 0.230Tot.Roof 12,739.1 0.0 12,739.1 N/A 2,931.268 0.230

Wall 1 6,491.6 4,569.3 1,922.3 0.250 480.563 0.250Tot.Wall 6,491.6 4,569.3 1,922.3 N/A 480.563 0.250

Glass 1 5,549.3 N/A 5,549.3 0.620 3,440.566 0.620Tot.Glass 5,549.3 N/A 5,549.3 N/A 3,440.566 0.620

Totals 20,210.7 6,852.396 0.339

WallDirection

WallArea

GlassArea

Wall NetArea

Wall AvgU-Factor

Glass AvgU-Factor

Glass AvgShd.Coef

N 5,427.7 4,249.3 1,178.4 0.250 0.620 0.460NE 0.0 0.0 0.0 0.000 0.000 0.000E 341.9 320.0 21.9 0.250 0.620 0.460SE 0.0 0.0 0.0 0.000 0.000 0.000S 722.0 0.0 722.0 0.250 0.000 0.000SW 0.0 0.0 0.0 0.000 0.000 0.000W 0.0 0.0 0.0 0.000 0.000 0.000NW 0.0 0.0 0.0 0.000 0.000 0.000

Totals 6,491.6 4,569.3 1,922.3 0.250 0.620 0.460

C:\ ...\AG-SC 001 P 16-71 C TERMICAS.CH8 miércoles, 14 de septiembre de 2016, 02:31 p. m.

Page 32: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.Aireg SAS Universidad Nacional TumacoBogota, Colombia, 11001000 Page 5

Air Handler #1 - Ucrv-01 - Summary Loads

RmNo

DescriptionRoom Peak Time

AreaPeople

Volume

Htg.LossHtg.CFMCFM/Sqft

Sen.GainClg.CFM

CFM/Sqft

Lat.GainS.Exh

W.Exh

Htg.O.A.Req.CFMAct.CFM

Clg.O.A.Req.CFMAct.CFM

1Z-01 P1 A1 Biblioteca6pm August

2,33338

23,329

5,468559

0.24

58,6932,593

1.11

7,60000

14.83/P,0.06/ft²

704559

14.83/P,0.06/ft²

704545

2Z-01 P2 A1 Laboratorios6pm August

85318

8,526

3,225330

0.39

36,4621,611

1.89

3,60000

14.83/P,0.06/ft²

318330

14.83/P,0.06/ft²

318338

The above Room occurs 4 times throughout this air system.

3Z-02 P2 A1 Ups5pm August

1241

1,430

1,223125

1.01

11,202495

3.98

24900

14.83/P,0.06/ft²

26125

14.83/P,0.06/ft²

26104

Room Peak Totals:Total Rooms: 6Unique Rooms: 3

5,868111

58,864

19,5902,002

0.34

215,7459,532

1.62

22,24900

2,0022,002

2,0022,002

C:\ ...\AG-SC 001 P 16-71 C TERMICAS.CH8 miércoles, 14 de septiembre de 2016, 02:31 p. m.

Page 33: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.Aireg SAS Universidad Nacional TumacoBogota, Colombia, 11001000 Page 6

Air Handler #1 - Ucrv-01 - Total Load Summary Air Handler Description: Ucrv-01 Variable Air VolumeSupply Air Fan: Draw-Thru with program estimated horsepower of 0.90 HPFan Input: 0% motor and fan efficiency with 0 in. water across the fanSensible Heat Ratio: 0.91 --- This system occurs 1 time(s) in the building. ---

Air System Peak Time: 5pm in August. Outdoor Conditions: Clg: 84° DB, 82° WB, 163.26 grains, Htg: 0° DBIndoor Conditions: Clg: 79° DB, 50% RH, Htg: 0° DB

Because of the diversity in room, plenum and ventilation loads, the room sensible peak time in August at 6pm is different from the total system peak time, hence the air system CFM was computed using a room sensible load of 215,703.

Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.

Room Space sensible loss: 19,590 BtuhInfiltration sensible loss: 0 Btuh 0 CFMOutside Air sensible loss: 0 Btuh 2,002 CFMSupply Duct sensible loss: 0 BtuhReturn Duct sensible loss: 0 BtuhReturn Plenum sensible loss: 0 BtuhTotal System sensible loss: 19,590 Btuh

Heating Supply Air: 19,590 / (1.000 X 1.08 X 9) = 2,002 CFMWinter Vent Outside Air (100.0% of supply) = 2,002 CFM

Room space sensible gain: 209,426 BtuhInfiltration sensible gain: 0 BtuhDraw-thru fan sensible gain: 2,283 BtuhSupply duct sensible gain: 0 BtuhReserve sensible gain: 0 BtuhTotal sensible gain on supply side of coil: 211,708 Btuh

Cooling Supply Air: 217,986 / (1.000 X 1.1 X 21) = 9,530 CFMSummer Vent Outside Air (21.0% of supply) = 2,002 CFM

Return duct sensible gain: 0 BtuhReturn plenum sensible gain: 0 BtuhOutside air sensible gain: -1,761 Btuh 2,002 CFMBlow-thru fan sensible gain: 0 BtuhTotal sensible gain on return side of coil: -1,761 BtuhTotal sensible gain on air handling system: 209,947 Btuh

Room space latent gain: 22,249 BtuhInfiltration latent gain: 0 BtuhOutside air latent gain: 71,944 BtuhTotal latent gain on air handling system: 94,193 BtuhTotal system sensible and latent gain: 304,140 BtuhPretreated air sensible gain: 13,209 BtuhPretreated air latent gain: 50,236 Btuh

Check FiguresTotal Air Handler Supply Air (based on a 21° TD): 9,530 CFMTotal Air Handler Vent. Air (21.01% of Supply): 2,002 CFM

Total Conditioned Air Space: 5,868 Sq.ftSupply Air Per Unit Area: 1.6241 CFM/Sq.ftArea Per Cooling Capacity: 231.5 Sq.ft/TonCooling Capacity Per Area: 0.0043 Tons/Sq.ftHeating Capacity Per Area: 3.34 Btuh/Sq.ft

Total Heating Required With Outside Air: 19,590 BtuhTotal Cooling Required With Outside Air: 25.35 Tons

C:\ ...\AG-SC 001 P 16-71 C TERMICAS.CH8 miércoles, 14 de septiembre de 2016, 02:31 p. m.

Page 34: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.Aireg SAS Universidad Nacional TumacoBogota, Colombia, 11001000 Page 7

Air Handler #2 - Ucrv-02 - Summary Loads

RmNo

DescriptionRoom Peak Time

AreaPeople

Volume

Htg.LossHtg.CFMCFM/Sqft

Sen.GainClg.CFM

CFM/Sqft

Lat.GainS.Exh

W.Exh

Htg.O.A.Req.CFMAct.CFM

Clg.O.A.Req.CFMAct.CFM

4Z-01 P1 B1 Oficina Del Chef12am August

551

630

1,823415

7.58

3,302127

2.33

20000

14.83/P,0.06/ft²

18415

14.83/P,0.06/ft²

1864

5Z-01 P2 B1 Classroom6pm August

71841

8,260

2,260515

0.72

31,5971,218

1.70

8,20000

14.83/P,0.06/ft²

651515

14.83/P,0.06/ft²

651615

The above Room occurs 3 times throughout this air system.

6Z-02 P2 B1 Classroom3pm August

71831

8,260

2,260515

0.72

29,4901,137

1.58

6,20000

14.83/P,0.06/ft²

503515

14.83/P,0.06/ft²

503574

Room Peak Totals:Total Rooms: 5Unique Rooms: 3

2,928155

33,669

10,8652,474

0.85

127,5834,920

1.68

31,00000

2,4742,474

2,4742,482

C:\ ...\AG-SC 001 P 16-71 C TERMICAS.CH8 miércoles, 14 de septiembre de 2016, 02:31 p. m.

Page 35: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.Aireg SAS Universidad Nacional TumacoBogota, Colombia, 11001000 Page 8

Air Handler #2 - Ucrv-02 - Total Load Summary Air Handler Description: Ucrv-02 Variable Air VolumeSupply Air Fan: Draw-Thru with program estimated horsepower of 0.46 HPFan Input: 0% motor and fan efficiency with 0 in. water across the fanSensible Heat Ratio: 0.80 --- This system occurs 1 time(s) in the building. ---

Air System Peak Time: 5pm in August. Outdoor Conditions: Clg: 84° DB, 82° WB, 163.26 grains, Htg: 0° DBIndoor Conditions: Clg: 79° DB, 50% RH, Htg: 0° DB

Because of the diversity in room, plenum and ventilation loads, the room sensible peak time in August at 6pm is different from the total system peak time, hence the air system CFM was computed using a room sensible load of 127,190.

Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.

Room Space sensible loss: 10,865 BtuhInfiltration sensible loss: 0 Btuh 0 CFMOutside Air sensible loss: 0 Btuh 2,474 CFMSupply Duct sensible loss: 0 BtuhReturn Duct sensible loss: 0 BtuhReturn Plenum sensible loss: 0 BtuhTotal System sensible loss: 10,865 Btuh

Heating Supply Air: 10,865 / (1.000 X 1.08 X 4) = 2,474 CFMWinter Vent Outside Air (100.0% of supply) = 2,474 CFM

Room space sensible gain: 125,012 BtuhInfiltration sensible gain: 0 BtuhDraw-thru fan sensible gain: 1,175 BtuhSupply duct sensible gain: 0 BtuhReserve sensible gain: 0 BtuhTotal sensible gain on supply side of coil: 126,187 Btuh

Cooling Supply Air: 128,365 / (1.000 X 1.1 X 24) = 4,904 CFMSummer Vent Outside Air (50.5% of supply) = 2,474 CFM

Return duct sensible gain: 0 BtuhReturn plenum sensible gain: 0 BtuhOutside air sensible gain: -2,177 Btuh 2,474 CFMBlow-thru fan sensible gain: 0 BtuhTotal sensible gain on return side of coil: -2,177 BtuhTotal sensible gain on air handling system: 124,010 Btuh

Room space latent gain: 31,000 BtuhInfiltration latent gain: 0 BtuhOutside air latent gain: 88,926 BtuhTotal latent gain on air handling system: 119,926 BtuhTotal system sensible and latent gain: 243,936 BtuhPretreated air sensible gain: 16,326 BtuhPretreated air latent gain: 62,094 Btuh

Check FiguresTotal Air Handler Supply Air (based on a 24° TD): 4,904 CFMTotal Air Handler Vent. Air (50.45% of Supply): 2,474 CFM

Total Conditioned Air Space: 2,928 Sq.ftSupply Air Per Unit Area: 1.6752 CFM/Sq.ftArea Per Cooling Capacity: 144.0 Sq.ft/TonCooling Capacity Per Area: 0.0069 Tons/Sq.ftHeating Capacity Per Area: 3.71 Btuh/Sq.ft

Total Heating Required With Outside Air: 10,865 BtuhTotal Cooling Required With Outside Air: 20.33 Tons

C:\ ...\AG-SC 001 P 16-71 C TERMICAS.CH8 miércoles, 14 de septiembre de 2016, 02:31 p. m.

Page 36: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.Aireg SAS Universidad Nacional TumacoBogota, Colombia, 11001000 Page 9

Air Handler #3 - Ucrv-03 - Summary Loads

RmNo

DescriptionRoom Peak Time

AreaPeople

Volume

Htg.LossHtg.CFMCFM/Sqft

Sen.GainClg.CFM

CFM/Sqft

Lat.GainS.Exh

W.Exh

Htg.O.A.Req.CFMAct.CFM

Clg.O.A.Req.CFMAct.CFM

7Z-03 P2 B1 Rack5pm August

350

400

51049

1.42

2,12489

2.57

7000

14.83/P,0.06/ft²

749

14.83/P,0.06/ft²

722

8Z-04 P2 B1 Ups5pm August

641

736

97194

1.47

9,947419

6.55

12800

14.83/P,0.06/ft²

1394

14.83/P,0.06/ft²

13104

9Z-05 P2 B1 Autonomos Work Area6pm August

77331

8,888

4,911477

0.62

46,5421,961

2.54

6,20000

14.83/P,0.06/ft²

506477

14.83/P,0.06/ft²

506488

10Z-06 P2 B1 Professor Room6pm August

673

773

31631

0.46

5,598236

3.51

60000

14.83/P,0.06/ft²

4931

14.83/P,0.06/ft²

4959

The above Room occurs 2 times throughout this air system.

11Z-07 P2 B1 Professor Room5pm August

673

773

31631

0.46

2,748116

1.72

60000

14.83/P,0.06/ft²

4931

14.83/P,0.06/ft²

4929

The above Room occurs 3 times throughout this air system.

12Z-08 P2 B1 Sala De Juntas12am August

1216

1,392

95192

0.76

4,611194

1.61

1,20000

14.83/P,0.06/ft²

9692

14.83/P,0.06/ft²

9648

Room Peak Totals:Total Rooms: 9Unique Rooms: 6

1,32953

15,282

8,920866

0.65

82,6643,483

2.62

10,59800

866866

866867

C:\ ...\AG-SC 001 P 16-71 C TERMICAS.CH8 miércoles, 14 de septiembre de 2016, 02:31 p. m.

Page 37: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.Aireg SAS Universidad Nacional TumacoBogota, Colombia, 11001000 Page 10

Air Handler #3 - Ucrv-03 - Total Load Summary Air Handler Description: Ucrv-03 Variable Air VolumeSupply Air Fan: Draw-Thru with program estimated horsepower of 0.33 HPFan Input: 0% motor and fan efficiency with 0 in. water across the fanSensible Heat Ratio: 0.89 --- This system occurs 1 time(s) in the building. ---

Air System Peak Time: 5pm in August. Outdoor Conditions: Clg: 84° DB, 82° WB, 163.26 grains, Htg: 0° DBIndoor Conditions: Clg: 79° DB, 50% RH, Htg: 0° DB

Because of the diversity in room, plenum and ventilation loads, the room sensible peak time in August at 6pm is different from the total system peak time, hence the air system CFM was computed using a room sensible load of 82,541.

Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.

Room Space sensible loss: 8,920 BtuhInfiltration sensible loss: 0 Btuh 0 CFMOutside Air sensible loss: 0 Btuh 866 CFMSupply Duct sensible loss: 0 BtuhReturn Duct sensible loss: 0 BtuhReturn Plenum sensible loss: 0 BtuhTotal System sensible loss: 8,920 Btuh

Heating Supply Air: 8,920 / (1.000 X 1.08 X 10) = 866 CFMWinter Vent Outside Air (100.0% of supply) = 866 CFM

Room space sensible gain: 80,570 BtuhInfiltration sensible gain: 0 BtuhDraw-thru fan sensible gain: 833 BtuhSupply duct sensible gain: 0 BtuhReserve sensible gain: 0 BtuhTotal sensible gain on supply side of coil: 81,403 Btuh

Cooling Supply Air: 83,374 / (1.000 X 1.1 X 22) = 3,478 CFMSummer Vent Outside Air (24.9% of supply) = 866 CFM

Return duct sensible gain: 0 BtuhReturn plenum sensible gain: 0 BtuhOutside air sensible gain: -761 Btuh 866 CFMBlow-thru fan sensible gain: 0 BtuhTotal sensible gain on return side of coil: -761 BtuhTotal sensible gain on air handling system: 80,641 Btuh

Room space latent gain: 10,598 BtuhInfiltration latent gain: 0 BtuhOutside air latent gain: 27,530 BtuhTotal latent gain on air handling system: 38,127 BtuhTotal system sensible and latent gain: 118,769 BtuhPretreated air sensible gain: 5,711 BtuhPretreated air latent gain: 25,299 Btuh

Check FiguresTotal Air Handler Supply Air (based on a 22° TD): 3,478 CFMTotal Air Handler Vent. Air (24.89% of Supply): 866 CFM

Total Conditioned Air Space: 1,329 Sq.ftSupply Air Per Unit Area: 2.6170 CFM/Sq.ftArea Per Cooling Capacity: 134.3 Sq.ft/TonCooling Capacity Per Area: 0.0074 Tons/Sq.ftHeating Capacity Per Area: 6.71 Btuh/Sq.ft

Total Heating Required With Outside Air: 8,920 BtuhTotal Cooling Required With Outside Air: 9.90 Tons

C:\ ...\AG-SC 001 P 16-71 C TERMICAS.CH8 miércoles, 14 de septiembre de 2016, 02:31 p. m.

Page 38: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.Aireg SAS Universidad Nacional TumacoBogota, Colombia, 11001000 Page 11

Air Handler #4 - Ucrv-04 - Summary Loads

RmNo

DescriptionRoom Peak Time

AreaPeople

Volume

Htg.LossHtg.CFMCFM/Sqft

Sen.GainClg.CFM

CFM/Sqft

Lat.GainS.Exh

W.Exh

Htg.O.A.Req.CFMAct.CFM

Clg.O.A.Req.CFMAct.CFM

13Z-01 P2 C1 Control Center6pm August

2563

2,944

1,553112

0.44

11,286499

1.95

60000

14.83/P,0.06/ft²

60112

14.83/P,0.06/ft²

6095

14Z-02 P2 C1 Rack6pm August

761

870

00

0.00

5,994265

3.50

15100

14.83/P,0.06/ft²

160

14.83/P,0.06/ft²

1651

15Z-03 P2 C1 Ice Room5pm August

1661

1,914

57341

0.25

3,477154

0.92

20000

14.83/P,0.06/ft²

2541

14.83/P,0.06/ft²

2529

16Z-04 P2 C1 Autonomos Work Area6pm August

77331

8,888

4,883353

0.46

46,5132,055

2.66

6,20000

14.83/P,0.06/ft²

506353

14.83/P,0.06/ft²

506393

17Z-05 P2 C1 Ici Room6pm August

49321

5,668

4,314311

0.63

34,8141,538

3.12

4,20000

14.83/P,0.06/ft²

341311

14.83/P,0.06/ft²

341294

18Z-06 P2 C1 Ups5pm August

641

736

1,456105

1.64

10,432461

7.20

12800

14.83/P,0.06/ft²

13105

14.83/P,0.06/ft²

1388

19Z-07 P2 C1 Rack5pm August

350

400

63146

1.31

2,24899

2.85

7000

14.83/P,0.06/ft²

746

14.83/P,0.06/ft²

719

Room Peak Totals:Total Rooms: 7Unique Rooms: 7

1,86358

21,420

13,410968

0.52

114,7655,070

2.72

11,54900

968968

968969

C:\ ...\AG-SC 001 P 16-71 C TERMICAS.CH8 miércoles, 14 de septiembre de 2016, 02:31 p. m.

Page 39: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.Aireg SAS Universidad Nacional TumacoBogota, Colombia, 11001000 Page 12

Air Handler #4 - Ucrv-04 - Total Load Summary Air Handler Description: Ucrv-04 Variable Air VolumeSupply Air Fan: Draw-Thru with program estimated horsepower of 0.48 HPFan Input: 0% motor and fan efficiency with 0 in. water across the fanSensible Heat Ratio: 0.91 --- This system occurs 1 time(s) in the building. ---

Air System Peak Time: 5pm in August. Outdoor Conditions: Clg: 84° DB, 82° WB, 163.26 grains, Htg: 0° DBIndoor Conditions: Clg: 79° DB, 50% RH, Htg: 0° DB

Because of the diversity in room, plenum and ventilation loads, the room sensible peak time in August at 6pm is different from the total system peak time, hence the air system CFM was computed using a room sensible load of 114,658.

Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.

Room Space sensible loss: 13,410 BtuhInfiltration sensible loss: 0 Btuh 0 CFMOutside Air sensible loss: 0 Btuh 968 CFMSupply Duct sensible loss: 0 BtuhReturn Duct sensible loss: 0 BtuhReturn Plenum sensible loss: 0 BtuhTotal System sensible loss: 13,410 Btuh

Heating Supply Air: 13,410 / (1.000 X 1.08 X 13) = 968 CFMWinter Vent Outside Air (100.0% of supply) = 968 CFM

Room space sensible gain: 112,117 BtuhInfiltration sensible gain: 0 BtuhDraw-thru fan sensible gain: 1,213 BtuhSupply duct sensible gain: 0 BtuhReserve sensible gain: 0 BtuhTotal sensible gain on supply side of coil: 113,330 Btuh

Cooling Supply Air: 115,871 / (1.000 X 1.1 X 21) = 5,066 CFMSummer Vent Outside Air (19.1% of supply) = 968 CFM

Return duct sensible gain: 0 BtuhReturn plenum sensible gain: 0 BtuhOutside air sensible gain: -852 Btuh 968 CFMBlow-thru fan sensible gain: 0 BtuhTotal sensible gain on return side of coil: -852 BtuhTotal sensible gain on air handling system: 112,479 Btuh

Room space latent gain: 11,549 BtuhInfiltration latent gain: 0 BtuhOutside air latent gain: 30,792 BtuhTotal latent gain on air handling system: 42,341 BtuhTotal system sensible and latent gain: 154,820 BtuhPretreated air sensible gain: 6,388 BtuhPretreated air latent gain: 28,297 Btuh

Check FiguresTotal Air Handler Supply Air (based on a 21° TD): 5,066 CFMTotal Air Handler Vent. Air (19.11% of Supply): 968 CFM

Total Conditioned Air Space: 1,863 Sq.ftSupply Air Per Unit Area: 2.7196 CFM/Sq.ftArea Per Cooling Capacity: 144.4 Sq.ft/TonCooling Capacity Per Area: 0.0069 Tons/Sq.ftHeating Capacity Per Area: 7.20 Btuh/Sq.ft

Total Heating Required With Outside Air: 13,410 BtuhTotal Cooling Required With Outside Air: 12.90 Tons

C:\ ...\AG-SC 001 P 16-71 C TERMICAS.CH8 miércoles, 14 de septiembre de 2016, 02:31 p. m.

Page 40: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.Aireg SAS Universidad Nacional TumacoBogota, Colombia, 11001000 Page 13

Air Handler #5 - Ucrv-05 - Summary Loads

RmNo

DescriptionRoom Peak Time

AreaPeople

Volume

Htg.LossHtg.CFMCFM/Sqft

Sen.GainClg.CFM

CFM/Sqft

Lat.GainS.Exh

W.Exh

Htg.O.A.Req.CFMAct.CFM

Clg.O.A.Req.CFMAct.CFM

21Z-02 P2 D1 Rack5pm August

450

516

1,84542

0.93

3,420151

3.37

9000

14.83/P,0.06/ft²

942

14.83/P,0.06/ft²

922

22Z-03 P2 D1 Control5pm August

462

532

00

0.00

3,000133

2.87

40000

14.83/P,0.06/ft²

320

14.83/P,0.06/ft²

3220

Room Peak Totals:Total Rooms: 2Unique Rooms: 2

912

1,048

1,84542

0.46

6,420284

3.11

49000

4242

4242

C:\ ...\AG-SC 001 P 16-71 C TERMICAS.CH8 miércoles, 14 de septiembre de 2016, 02:31 p. m.

Page 41: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.Aireg SAS Universidad Nacional TumacoBogota, Colombia, 11001000 Page 14

Air Handler #5 - Ucrv-05 - Total Load Summary Air Handler Description: Ucrv-05 Variable Air VolumeSupply Air Fan: Draw-Thru with program estimated horsepower of 0.03 HPFan Input: 0% motor and fan efficiency with 0 in. water across the fanSensible Heat Ratio: 0.93 --- This system occurs 1 time(s) in the building. ---

Air System Peak Time: 5pm in August. Outdoor Conditions: Clg: 84° DB, 82° WB, 163.26 grains, Htg: 0° DBIndoor Conditions: Clg: 79° DB, 50% RH, Htg: 0° DB

Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.

Room Space sensible loss: 1,845 BtuhInfiltration sensible loss: 0 Btuh 0 CFMOutside Air sensible loss: 0 Btuh 42 CFMSupply Duct sensible loss: 0 BtuhReturn Duct sensible loss: 0 BtuhReturn Plenum sensible loss: 0 BtuhTotal System sensible loss: 1,845 Btuh

Heating Supply Air: 1,845 / (1.000 X 1.08 X 41) = 42 CFMWinter Vent Outside Air (100.0% of supply) = 42 CFM

Room space sensible gain: 6,420 BtuhInfiltration sensible gain: 0 BtuhDraw-thru fan sensible gain: 68 BtuhSupply duct sensible gain: 0 BtuhReserve sensible gain: 0 BtuhTotal sensible gain on supply side of coil: 6,488 Btuh

Cooling Supply Air: 6,488 / (1.000 X 1.1 X 21) = 284 CFMSummer Vent Outside Air (14.7% of supply) = 42 CFM

Return duct sensible gain: 0 BtuhReturn plenum sensible gain: 0 BtuhOutside air sensible gain: 239 Btuh 42 CFMBlow-thru fan sensible gain: 0 BtuhTotal sensible gain on return side of coil: 239 BtuhTotal sensible gain on air handling system: 6,727 Btuh

Room space latent gain: 490 BtuhInfiltration latent gain: 0 BtuhOutside air latent gain: 2,536 BtuhTotal latent gain on air handling system: 3,026 BtuhTotal system sensible and latent gain: 9,754 Btuh

Check FiguresTotal Air Handler Supply Air (based on a 21° TD): 284 CFMTotal Air Handler Vent. Air (14.73% of Supply): 42 CFM

Total Conditioned Air Space: 91 Sq.ftSupply Air Per Unit Area: 3.1123 CFM/Sq.ftArea Per Cooling Capacity: 112.1 Sq.ft/TonCooling Capacity Per Area: 0.0089 Tons/Sq.ftHeating Capacity Per Area: 20.24 Btuh/Sq.ft

Total Heating Required With Outside Air: 1,845 BtuhTotal Cooling Required With Outside Air: 0.81 Tons

C:\ ...\AG-SC 001 P 16-71 C TERMICAS.CH8 miércoles, 14 de septiembre de 2016, 02:31 p. m.

Page 42: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.Aireg SAS Universidad Nacional TumacoBogota, Colombia, 11001000 Page 15

Air Handler #6 - Upa-01 - Summary Loads

RmNo

DescriptionRoom Peak Time

AreaPeople

Volume

Htg.LossHtg.CFMCFM/Sqft

Sen.GainClg.CFM

CFM/Sqft

Lat.GainS.Exh

W.Exh

Htg.O.A.Req.CFMAct.CFM

Clg.O.A.Req.CFMAct.CFM

20 Z-01 P2 D1 Auditorio5pm August

3,170240

42,791

6,5051,200

0.38

109,3214,215

1.33

54,10300

5/P1,2001,200

5/P1,2001,200

Room Peak Totals:Total Rooms: 1Unique Rooms: 1

3,170240

42,791

6,5051,200

0.38

109,3214,215

1.33

54,10300

1,2001,200

1,2001,200

C:\ ...\AG-SC 001 P 16-71 C TERMICAS.CH8 miércoles, 14 de septiembre de 2016, 02:31 p. m.

Page 43: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.Aireg SAS Universidad Nacional TumacoBogota, Colombia, 11001000 Page 16

Air Handler #6 - Upa-01 - Total Load Summary Air Handler Description: Upa-01 Variable Air VolumeSupply Air Fan: Draw-Thru with program estimated horsepower of 0.40 HPFan Input: 0% motor and fan efficiency with 0 in. water across the fanSensible Heat Ratio: 0.67 --- This system occurs 1 time(s) in the building. ---

Air System Peak Time: 5pm in August. Outdoor Conditions: Clg: 84° DB, 82° WB, 163.26 grains, Htg: 0° DBIndoor Conditions: Clg: 79° DB, 50% RH, Htg: 0° DB

Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.

Room Space sensible loss: 6,505 BtuhInfiltration sensible loss: 0 Btuh 100 CFMOutside Air sensible loss: 0 Btuh 1,200 CFMSupply Duct sensible loss: 0 BtuhReturn Duct sensible loss: 0 BtuhReturn Plenum sensible loss: 0 BtuhTotal System sensible loss: 6,505 Btuh

Heating Supply Air: 6,505 / (1.000 X 1.08 X 5) = 1,200 CFMWinter Vent Outside Air (100.0% of supply) = 1,200 CFM

Room space sensible gain: 108,749 BtuhInfiltration sensible gain: 572 BtuhDraw-thru fan sensible gain: 1,010 BtuhSupply duct sensible gain: 0 BtuhReserve sensible gain: 0 BtuhTotal sensible gain on supply side of coil: 110,331 Btuh

Cooling Supply Air: 110,331 / (1.000 X 1.1 X 24) = 4,215 CFMSummer Vent Outside Air (28.5% of supply) = 1,200 CFM

Return duct sensible gain: 0 BtuhReturn plenum sensible gain: 0 BtuhOutside air sensible gain: -1,056 Btuh 1,200 CFMBlow-thru fan sensible gain: 0 BtuhTotal sensible gain on return side of coil: -1,056 BtuhTotal sensible gain on air handling system: 109,275 Btuh

Room space latent gain: 48,000 BtuhInfiltration latent gain: 6,103 BtuhOutside air latent gain: 43,128 BtuhTotal latent gain on air handling system: 97,231 BtuhTotal system sensible and latent gain: 206,506 BtuhPretreated air sensible gain: 7,918 BtuhPretreated air latent gain: 30,115 Btuh

Check FiguresTotal Air Handler Supply Air (based on a 24° TD): 4,215 CFMTotal Air Handler Vent. Air (28.47% of Supply): 1,200 CFM

Total Conditioned Air Space: 3,170 Sq.ftSupply Air Per Unit Area: 1.3299 CFM/Sq.ftArea Per Cooling Capacity: 184.2 Sq.ft/TonCooling Capacity Per Area: 0.0054 Tons/Sq.ftHeating Capacity Per Area: 2.05 Btuh/Sq.ft

Total Heating Required With Outside Air: 6,505 BtuhTotal Cooling Required With Outside Air: 17.21 Tons

C:\ ...\AG-SC 001 P 16-71 C TERMICAS.CH8 miércoles, 14 de septiembre de 2016, 02:31 p. m.

Page 44: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 27/02/12

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 28 de 34

28/34

7.2.2 Anexo ELEMENTOS FINITOS

Page 45: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios
Page 46: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios
Page 47: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios
Page 48: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios
Page 49: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios
Page 50: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios
Page 51: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios
Page 52: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios
Page 53: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 27/02/12

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 29 de 34

29/34

7.2.3 Anexo EXTRACCIONES MECANICAS

Page 54: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

FECHA 05/07/2016

REVISION 1 D Castro

ANOTACIONES Version Inicial 05/07/2016

PISO ZONA ITEM CANTIDAD SISTEMA AREA EXTRACCION AREA** ALTURA** UNIDADES*** CAMBIOS / HORA **** CFM/UNID CFM -CAMBIOS CFM-UNIDAD CFM CFM AJUSTADOS OBSERVACIONES

VE-XX mts 2 mts Sanit y Orinales

PRIMERO EDIFICIO A1 ZE-01 P1 A1 2 1 BAÑOS 10.2 3 2 10 70 182 140 182 200 0

PRIMERO EDIFICIO A1 ZE-02 P1 A1 2 1 BAÑOS 5.8 3 1 10 70 104 70 104 100 0

SEGUNDO EDIFICIO A1 ZE-03 P1 A1 1 6 ALMACEN QUIMICOS 8.95 3 0 10 71 160 0 160 200

PRIMERO EDIFICIO B1 ZE-01 P1 B1 2 2 BAÑOS 10.2 3 2 10 70 182 140 182 102 0

PRIMERO EDIFICIO B1 ZE-02 P1 B1 2 2 BAÑOS 5.8 3 1 10 70 104 70 104 100 0

PRIMERO EDIFICIO B1 ZE-03 P1 B1 1 2 CLEARNING 7.2 3 0 10 70 129 0 129 150 0

PRIMERO EDIFICIO B1 ZE-04 P1 B1 1 3 BASURAS 2.7 3 0 20 70 96 0 96 100 0

PRIMERO EDIFICIO B1 ZE-05 P1 B1 2 3 BAÑOS 1.8 3 0 10 70 32 0 32 50 0

PRIMERO EDIFICIO B1 ZE-06 P1 B1 2 3 VESTIER 5.8 3 0 10 70 104 0 104 100 0

PRIMERO EDIFICIO B1 ZE-07 P1 B1 1 3 CUARTO 4.3 3 0 10 70 77 0 77 100 0

SEGUNDO EDIFICIO B1 ZE-01 P2 B1 2 4 BAÑOS 5 3 1 10 70 89 70 89 100 0

SEGUNDO EDIFICIO B1 ZE-02 P2 B1 2 4 BAÑOS 12 3 3 10 70 214 210 214 200 0

SEGUNDO EDIFICIO D1 ZE-01 P2 D1 2 5 BAÑOS 5 3 3 10 70 89 210 210 200 0

0 0 0 3 0 10 70 0 0 - 0 0

* Basado en ANSI/ASHRAE st 62.1-2004

** Solo para calculos x Cambios Hora

**** Basado en ASHRAE Hospital and clinics

AG-MC 001

ANOTACIONES

VERSIÓN 0

PROYECTO P16-71 UNAL TUMACO UBICACIÓN

MEMORIA DE CÁLCULOS: EXTRACCIONES PUNTUALES

TUMACO DISEÑADOR Ing Diego G Castro

EXTRACCION

DIRECTA

TABLA DE DATOS

ESPACIO PARA LOGO

Page 55: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 27/02/12

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 30 de 34

30/34

7.2.4 Anexo VENTILACIONES MECANICAS

Page 56: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

BLOQUE ITEM PISO AREA (m2) NO. PERSONAS

NORMA POR AREA

(l/s/m2)

NORMA POR PERSONAS

(l/s por persona)

A Z-01 P1 A1 1 193.29 29 0.06 0.7

Z-01 P2 A1 2 79.41 19 0.06 0.7

Z-02 P2 A1 2 8.77 1 0.06 0.7

B Z-01 P2 B1 2 67.42 41 0.06 0.7

Z-02 P2 B1 2 67.42 31 0.06 0.7

Z-03 P2 B1 2 3.4 1 0.06 0.7

Z-04 P2 B1 2 10.33 1 0.06 0.7

Z-05 P2 B1 2 72.01 25 0.06 0.7

Z-06 P2 B1 2 5.83 3 0.06 0.7

Z-07 P2 B1 2 5.83 3 0.06 0.7

Z-08 P2 B1 2 11.87 8 0.06 0.7

C Z-01 P2 C1 2 30.83 3 0.06 0.7

Z-02 P2 C1 2 7.16 1 0.06 0.7

Z-03 P2 C1 2 15.57 1 0.06 0.7

Z-04 P2 C1 2 72.48 25 0.06 0.7

Z-05 P2 C1 2 45.12 21 0.06 0.7

Z-06 P2 C1 2 4.2 1 0.06 0.7

Z-07 P2 C1 2 6.79 1 0.06 0.7

D Z-01 P2 D1 2 212.94 244 0.06 0.7

Z-02 P2 D1 2 1.46 1 0.06 0.7

Z-03 P2 D1 2 4.25 2 0.06 0.7

Ing Diego G CastroTUMACO

MEMORIA DE CALCULO: NIVELES DE VENTILACION

ESPACIO PARA LOGO

AG-MC VERSIÓN 0

PROYECTO P16-71 UNAL TUMACO UBICACIÓN DISEÑADOR

NOMBRE NIVELES DE VENTILACION

BIBLIOTECA

LABORATORIOS

CUARTO TECNICO

Ver calculo de cargas termicas

Ver calculo de cargas termicas

Ver calculo de cargas termicas

Ver calculo de cargas termicas

Ver calculo de cargas termicas

Ver calculo de cargas termicas

Ver calculo de cargas termicas

SALON ICI

RACK

CUARTO TECNICO

AUDITORIO

RACK

CONTROL

OFICINA DOCENTES

Ver calculo de cargas termicas

Ver calculo de cargas termicas

Ver calculo de cargas termicas

Ver calculo de cargas termicas

Ver calculo de cargas termicas

Ver calculo de cargas termicas

Ver calculo de cargas termicas

Ver calculo de cargas termicas

Ver calculo de cargas termicas

Ver calculo de cargas termicas

Ver calculo de cargas termicas

Ver calculo de cargas termicas

Ver calculo de cargas termicas

TABLA DE DATOS

Ver calculo de cargas termicas

SALA DE JUNTAS

CENTRO DE CONTROL

RACK

CUARTO ICE

ZONA DE TRABAJO AUTONOMO

AULAS 1 A 3

AULA 4

RACK

CUARTO TECNICO

ZONA DE TRABAJO AUTONOMO

OFICINA DOCENTES

Page 57: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 27/02/12

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 31 de 34

31/34

7.2.5 Anexo CALCULO DUCTOS

Page 58: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 08/09/16

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 28 de 31

28/31

7.2.5 Anexo CALCULO DUCTOS

Page 59: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

Duct Pressure Loss ReportProject Name UNIVERSIDAD NACIONAL DE TUMACOProject Issue Date 14/09/2016Project StatusClient Name UNIVERSIDAD NACIONALProject Address BDFGHFGHDGProject Number 16‐71Organiza㐀鸂on Name AIREG SASOrganiza㐀鸂on Descrip㐀鸂onBuilding Name UNIVERSIDAD NACIONAL SEDE TUMACOAuthor ING DIEGO CASTRO GRun Time 14/09/2016 14:25:30

UPA‐01System Informa㐀鸂onSystem Classifica㐀鸂on Supply AirSystem Type Supply AirSystem Name UPA‐01Abbrevia㐀鸂on

Total Pressure Loss Calcula㐀鸂ons by Sec㐀鸂ons

Sec㐀鸂on Element Flow Size Velocity VelocityPressure Length Loss

Coefficient Fric㐀鸂onTotalPressureLoss

Sec㐀鸂onPressure Loss

1Duct 1100 CFM 10"x16" 990.0

䴀턃/min ‐ 4.12 ‐ 0.11 in‐wg/100䴀턃 3.9 Pa

Fiᜀꘂngs 1100 CFM ‐ 990.0䴀턃/min 15.2 Pa ‐ 0 ‐ 0.0 Pa

3.9 Pa

4Duct 0 CFM 18"x16" 0.0 䴀턃/min ‐ 0.36 ‐ 0.00 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 0 CFM ‐ 0.0 䴀턃/min 0.0 Pa ‐ 0 ‐ 0.0 Pa0.0 Pa

5Duct 4950 CFM 28"x16" 1591.1

䴀턃/min ‐ 2.43 ‐ 0.15 in‐wg/100䴀턃 3.0 Pa

Fiᜀꘂngs 4950 CFM ‐ 1591.1䴀턃/min 39.3 Pa ‐ 1.0875 ‐ 42.7 Pa

45.7 Pa

6Duct 0 CFM 12"x16" 0.0 䴀턃/min ‐ 0.65 ‐ 0.00 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 0 CFM ‐ 0.0 䴀턃/min 0.0 Pa ‐ 0 ‐ 0.0 Pa0.0 Pa

7Duct 1650 CFM 12"x16" 1237.5

䴀턃/min ‐ 1.64 ‐ 0.15 in‐wg/100䴀턃 2.0 Pa

Fiᜀꘂngs 1650 CFM ‐ 1237.5䴀턃/min 23.8 Pa ‐ 0 ‐ 0.0 Pa

2.0 Pa

8Duct 2750 CFM 18"x16" 1375.0

䴀턃/min ‐ 2.77 ‐ 0.14 in‐wg/100䴀턃 3.2 Pa

Fiᜀꘂngs 2750 CFM ‐ 1375.0䴀턃/min 29.3 Pa ‐ 1.249206 ‐ 36.6 Pa

39.9 Pa

9Duct 0 CFM 14"x16" 0.0 䴀턃/min ‐ 0.44 ‐ 0.00 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 0 CFM ‐ 0.0 䴀턃/min 0.0 Pa ‐ 0 ‐ 0.0 Pa0.0 Pa

10Duct 0 CFM 6"x16" 0.0 䴀턃/min ‐ 0.32 ‐ 0.00 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 0 CFM ‐ 0.0 䴀턃/min 0.0 Pa ‐ 0 ‐ 0.0 Pa0.0 Pa

11Duct 2200 CFM 14"x16" 1414.3

䴀턃/min ‐ 1.00 ‐ 0.18 in‐wg/100䴀턃 1.4 Pa

Fiᜀꘂngs 2200 CFM ‐ 1414.3䴀턃/min 31.0 Pa ‐ 1.315556 ‐ 40.8 Pa

42.3 Pa

12Duct 550 CFM 6"x16" 825.0

䴀턃/min ‐ 4.12 ‐ 0.13 in‐wg/100䴀턃 4.3 Pa

Fiᜀꘂngs 550 CFM ‐ 825.0䴀턃/min 10.6 Pa ‐ 0.068951 ‐ 0.7 Pa

5.0 Pa

Duct 1650 CFM 12"x16" 1237.5䴀턃/min ‐ 1.69 ‐ 0.15 in‐

wg/100䴀턃 2.1 Pa

Page 60: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

13 Fiᜀꘂngs 1650 CFM ‐ 1237.5䴀턃/min

23.8 Pa ‐ 0 ‐ 0.0 Pa 2.1 Pa

14Fiᜀꘂngs 550 CFM ‐ 6715.7

䴀턃/min 699.8 Pa ‐ 0 ‐ 0.0 Pa

Equipment 550 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa0.0 Pa

15Duct 550 CFM ‐ 6302.5

䴀턃/min ‐ 1.44 ‐ 15.26 in‐wg/100䴀턃 179.3 Pa

Fiᜀꘂngs 550 CFM ‐ 6302.5䴀턃/min 616.4 Pa ‐ 0 ‐ 0.0 Pa

179.3 Pa

16Duct 550 CFM 6"x16" 825.0

䴀턃/min ‐ 2.90 ‐ 0.13 in‐wg/100䴀턃 3.0 Pa

Fiᜀꘂngs 550 CFM ‐ 825.0䴀턃/min 10.6 Pa ‐ 0 ‐ 0.0 Pa

3.0 Pa

17Fiᜀꘂngs 550 CFM ‐ 6715.7

䴀턃/min 699.8 Pa ‐ 0 ‐ 0.0 Pa

Equipment 550 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa0.0 Pa

18Duct 550 CFM ‐ 6302.5

䴀턃/min ‐ 1.36 ‐ 15.26 in‐wg/100䴀턃 169.4 Pa

Fiᜀꘂngs 550 CFM ‐ 6302.5䴀턃/min 616.4 Pa ‐ 0 ‐ 0.0 Pa

169.4 Pa

19Duct 550 CFM 12"x16" 412.5

䴀턃/min ‐ 0.48 ‐ 0.02 in‐wg/100䴀턃 0.1 Pa

Fiᜀꘂngs 550 CFM ‐ 412.5䴀턃/min 2.6 Pa ‐ 0 ‐ 0.0 Pa

0.1 Pa

20Fiᜀꘂngs 550 CFM ‐ 6715.7

䴀턃/min 699.8 Pa ‐ 0 ‐ 0.0 Pa

Equipment 550 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa0.0 Pa

21Duct 550 CFM ‐ 6302.5

䴀턃/min ‐ 1.44 ‐ 15.26 in‐wg/100䴀턃 179.7 Pa

Fiᜀꘂngs 550 CFM ‐ 6302.5䴀턃/min 616.4 Pa ‐ 0 ‐ 0.0 Pa

179.7 Pa

22Duct 0 CFM 6"x16" 0.0 䴀턃/min ‐ 0.51 ‐ 0.00 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 0 CFM ‐ 0.0 䴀턃/min 0.0 Pa ‐ 0 ‐ 0.0 Pa0.0 Pa

23Fiᜀꘂngs 550 CFM ‐ 6715.7

䴀턃/min 699.8 Pa ‐ 0 ‐ 0.0 Pa

Equipment 550 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa0.0 Pa

24Duct 550 CFM ‐ 6302.5

䴀턃/min ‐ 1.98 ‐ 15.26 in‐wg/100䴀턃 246.7 Pa

Fiᜀꘂngs 550 CFM ‐ 6302.5䴀턃/min 616.4 Pa ‐ 0 ‐ 0.0 Pa

246.7 Pa

26Fiᜀꘂngs 550 CFM ‐ 6715.7

䴀턃/min 699.8 Pa ‐ 0 ‐ 0.0 Pa

Equipment 550 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa0.0 Pa

27Duct 550 CFM ‐ 6302.5

䴀턃/min ‐ 1.88 ‐ 15.26 in‐wg/100䴀턃 234.0 Pa

Fiᜀꘂngs 550 CFM ‐ 6302.5䴀턃/min 616.4 Pa ‐ 0 ‐ 0.0 Pa

234.0 Pa

28Duct 1100 CFM 12"x16" 825.0

䴀턃/min ‐ 2.47 ‐ 0.07 in‐wg/100䴀턃 1.5 Pa

Fiᜀꘂngs 1100 CFM ‐ 825.0䴀턃/min 10.6 Pa ‐ 0 ‐ 0.0 Pa

1.5 Pa

29Fiᜀꘂngs 550 CFM ‐ 6715.7

䴀턃/min 699.8 Pa ‐ 0 ‐ 0.0 Pa

Equipment 550 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa0.0 Pa

30Duct 550 CFM ‐ 6302.5

䴀턃/min ‐ 1.55 ‐ 15.26 in‐wg/100䴀턃 192.7 Pa

Fiᜀꘂngs 550 CFM ‐ 6302.5䴀턃/min 616.4 Pa ‐ 0 ‐ 0.0 Pa

192.7 Pa

32Fiᜀꘂngs 550 CFM ‐ 6715.7

䴀턃/min 699.8 Pa ‐ 0 ‐ 0.0 Pa

Equipment 550 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa0.0 Pa

Duct 550 CFM ‐ 6302.5 ‐ 1.50 ‐ 15.26 in‐ 187.2 Pa

Page 61: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

33 䴀턃/min wg/100䴀턃Fiᜀꘂngs 550 CFM ‐ 6302.5

䴀턃/min 616.4 Pa ‐ 0 ‐ 0.0 Pa187.2 Pa

34Duct 1100 CFM 12"x16" 825.0

䴀턃/min ‐ 0.50 ‐ 0.07 in‐wg/100䴀턃 0.3 Pa

Fiᜀꘂngs 1100 CFM ‐ 825.0䴀턃/min 10.6 Pa ‐ 0 ‐ 0.0 Pa

0.3 Pa

35Fiᜀꘂngs 550 CFM ‐ 6715.7

䴀턃/min 699.8 Pa ‐ 0 ‐ 0.0 Pa

Equipment 550 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa0.0 Pa

36Duct 550 CFM ‐ 6302.5

䴀턃/min ‐ 1.53 ‐ 15.26 in‐wg/100䴀턃 190.4 Pa

Fiᜀꘂngs 550 CFM ‐ 6302.5䴀턃/min 616.4 Pa ‐ 0 ‐ 0.0 Pa

190.4 Pa

37Duct 0 CFM 10"x16" 0.0 䴀턃/min ‐ 0.51 ‐ 0.00 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 0 CFM ‐ 0.0 䴀턃/min 0.0 Pa ‐ 0 ‐ 0.0 Pa0.0 Pa

38Duct 550 CFM ‐ 6302.5

䴀턃/min ‐ 1.87 ‐ 15.26 in‐wg/100䴀턃 232.4 Pa

Fiᜀꘂngs 550 CFM ‐ 6302.5䴀턃/min 616.4 Pa ‐ 0 ‐ 0.0 Pa

232.4 Pa

39Fiᜀꘂngs 550 CFM ‐ 6715.7

䴀턃/min 699.8 Pa ‐ 0 ‐ 0.0 Pa

Equipment 550 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa0.0 Pa

40 Duct 550 CFM 12"x16" 412.5䴀턃/min ‐ 0.00 ‐ 0.02 in‐

wg/100䴀턃 0.0 Pa 0.0 Pa

41 Duct 1100 CFM 12"x16" 825.0䴀턃/min ‐ 0.02 ‐ 0.07 in‐

wg/100䴀턃 0.0 Pa 0.0 Pa

42 Duct 550 CFM 14"x16" 353.6䴀턃/min ‐ 0.03 ‐ 0.01 in‐

wg/100䴀턃 0.0 Pa 0.0 Pa

Cri㐀鸂cal Path : 5‐11‐13‐24‐23 ; Total Pressure Loss : 336.7 Pa

Detail Informa㐀鸂on of Straight Segment by Sec㐀鸂ons

Sec㐀鸂on Element ID Flow Size Velocity VelocityPressure Length Pressure Loss Total

Pressure Loss

1 883871 1100 CFM 10"x16" 990.0 䴀턃/min 15.2 Pa 4.12 3.9 Pa 3.9 Pa

4 883874 0 CFM 18"x16" 0.0 䴀턃/min 0.0 Pa 0.36 0.0 Pa 0.0 Pa

5883887 4950 CFM 28"x16" 1591.1 䴀턃/min 39.3 Pa 0.24 0.3 Pa883888 4950 CFM 28"x16" 1591.1 䴀턃/min 39.3 Pa 2.19 2.7 Pa

3.0 Pa

6 883873 0 CFM 12"x16" 0.0 䴀턃/min 0.0 Pa 0.65 0.0 Pa 0.0 Pa

7 883872 1650 CFM 12"x16" 1237.5 䴀턃/min 23.8 Pa 1.64 2.0 Pa 2.0 Pa

8 883874 2750 CFM 18"x16" 1375.0 䴀턃/min 29.3 Pa 2.77 3.2 Pa 3.2 Pa

9 883885 0 CFM 14"x16" 0.0 䴀턃/min 0.0 Pa 0.44 0.0 Pa 0.0 Pa

10 883881 0 CFM 6"x16" 0.0 䴀턃/min 0.0 Pa 0.32 0.0 Pa 0.0 Pa

11 883885 2200 CFM 14"x16" 1414.3 䴀턃/min 31.0 Pa 1.00 1.4 Pa 1.4 Pa

12 883879 550 CFM 6"x16" 825.0 䴀턃/min 10.6 Pa 4.12 4.3 Pa 4.3 Pa

13 883880 1650 CFM 12"x16" 1237.5 䴀턃/min 23.8 Pa 1.69 2.1 Pa 2.1 Pa

15 883895 550 CFM 4" 6302.5 䴀턃/min 616.4 Pa 1.44 179.3 Pa 179.3 Pa

16 883881 550 CFM 6"x16" 825.0 䴀턃/min 10.6 Pa 2.90 3.0 Pa 3.0 Pa

18 883901 550 CFM 4" 6302.5 䴀턃/min 616.4 Pa 1.36 169.4 Pa 169.4 Pa

19 883880 550 CFM 12"x16" 412.5 䴀턃/min 2.6 Pa 0.48 0.1 Pa 0.1 Pa

21 883907 550 CFM 4" 6302.5 䴀턃/min 616.4 Pa 1.44 179.7 Pa 179.7 Pa

22 883879 0 CFM 6"x16" 0.0 䴀턃/min 0.0 Pa 0.51 0.0 Pa 0.0 Pa

24 883913 550 CFM 4" 6302.5 䴀턃/min 616.4 Pa 1.98 246.7 Pa 246.7 Pa

27 883919 550 CFM 4" 6302.5 䴀턃/min 616.4 Pa 1.88 234.0 Pa 234.0 Pa

28 883873 1100 CFM 12"x16" 825.0 䴀턃/min 10.6 Pa 2.47 1.5 Pa 1.5 Pa

30 883925 550 CFM 4" 6302.5 䴀턃/min 616.4 Pa 1.55 192.7 Pa 192.7 Pa

33 883931 550 CFM 4" 6302.5 䴀턃/min 616.4 Pa 1.50 187.2 Pa 187.2 Pa

Page 62: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

34 883872 1100 CFM 12"x16" 825.0 䴀턃/min 10.6 Pa 0.50 0.3 Pa 0.3 Pa

36 883937 550 CFM 4" 6302.5 䴀턃/min 616.4 Pa 1.53 190.4 Pa 190.4 Pa

37 883871 0 CFM 10"x16" 0.0 䴀턃/min 0.0 Pa 0.51 0.0 Pa 0.0 Pa

38 883944 550 CFM 4" 6302.5 䴀턃/min 616.4 Pa 1.87 232.4 Pa 232.4 Pa

40 883873 550 CFM 12"x16" 412.5 䴀턃/min 2.6 Pa 0.00 0.0 Pa 0.0 Pa

41 883880 1100 CFM 12"x16" 825.0 䴀턃/min 10.6 Pa 0.02 0.0 Pa 0.0 Pa

42 883885 550 CFM 14"x16" 353.6 䴀턃/min 1.9 Pa 0.03 0.0 Pa 0.0 Pa

Fiᜀꘂng and Accessory Loss Coefficient Summary by Sec㐀鸂ons

Sec㐀鸂on Element ID Loss Method ASHRAE Table Loss Coefficient Pressure Loss TotalPressure Loss

1 883882 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

4 883876 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

5883884 Coefficient from

ASHRAE Table SR5‐15 0 0.0 Pa

883889 Coefficient fromASHRAE Table SR3‐1 1.0875 42.7 Pa

42.7 Pa

6 883877 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

7 883883 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

8 883884 Coefficient fromASHRAE Table SR5‐15 1.249206 36.6 Pa 36.6 Pa

9 883886 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

10 883893 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

11 883884 Coefficient fromASHRAE Table SR5‐15 1.315556 40.8 Pa 40.8 Pa

12 883892 Coefficient fromASHRAE Table SR4‐2 0.068951 0.7 Pa 0.7 Pa

13 883891 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

14 883897 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

15883897 Coefficient from

ASHRAE Table ‐ 0 0.0 Pa

883899 Coefficient fromASHRAE Table ‐ 0 0.0 Pa

0.0 Pa

16 883890 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

17 883903 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

18

883903 Coefficient fromASHRAE Table ‐ 0 0.0 Pa

883905 Coefficient fromASHRAE Table ‐ 0 0.0 Pa

0.0 Pa

19 883892 Coefficient fromASHRAE Table SR4‐2 0 0.0 Pa 0.0 Pa

20 883909 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

21883909 Coefficient from

ASHRAE Table ‐ 0 0.0 Pa

883911 Coefficient fromASHRAE Table ‐ 0 0.0 Pa

0.0 Pa

22 883894 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

23 883915 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

Page 63: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

24883915 Coefficient from

ASHRAE Table‐ 0 0.0 Pa

883917 Coefficient fromASHRAE Table ‐ 0 0.0 Pa

0.0 Pa

26 883921 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

27883921 Coefficient from

ASHRAE Table ‐ 0 0.0 Pa

883923 Coefficient fromASHRAE Table ‐ 0 0.0 Pa

0.0 Pa

28 883875 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

29 883927 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

30883927 Coefficient from

ASHRAE Table ‐ 0 0.0 Pa

883929 Coefficient fromASHRAE Table ‐ 0 0.0 Pa

0.0 Pa

32 883933 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

33883933 Coefficient from

ASHRAE Table ‐ 0 0.0 Pa

883935 Coefficient fromASHRAE Table ‐ 0 0.0 Pa

0.0 Pa

34 883882 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

35 883939 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

36883939 Coefficient from

ASHRAE Table ‐ 0 0.0 Pa

883941 Coefficient fromASHRAE Table ‐ 0 0.0 Pa

0.0 Pa

37 883878 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

38883946 Coefficient from

ASHRAE Table ‐ 0 0.0 Pa

883948 Coefficient fromASHRAE Table ‐ 0 0.0 Pa

0.0 Pa

39 883946 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

UPA‐01 RSystem Informa㐀鸂onSystem Classifica㐀鸂on Return AirSystem Type Return AirSystem Name UPA‐01 RAbbrevia㐀鸂on

Total Pressure Loss Calcula㐀鸂ons by Sec㐀鸂ons

Sec㐀鸂on Element Flow Size Velocity VelocityPressure Length Loss

Coefficient Fric㐀鸂onTotalPressureLoss

Sec㐀鸂onPressure Loss

1

Duct 938 CFM 16"x16" 527.6䴀턃/min ‐ 0.10 ‐ 0.03 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 938 CFM ‐ 527.6䴀턃/min 4.3 Pa ‐ 0 ‐ 0.0 Pa

Air Terminal 938 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa

0.0 Pa

2Duct 0 CFM 28"x10" 0.0 䴀턃/min ‐ 0.52 ‐ 0.00 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 0 CFM ‐ 0.0 䴀턃/min 0.0 Pa ‐ 0 ‐ 0.0 Pa0.0 Pa

3

Duct 0 CFM 26"x10" 0.0 䴀턃/min ‐ 2.04 ‐ 0.10 in‐wg/100䴀턃 1.7 Pa

Fiᜀꘂngs 0 CFM ‐ 0.0 䴀턃/min 16.8 Pa ‐ 0 ‐ 0.0 Pa 1.7 Pa

Page 64: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

4

Duct 938 CFM 16"x16" 527.6䴀턃/min ‐ 0.10 ‐ 0.03 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 938 CFM ‐ 527.6䴀턃/min 4.3 Pa ‐ 0 ‐ 0.0 Pa

Air Terminal 938 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa

0.0 Pa

8Duct 1876 CFM 28"x10" 964.8

䴀턃/min ‐ 0.32 ‐ 0.09 in‐wg/100䴀턃 0.2 Pa

Fiᜀꘂngs 1876 CFM ‐ 964.8䴀턃/min 14.4 Pa ‐ 0 ‐ 0.0 Pa

0.2 Pa

12Duct 1876 CFM 26"x10" 1039.0

䴀턃/min ‐ 2.31 ‐ 0.10 in‐wg/100䴀턃 1.9 Pa

Fiᜀꘂngs 1876 CFM ‐ 1039.0䴀턃/min 16.8 Pa ‐ 1.223846 ‐ 20.5 Pa

22.4 Pa

13Duct 3752 CFM 26"x18" 1154.5

䴀턃/min ‐ 11.54 ‐ 0.08 in‐wg/100䴀턃 7.4 Pa

Fiᜀꘂngs 3752 CFM ‐ 1154.5䴀턃/min 20.7 Pa ‐ 2.299886 ‐ 47.6 Pa

54.9 Pa

14

Duct 938 CFM 16"x16" 527.6䴀턃/min ‐ 0.10 ‐ 0.03 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 938 CFM ‐ 527.6䴀턃/min 4.3 Pa ‐ 0 ‐ 0.0 Pa

Air Terminal 938 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa

0.0 Pa

15Duct 1876 CFM 26"x10" 1039.0

䴀턃/min ‐ 4.13 ‐ 0.10 in‐wg/100䴀턃 1.7 Pa

Fiᜀꘂngs 1876 CFM ‐ 1039.0䴀턃/min 16.8 Pa ‐ 1.223846 ‐ 20.5 Pa

22.2 Pa

16

Duct 938 CFM 16"x16" 527.6䴀턃/min ‐ 0.10 ‐ 0.03 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 938 CFM ‐ 527.6䴀턃/min 4.3 Pa ‐ 0 ‐ 0.0 Pa

Air Terminal 938 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa

0.0 Pa

18 Fiᜀꘂngs 3752 CFM ‐ 2287.2䴀턃/min 81.2 Pa ‐ 0.241461 ‐ 19.6 Pa 19.6 Pa

19 Duct 938 CFM 28"x10" 482.4䴀턃/min ‐ 0.60 ‐ 0.02 in‐

wg/100䴀턃 0.1 Pa 0.1 Pa

20 Duct 938 CFM 26"x10" 519.5䴀턃/min ‐ 0.60 ‐ 0.03 in‐

wg/100䴀턃 0.1 Pa 0.1 Pa

21 Duct 1876 CFM 26"x10" 1039.0䴀턃/min ‐ 9.54 ‐ 0.10 in‐

wg/100䴀턃 8.0 Pa 8.0 Pa

Cri㐀鸂cal Path : 3‐15‐18‐13 ; Total Pressure Loss : 98.5 Pa

Detail Informa㐀鸂on of Straight Segment by Sec㐀鸂ons

Sec㐀鸂on Element ID Flow Size Velocity VelocityPressure Length Pressure Loss Total

Pressure Loss

1 883957 938 CFM 16"x16" 527.6 䴀턃/min 4.3 Pa 0.10 0.0 Pa 0.0 Pa

2 883954 0 CFM 28"x10" 0.0 䴀턃/min 0.0 Pa 0.52 0.0 Pa 0.0 Pa

3 883963 0 CFM 26"x10" 0.0 䴀턃/min 16.8 Pa 0.00 1.7 Pa 1.7 Pa

4 883958 938 CFM 16"x16" 527.6 䴀턃/min 4.3 Pa 0.10 0.0 Pa 0.0 Pa

8 883954 1876 CFM 28"x10" 964.8 䴀턃/min 14.4 Pa 0.32 0.2 Pa 0.2 Pa

12 883955 1876 CFM 26"x10" 1039.0 䴀턃/min 16.8 Pa 2.31 1.9 Pa 1.9 Pa

13883973 3752 CFM 26"x18" 1154.5 䴀턃/min 20.7 Pa 8.81 5.6 Pa883974 3752 CFM 26"x18" 1154.5 䴀턃/min 20.7 Pa 0.58 0.4 Pa883976 3752 CFM 26"x18" 1154.5 䴀턃/min 20.7 Pa 2.14 1.4 Pa

7.4 Pa

14 883968 938 CFM 16"x16" 527.6 䴀턃/min 4.3 Pa 0.10 0.0 Pa 0.0 Pa

15883962 1876 CFM 26"x10" 1039.0 䴀턃/min 16.8 Pa 2.08 1.7 Pa883963 1876 CFM 26"x10" 1039.0 䴀턃/min 16.8 Pa 0.00 0.0 Pa

1.7 Pa

16 883970 938 CFM 16"x16" 527.6 䴀턃/min 4.3 Pa 0.10 0.0 Pa 0.0 Pa

19 883954 938 CFM 28"x10" 482.4 䴀턃/min 3.6 Pa 0.60 0.1 Pa 0.1 Pa

20 883963 938 CFM 26"x10" 519.5 䴀턃/min 4.2 Pa 0.60 0.1 Pa 0.1 Pa

Page 65: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

21 883963 1876 CFM 26"x10" 1039.0 䴀턃/min 16.8 Pa 9.54 8.0 Pa 8.0 Pa

Fiᜀꘂng and Accessory Loss Coefficient Summary by Sec㐀鸂ons

Sec㐀鸂on Element ID Loss Method ASHRAE Table Loss Coefficient Pressure Loss TotalPressure Loss

1 883961 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

2 883956 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

3 883965 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

4 883960 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

8 883967 Coefficient fromASHRAE Table ER3‐1 0 0.0 Pa 0.0 Pa

12

883959 Coefficient fromASHRAE Table ‐ 0 0.0 Pa

883966 Coefficient fromASHRAE Table ER3‐1 1.223846 20.5 Pa

883967 Coefficient fromASHRAE Table ER3‐1 0 0.0 Pa

20.5 Pa

13

883972 Coefficient fromASHRAE Table ER4‐2 0 0.0 Pa

883975 Coefficient fromASHRAE Table ER3‐1 1.186923 24.5 Pa

883977 Coefficient fromASHRAE Table ER3‐1 1.112963 23.0 Pa

47.6 Pa

14 883969 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

15883959 Coefficient from

ASHRAE Table ‐ 0 0.0 Pa

883964 Coefficient fromASHRAE Table ER3‐1 1.223846 20.5 Pa

20.5 Pa

16 883971 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

18883959 Coefficient from

ASHRAE Table ‐ 0 0.0 Pa

883972 Coefficient fromASHRAE Table ER4‐2 0.241461 19.6 Pa

19.6 Pa

URC‐01 OutdoorSystem Informa㐀鸂onSystem Classifica㐀鸂on Supply AirSystem Type Outdoor AirSystem Name URC‐01 OutdoorAbbrevia㐀鸂on

Total Pressure Loss Calcula㐀鸂ons by Sec㐀鸂ons

Sec㐀鸂on Element Flow Size Velocity VelocityPressure Length Loss

Coefficient Fric㐀鸂onTotalPressureLoss

Sec㐀鸂onPressure Loss

1Fiᜀꘂngs 350 CFM ‐ 662.4

䴀턃/min 6.8 Pa ‐ 0 ‐ 0.0 Pa

Equipment 350 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa0.0 Pa

2Duct 350 CFM 12"x6" 700.0

䴀턃/min ‐ 7.89 ‐ 0.10 in‐wg/100䴀턃 6.7 Pa

Fiᜀꘂngs 350 CFM ‐ 700.0䴀턃/min 7.6 Pa ‐ 1.215503 ‐ 9.2 Pa

16.0 Pa

3

Duct 350 CFM 12"x12" 350.0䴀턃/min ‐ 0.09 ‐ 0.02 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 350 CFM ‐ 350.0䴀턃/min 1.9 Pa ‐ 0 ‐ 0.0 Pa

Air Terminal 350 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa

0.0 Pa

Page 66: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

4 Duct 0 CFM 12"x6" 0.0 䴀턃/min ‐ 0.32 ‐ 0.00 in‐wg/100䴀턃

0.0 Pa

Fiᜀꘂngs 0 CFM ‐ 0.0 䴀턃/min 0.0 Pa ‐ 0 ‐ 0.0 Pa

0.0 Pa

Cri㐀鸂cal Path : 1‐2‐3 ; Total Pressure Loss : 16.0 Pa

Detail Informa㐀鸂on of Straight Segment by Sec㐀鸂ons

Sec㐀鸂on Element ID Flow Size Velocity VelocityPressure Length Pressure Loss Total

Pressure Loss

2813245 350 CFM 12"x6" 700.0 䴀턃/min 7.6 Pa 3.78 3.2 Pa813256 350 CFM 12"x6" 700.0 䴀턃/min 7.6 Pa 4.11 3.5 Pa

6.7 Pa

3 813816 350 CFM 12"x12" 350.0 䴀턃/min 1.9 Pa 0.09 0.0 Pa 0.0 Pa

4 813245 0 CFM 12"x6" 0.0 䴀턃/min 0.0 Pa 0.32 0.0 Pa 0.0 Pa

Fiᜀꘂng and Accessory Loss Coefficient Summary by Sec㐀鸂ons

Sec㐀鸂on Element ID Loss Method ASHRAE Table Loss Coefficient Pressure Loss TotalPressure Loss

1 828647 Coefficient fromASHRAE Table SR4‐3 0 0.0 Pa 0.0 Pa

2828646 Coefficient from

ASHRAE Table SR3‐1 1.21 9.2 Pa

828647 Coefficient fromASHRAE Table SR4‐3 0.005503 0.0 Pa

9.2 Pa

3 813824 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

4 813327 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

URC‐02 OutdoorSystem Informa㐀鸂onSystem Classifica㐀鸂on Supply AirSystem Type Outdoor AirSystem Name URC‐02 OutdoorAbbrevia㐀鸂on

Total Pressure Loss Calcula㐀鸂ons by Sec㐀鸂ons

Sec㐀鸂on Element Flow Size Velocity VelocityPressure Length Loss

Coefficient Fric㐀鸂onTotalPressureLoss

Sec㐀鸂onPressure Loss

1Fiᜀꘂngs 350 CFM ‐ 662.4

䴀턃/min 6.8 Pa ‐ 0 ‐ 0.0 Pa

Equipment 350 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa0.0 Pa

2Duct 350 CFM 12"x6" 700.0

䴀턃/min ‐ 5.13 ‐ 0.10 in‐wg/100䴀턃 4.4 Pa

Fiᜀꘂngs 350 CFM ‐ 700.0䴀턃/min 7.6 Pa ‐ 1.215503 ‐ 9.2 Pa

13.6 Pa

3

Duct 350 CFM 12"x12" 350.0䴀턃/min ‐ 0.09 ‐ 0.02 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 350 CFM ‐ 350.0䴀턃/min 1.9 Pa ‐ 0 ‐ 0.0 Pa

Air Terminal 350 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa

0.0 Pa

4Duct 0 CFM 12"x6" 0.0 䴀턃/min ‐ 0.32 ‐ 0.00 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 0 CFM ‐ 0.0 䴀턃/min 0.0 Pa ‐ 0 ‐ 0.0 Pa0.0 Pa

Cri㐀鸂cal Path : 1‐2‐3 ; Total Pressure Loss : 13.6 Pa

Detail Informa㐀鸂on of Straight Segment by Sec㐀鸂ons

Sec㐀鸂on Element ID Flow Size Velocity VelocityPressure Length Pressure Loss Total

Pressure Loss

2813885 350 CFM 12"x6" 700.0 䴀턃/min 7.6 Pa 3.78 3.2 Pa814098 350 CFM 12"x6" 700.0 䴀턃/min 7.6 Pa 1.35 1.2 Pa

4.4 Pa

3 813892 350 CFM 12"x12" 350.0 䴀턃/min 1.9 Pa 0.09 0.0 Pa 0.0 Pa

4 813885 0 CFM 12"x6" 0.0 䴀턃/min 0.0 Pa 0.32 0.0 Pa 0.0 Pa

Page 67: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

Fiᜀꘂng and Accessory Loss Coefficient Summary by Sec㐀鸂ons

Sec㐀鸂on Element ID Loss Method ASHRAE Table Loss Coefficient Pressure Loss TotalPressure Loss

1 819654 Coefficient fromASHRAE Table SR4‐3 0 0.0 Pa 0.0 Pa

2819653 Coefficient from

ASHRAE Table SR3‐1 1.21 9.2 Pa

819654 Coefficient fromASHRAE Table SR4‐3 0.005503 0.0 Pa

9.2 Pa

3 813893 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

4 813887 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

URC‐03 OutdoorSystem Informa㐀鸂onSystem Classifica㐀鸂on Supply AirSystem Type Outdoor AirSystem Name URC‐03 OutdoorAbbrevia㐀鸂on

Total Pressure Loss Calcula㐀鸂ons by Sec㐀鸂ons

Sec㐀鸂on Element Flow Size Velocity VelocityPressure Length Loss

Coefficient Fric㐀鸂onTotalPressureLoss

Sec㐀鸂onPressure Loss

1Fiᜀꘂngs 320 CFM ‐ 605.6

䴀턃/min 5.7 Pa ‐ 0 ‐ 0.0 Pa

Equipment 320 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa0.0 Pa

2Duct 320 CFM 12"x6" 640.0

䴀턃/min ‐ 5.06 ‐ 0.09 in‐wg/100䴀턃 3.7 Pa

Fiᜀꘂngs 320 CFM ‐ 640.0䴀턃/min 6.4 Pa ‐ 2.425503 ‐ 15.4 Pa

19.1 Pa

3

Duct 320 CFM 12"x12" 320.0䴀턃/min ‐ 0.09 ‐ 0.02 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 320 CFM ‐ 320.0䴀턃/min 1.6 Pa ‐ 0 ‐ 0.0 Pa

Air Terminal 320 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa

0.0 Pa

4Duct 0 CFM 12"x6" 0.0 䴀턃/min ‐ 0.32 ‐ 0.00 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 0 CFM ‐ 0.0 䴀턃/min 0.0 Pa ‐ 0 ‐ 0.0 Pa0.0 Pa

Cri㐀鸂cal Path : 1‐2‐3 ; Total Pressure Loss : 19.1 Pa

Detail Informa㐀鸂on of Straight Segment by Sec㐀鸂ons

Sec㐀鸂on Element ID Flow Size Velocity VelocityPressure Length Pressure Loss Total

Pressure Loss

2851809 320 CFM 12"x6" 640.0 䴀턃/min 6.4 Pa 2.64 1.9 Pa851810 320 CFM 12"x6" 640.0 䴀턃/min 6.4 Pa 2.01 1.5 Pa851812 320 CFM 12"x6" 640.0 䴀턃/min 6.4 Pa 0.41 0.3 Pa

3.7 Pa

3 851816 320 CFM 12"x12" 320.0 䴀턃/min 1.6 Pa 0.09 0.0 Pa 0.0 Pa

4 851809 0 CFM 12"x6" 0.0 䴀턃/min 0.0 Pa 0.32 0.0 Pa 0.0 Pa

Fiᜀꘂng and Accessory Loss Coefficient Summary by Sec㐀鸂ons

Sec㐀鸂on Element ID Loss Method ASHRAE Table Loss Coefficient Pressure Loss TotalPressure Loss

1 851814 Coefficient fromASHRAE Table SR4‐3 0 0.0 Pa 0.0 Pa

2

851811 Coefficient fromASHRAE Table SR3‐1 1.21 7.7 Pa

851813 Coefficient fromASHRAE Table SR3‐1 1.21 7.7 Pa

851814 Coefficient fromASHRAE Table SR4‐3 0.005503 0.0 Pa

15.4 Pa

Page 68: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

3 851817 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

4 851815 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

URC‐04 OutdoorSystem Informa㐀鸂onSystem Classifica㐀鸂on Supply AirSystem Type Outdoor AirSystem Name URC‐04 OutdoorAbbrevia㐀鸂on

Total Pressure Loss Calcula㐀鸂ons by Sec㐀鸂ons

Sec㐀鸂on Element Flow Size Velocity VelocityPressure Length Loss

Coefficient Fric㐀鸂onTotalPressureLoss

Sec㐀鸂onPressure Loss

1Fiᜀꘂngs 320 CFM ‐ 605.6

䴀턃/min 5.7 Pa ‐ 0 ‐ 0.0 Pa

Equipment 320 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa0.0 Pa

2Duct 320 CFM 12"x6" 640.0

䴀턃/min ‐ 5.06 ‐ 0.09 in‐wg/100䴀턃 3.7 Pa

Fiᜀꘂngs 320 CFM ‐ 640.0䴀턃/min 6.4 Pa ‐ 2.425503 ‐ 15.4 Pa

19.1 Pa

3

Duct 320 CFM 12"x12" 320.0䴀턃/min ‐ 0.09 ‐ 0.02 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 320 CFM ‐ 320.0䴀턃/min 1.6 Pa ‐ 0 ‐ 0.0 Pa

Air Terminal 320 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa

0.0 Pa

4Duct 0 CFM 12"x6" 0.0 䴀턃/min ‐ 0.32 ‐ 0.00 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 0 CFM ‐ 0.0 䴀턃/min 0.0 Pa ‐ 0 ‐ 0.0 Pa0.0 Pa

Cri㐀鸂cal Path : 1‐2‐3 ; Total Pressure Loss : 19.1 Pa

Detail Informa㐀鸂on of Straight Segment by Sec㐀鸂ons

Sec㐀鸂on Element ID Flow Size Velocity VelocityPressure Length Pressure Loss Total

Pressure Loss

2851827 320 CFM 12"x6" 640.0 䴀턃/min 6.4 Pa 2.64 1.9 Pa851828 320 CFM 12"x6" 640.0 䴀턃/min 6.4 Pa 2.01 1.5 Pa851830 320 CFM 12"x6" 640.0 䴀턃/min 6.4 Pa 0.41 0.3 Pa

3.7 Pa

3 851832 320 CFM 12"x12" 320.0 䴀턃/min 1.6 Pa 0.09 0.0 Pa 0.0 Pa

4 851827 0 CFM 12"x6" 0.0 䴀턃/min 0.0 Pa 0.32 0.0 Pa 0.0 Pa

Fiᜀꘂng and Accessory Loss Coefficient Summary by Sec㐀鸂ons

Sec㐀鸂on Element ID Loss Method ASHRAE Table Loss Coefficient Pressure Loss TotalPressure Loss

1 851945 Coefficient fromASHRAE Table SR4‐3 0 0.0 Pa 0.0 Pa

2

851829 Coefficient fromASHRAE Table SR3‐1 1.21 7.7 Pa

851944 Coefficient fromASHRAE Table SR3‐1 1.21 7.7 Pa

851945 Coefficient fromASHRAE Table SR4‐3 0.005503 0.0 Pa

15.4 Pa

3 851833 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

4 851831 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

URC‐05 OutdoorSystem Informa㐀鸂onSystem Classifica㐀鸂on Supply AirSystem Type Outdoor Air

Page 69: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

System Name URC‐05 OutdoorAbbrevia㐀鸂on

Total Pressure Loss Calcula㐀鸂ons by Sec㐀鸂ons

Sec㐀鸂on Element Flow Size Velocity VelocityPressure Length Loss

Coefficient Fric㐀鸂onTotalPressureLoss

Sec㐀鸂onPressure Loss

1Fiᜀꘂngs 320 CFM ‐ 605.6

䴀턃/min 5.7 Pa ‐ 0 ‐ 0.0 Pa

Equipment 320 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa0.0 Pa

2Duct 320 CFM 12"x6" 640.0

䴀턃/min ‐ 5.06 ‐ 0.09 in‐wg/100䴀턃 3.7 Pa

Fiᜀꘂngs 320 CFM ‐ 640.0䴀턃/min 6.4 Pa ‐ 2.425503 ‐ 15.4 Pa

19.1 Pa

3

Duct 320 CFM 12"x12" 320.0䴀턃/min ‐ 0.09 ‐ 0.02 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 320 CFM ‐ 320.0䴀턃/min 1.6 Pa ‐ 0 ‐ 0.0 Pa

Air Terminal 320 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa

0.0 Pa

4Duct 0 CFM 12"x6" 0.0 䴀턃/min ‐ 0.32 ‐ 0.00 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 0 CFM ‐ 0.0 䴀턃/min 0.0 Pa ‐ 0 ‐ 0.0 Pa0.0 Pa

Cri㐀鸂cal Path : 1‐2‐3 ; Total Pressure Loss : 19.1 Pa

Detail Informa㐀鸂on of Straight Segment by Sec㐀鸂ons

Sec㐀鸂on Element ID Flow Size Velocity VelocityPressure Length Pressure Loss Total

Pressure Loss

2851842 320 CFM 12"x6" 640.0 䴀턃/min 6.4 Pa 2.64 1.9 Pa851843 320 CFM 12"x6" 640.0 䴀턃/min 6.4 Pa 2.01 1.5 Pa851845 320 CFM 12"x6" 640.0 䴀턃/min 6.4 Pa 0.41 0.3 Pa

3.7 Pa

3 851849 320 CFM 12"x12" 320.0 䴀턃/min 1.6 Pa 0.09 0.0 Pa 0.0 Pa

4 851842 0 CFM 12"x6" 0.0 䴀턃/min 0.0 Pa 0.32 0.0 Pa 0.0 Pa

Fiᜀꘂng and Accessory Loss Coefficient Summary by Sec㐀鸂ons

Sec㐀鸂on Element ID Loss Method ASHRAE Table Loss Coefficient Pressure Loss TotalPressure Loss

1 851847 Coefficient fromASHRAE Table SR4‐3 0 0.0 Pa 0.0 Pa

2

851844 Coefficient fromASHRAE Table SR3‐1 1.21 7.7 Pa

851846 Coefficient fromASHRAE Table SR3‐1 1.21 7.7 Pa

851847 Coefficient fromASHRAE Table SR4‐3 0.005503 0.0 Pa

15.4 Pa

3 851850 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

4 851848 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

URC‐06 OutdoorSystem Informa㐀鸂onSystem Classifica㐀鸂on Supply AirSystem Type Outdoor AirSystem Name URC‐06 OutdoorAbbrevia㐀鸂on

Total Pressure Loss Calcula㐀鸂ons by Sec㐀鸂ons

Sec㐀鸂on Element Flow Size Velocity VelocityPressure Length Loss

Coefficient Fric㐀鸂onTotalPressureLoss

Sec㐀鸂onPressure Loss

1Fiᜀꘂngs 320 CFM ‐ 605.6

䴀턃/min 5.7 Pa ‐ 0 ‐ 0.0 Pa

320 CFM 0.0 Pa

Page 70: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

Equipment ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa

2Duct 320 CFM 12"x6" 640.0

䴀턃/min ‐ 5.06 ‐ 0.09 in‐wg/100䴀턃 3.7 Pa

Fiᜀꘂngs 320 CFM ‐ 640.0䴀턃/min 6.4 Pa ‐ 2.425503 ‐ 15.4 Pa

19.1 Pa

3

Duct 320 CFM 12"x12" 320.0䴀턃/min ‐ 0.09 ‐ 0.02 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 320 CFM ‐ 320.0䴀턃/min 1.6 Pa ‐ 0 ‐ 0.0 Pa

Air Terminal 320 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa

0.0 Pa

4Duct 0 CFM 12"x6" 0.0 䴀턃/min ‐ 0.32 ‐ 0.00 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 0 CFM ‐ 0.0 䴀턃/min 0.0 Pa ‐ 0 ‐ 0.0 Pa0.0 Pa

Cri㐀鸂cal Path : 1‐2‐3 ; Total Pressure Loss : 19.1 Pa

Detail Informa㐀鸂on of Straight Segment by Sec㐀鸂ons

Sec㐀鸂on Element ID Flow Size Velocity VelocityPressure Length Pressure Loss Total

Pressure Loss

2851861 320 CFM 12"x6" 640.0 䴀턃/min 6.4 Pa 2.64 1.9 Pa851862 320 CFM 12"x6" 640.0 䴀턃/min 6.4 Pa 2.01 1.5 Pa851864 320 CFM 12"x6" 640.0 䴀턃/min 6.4 Pa 0.41 0.3 Pa

3.7 Pa

3 851868 320 CFM 12"x12" 320.0 䴀턃/min 1.6 Pa 0.09 0.0 Pa 0.0 Pa

4 851861 0 CFM 12"x6" 0.0 䴀턃/min 0.0 Pa 0.32 0.0 Pa 0.0 Pa

Fiᜀꘂng and Accessory Loss Coefficient Summary by Sec㐀鸂ons

Sec㐀鸂on Element ID Loss Method ASHRAE Table Loss Coefficient Pressure Loss TotalPressure Loss

1 851866 Coefficient fromASHRAE Table SR4‐3 0 0.0 Pa 0.0 Pa

2

851863 Coefficient fromASHRAE Table SR3‐1 1.21 7.7 Pa

851865 Coefficient fromASHRAE Table SR3‐1 1.21 7.7 Pa

851866 Coefficient fromASHRAE Table SR4‐3 0.005503 0.0 Pa

15.4 Pa

3 851869 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

4 851867 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

URC‐07 OutdoorSystem Informa㐀鸂onSystem Classifica㐀鸂on Supply AirSystem Type Outdoor AirSystem Name URC‐07 OutdoorAbbrevia㐀鸂on

Total Pressure Loss Calcula㐀鸂ons by Sec㐀鸂ons

Sec㐀鸂on Element Flow Size Velocity VelocityPressure Length Loss

Coefficient Fric㐀鸂onTotalPressureLoss

Sec㐀鸂onPressure Loss

1Fiᜀꘂngs 650 CFM ‐ 1230.2

䴀턃/min 23.5 Pa ‐ 0 ‐ 0.0 Pa

Equipment 650 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa0.0 Pa

2Duct 650 CFM 16"x6" 975.0

䴀턃/min ‐ 2.75 ‐ 0.17 in‐wg/100䴀턃 3.9 Pa

Fiᜀꘂngs 650 CFM ‐ 975.0䴀턃/min 14.8 Pa ‐ 2.755825 ‐ 40.7 Pa

44.5 Pa

3

Duct 650 CFM 15"x15" 416.0䴀턃/min ‐ 0.09 ‐ 0.02 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 650 CFM ‐ 416.0䴀턃/min 2.7 Pa ‐ 0 ‐ 0.0 Pa 0.0 Pa

Page 71: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

Air Terminal 650 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa

4Duct 0 CFM 16"x6" 0.0 䴀턃/min ‐ 0.35 ‐ 0.00 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 0 CFM ‐ 0.0 䴀턃/min 0.0 Pa ‐ 0 ‐ 0.0 Pa0.0 Pa

Cri㐀鸂cal Path : 1‐2‐3 ; Total Pressure Loss : 44.5 Pa

Detail Informa㐀鸂on of Straight Segment by Sec㐀鸂ons

Sec㐀鸂on Element ID Flow Size Velocity VelocityPressure Length Pressure Loss Total

Pressure Loss

2859991 650 CFM 16"x6" 975.0 䴀턃/min 14.8 Pa 2.48 3.5 Pa859992 650 CFM 16"x6" 975.0 䴀턃/min 14.8 Pa 0.24 0.3 Pa859994 650 CFM 16"x6" 975.0 䴀턃/min 14.8 Pa 0.03 0.0 Pa

3.9 Pa

3 859998 650 CFM 15"x15" 416.0 䴀턃/min 2.7 Pa 0.09 0.0 Pa 0.0 Pa

4 859991 0 CFM 16"x6" 0.0 䴀턃/min 0.0 Pa 0.35 0.0 Pa 0.0 Pa

Fiᜀꘂng and Accessory Loss Coefficient Summary by Sec㐀鸂ons

Sec㐀鸂on Element ID Loss Method ASHRAE Table Loss Coefficient Pressure Loss TotalPressure Loss

1 859996 Coefficient fromASHRAE Table SR4‐3 0 0.0 Pa 0.0 Pa

2

859993 Coefficient fromASHRAE Table SR3‐1 1.225 18.1 Pa

859995 Coefficient fromASHRAE Table SR3‐1 1.225 18.1 Pa

859996 Coefficient fromASHRAE Table SR4‐3 0.305825 4.5 Pa

40.7 Pa

3 859999 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

4 859997 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

URC‐08 OutdoorSystem Informa㐀鸂onSystem Classifica㐀鸂on Supply AirSystem Type Outdoor AirSystem Name URC‐08 OutdoorAbbrevia㐀鸂on

Total Pressure Loss Calcula㐀鸂ons by Sec㐀鸂ons

Sec㐀鸂on Element Flow Size Velocity VelocityPressure Length Loss

Coefficient Fric㐀鸂onTotalPressureLoss

Sec㐀鸂onPressure Loss

1Fiᜀꘂngs 650 CFM ‐ 1230.2

䴀턃/min 23.5 Pa ‐ 0 ‐ 0.0 Pa

Equipment 650 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa0.0 Pa

2Duct 650 CFM 16"x6" 975.0

䴀턃/min ‐ 2.75 ‐ 0.17 in‐wg/100䴀턃 3.9 Pa

Fiᜀꘂngs 650 CFM ‐ 975.0䴀턃/min 14.8 Pa ‐ 2.755825 ‐ 40.7 Pa

44.5 Pa

3

Duct 650 CFM 15"x15" 416.0䴀턃/min ‐ 0.09 ‐ 0.02 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 650 CFM ‐ 416.0䴀턃/min 2.7 Pa ‐ 0 ‐ 0.0 Pa

Air Terminal 650 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa

0.0 Pa

4Duct 0 CFM 16"x6" 0.0 䴀턃/min ‐ 0.35 ‐ 0.00 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 0 CFM ‐ 0.0 䴀턃/min 0.0 Pa ‐ 0 ‐ 0.0 Pa0.0 Pa

Cri㐀鸂cal Path : 1‐2‐3 ; Total Pressure Loss : 44.5 Pa

Detail Informa㐀鸂on of Straight Segment by Sec㐀鸂ons

Sec㐀鸂on Element ID Flow Size Velocity VelocityPressure Length Pressure Loss Total

Pressure Loss

Page 72: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

2860010 650 CFM 16"x6" 975.0 䴀턃/min 14.8 Pa 2.48 3.5 Pa860011 650 CFM 16"x6" 975.0 䴀턃/min 14.8 Pa 0.24 0.3 Pa860013 650 CFM 16"x6" 975.0 䴀턃/min 14.8 Pa 0.03 0.0 Pa

3.9 Pa

3 860017 650 CFM 15"x15" 416.0 䴀턃/min 2.7 Pa 0.09 0.0 Pa 0.0 Pa

4 860010 0 CFM 16"x6" 0.0 䴀턃/min 0.0 Pa 0.35 0.0 Pa 0.0 Pa

Fiᜀꘂng and Accessory Loss Coefficient Summary by Sec㐀鸂ons

Sec㐀鸂on Element ID Loss Method ASHRAE Table Loss Coefficient Pressure Loss TotalPressure Loss

1 860015 Coefficient fromASHRAE Table SR4‐3 0 0.0 Pa 0.0 Pa

2

860012 Coefficient fromASHRAE Table SR3‐1 1.225 18.1 Pa

860014 Coefficient fromASHRAE Table SR3‐1 1.225 18.1 Pa

860015 Coefficient fromASHRAE Table SR4‐3 0.305825 4.5 Pa

40.7 Pa

3 860018 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

4 860016 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

URC‐09 OutdoorSystem Informa㐀鸂onSystem Classifica㐀鸂on Supply AirSystem Type Outdoor AirSystem Name URC‐09 OutdoorAbbrevia㐀鸂on

Total Pressure Loss Calcula㐀鸂ons by Sec㐀鸂ons

Sec㐀鸂on Element Flow Size Velocity VelocityPressure Length Loss

Coefficient Fric㐀鸂onTotalPressureLoss

Sec㐀鸂onPressure Loss

1Fiᜀꘂngs 650 CFM ‐ 1230.2

䴀턃/min 23.5 Pa ‐ 0 ‐ 0.0 Pa

Equipment 650 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa0.0 Pa

2Duct 650 CFM 16"x6" 975.0

䴀턃/min ‐ 2.75 ‐ 0.17 in‐wg/100䴀턃 3.9 Pa

Fiᜀꘂngs 650 CFM ‐ 975.0䴀턃/min 14.8 Pa ‐ 2.755825 ‐ 40.7 Pa

44.5 Pa

3

Duct 650 CFM 15"x15" 416.0䴀턃/min ‐ 0.09 ‐ 0.02 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 650 CFM ‐ 416.0䴀턃/min 2.7 Pa ‐ 0 ‐ 0.0 Pa

Air Terminal 650 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa

0.0 Pa

4Duct 0 CFM 16"x6" 0.0 䴀턃/min ‐ 0.35 ‐ 0.00 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 0 CFM ‐ 0.0 䴀턃/min 0.0 Pa ‐ 0 ‐ 0.0 Pa0.0 Pa

Cri㐀鸂cal Path : 1‐2‐3 ; Total Pressure Loss : 44.5 Pa

Detail Informa㐀鸂on of Straight Segment by Sec㐀鸂ons

Sec㐀鸂on Element ID Flow Size Velocity VelocityPressure Length Pressure Loss Total

Pressure Loss

2860029 650 CFM 16"x6" 975.0 䴀턃/min 14.8 Pa 2.48 3.5 Pa860030 650 CFM 16"x6" 975.0 䴀턃/min 14.8 Pa 0.24 0.3 Pa860032 650 CFM 16"x6" 975.0 䴀턃/min 14.8 Pa 0.03 0.0 Pa

3.9 Pa

3 860036 650 CFM 15"x15" 416.0 䴀턃/min 2.7 Pa 0.09 0.0 Pa 0.0 Pa

4 860029 0 CFM 16"x6" 0.0 䴀턃/min 0.0 Pa 0.35 0.0 Pa 0.0 Pa

Fiᜀꘂng and Accessory Loss Coefficient Summary by Sec㐀鸂ons

Sec㐀鸂on Element ID Loss Method ASHRAE Table Loss Coefficient Pressure Loss TotalPressure Loss

Page 73: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

1 860034 Coefficient fromASHRAE Table

SR4‐3 0 0.0 Pa 0.0 Pa

2

860031 Coefficient fromASHRAE Table SR3‐1 1.225 18.1 Pa

860033 Coefficient fromASHRAE Table SR3‐1 1.225 18.1 Pa

860034 Coefficient fromASHRAE Table SR4‐3 0.305825 4.5 Pa

40.7 Pa

3 860037 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

4 860035 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

URC‐10 OutdoorSystem Informa㐀鸂onSystem Classifica㐀鸂on Supply AirSystem Type Outdoor AirSystem Name URC‐10 OutdoorAbbrevia㐀鸂on

Total Pressure Loss Calcula㐀鸂ons by Sec㐀鸂ons

Sec㐀鸂on Element Flow Size Velocity VelocityPressure Length Loss

Coefficient Fric㐀鸂onTotalPressureLoss

Sec㐀鸂onPressure Loss

1Fiᜀꘂngs 500 CFM ‐ 946.3

䴀턃/min 13.9 Pa ‐ 0 ‐ 0.0 Pa

Equipment 500 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa0.0 Pa

2Duct 500 CFM 16"x6" 750.0

䴀턃/min ‐ 2.75 ‐ 0.11 in‐wg/100䴀턃 2.4 Pa

Fiᜀꘂngs 500 CFM ‐ 750.0䴀턃/min 8.7 Pa ‐ 2.755825 ‐ 24.1 Pa

26.4 Pa

3

Duct 500 CFM 15"x15" 320.0䴀턃/min ‐ 0.09 ‐ 0.01 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 500 CFM ‐ 320.0䴀턃/min 1.6 Pa ‐ 0 ‐ 0.0 Pa

Air Terminal 500 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa

0.0 Pa

4Duct 0 CFM 16"x6" 0.0 䴀턃/min ‐ 0.35 ‐ 0.00 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 0 CFM ‐ 0.0 䴀턃/min 0.0 Pa ‐ 0 ‐ 0.0 Pa0.0 Pa

Cri㐀鸂cal Path : 1‐2‐3 ; Total Pressure Loss : 26.5 Pa

Detail Informa㐀鸂on of Straight Segment by Sec㐀鸂ons

Sec㐀鸂on Element ID Flow Size Velocity VelocityPressure Length Pressure Loss Total

Pressure Loss

2860048 500 CFM 16"x6" 750.0 䴀턃/min 8.7 Pa 2.48 2.2 Pa860049 500 CFM 16"x6" 750.0 䴀턃/min 8.7 Pa 0.24 0.2 Pa860051 500 CFM 16"x6" 750.0 䴀턃/min 8.7 Pa 0.03 0.0 Pa

2.4 Pa

3 860055 500 CFM 15"x15" 320.0 䴀턃/min 1.6 Pa 0.09 0.0 Pa 0.0 Pa

4 860048 0 CFM 16"x6" 0.0 䴀턃/min 0.0 Pa 0.35 0.0 Pa 0.0 Pa

Fiᜀꘂng and Accessory Loss Coefficient Summary by Sec㐀鸂ons

Sec㐀鸂on Element ID Loss Method ASHRAE Table Loss Coefficient Pressure Loss TotalPressure Loss

1 860053 Coefficient fromASHRAE Table SR4‐3 0 0.0 Pa 0.0 Pa

2

860050 Coefficient fromASHRAE Table SR3‐1 1.225 10.7 Pa

860052 Coefficient fromASHRAE Table SR3‐1 1.225 10.7 Pa

860053 Coefficient fromASHRAE Table SR4‐3 0.305825 2.7 Pa

24.1 Pa

3 860056 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

Page 74: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

4 860054 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

URC‐11 OutdoorSystem Informa㐀鸂onSystem Classifica㐀鸂on Supply AirSystem Type Outdoor AirSystem Name URC‐11 OutdoorAbbrevia㐀鸂on

Total Pressure Loss Calcula㐀鸂ons by Sec㐀鸂ons

Sec㐀鸂on Element Flow Size Velocity VelocityPressure Length Loss

Coefficient Fric㐀鸂onTotalPressureLoss

Sec㐀鸂onPressure Loss

1Duct 100 CFM 10"x4" 360.0

䴀턃/min ‐ 1.81 ‐ 0.05 in‐wg/100䴀턃 0.7 Pa

Fiᜀꘂngs 100 CFM ‐ 360.0䴀턃/min 2.0 Pa ‐ 0 ‐ 0.0 Pa

0.7 Pa

2Duct 50 CFM 10"x4" 180.0

䴀턃/min ‐ 2.74 ‐ 0.01 in‐wg/100䴀턃 0.3 Pa

Fiᜀꘂngs 50 CFM ‐ 180.0䴀턃/min 0.5 Pa ‐ 1.222 ‐ 0.6 Pa

0.9 Pa

3Duct 0 CFM 10"x4" 0.0 䴀턃/min ‐ 0.28 ‐ 0.00 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 0 CFM ‐ 0.0 䴀턃/min 0.0 Pa ‐ 0 ‐ 0.0 Pa0.0 Pa

4Duct 0 CFM 10"x4" 0.0 䴀턃/min ‐ 0.24 ‐ 0.00 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 0 CFM ‐ 0.0 䴀턃/min 0.0 Pa ‐ 0 ‐ 0.0 Pa0.0 Pa

5Duct 150 CFM 10"x4" 540.0

䴀턃/min ‐ 3.42 ‐ 0.10 in‐wg/100䴀턃 2.8 Pa

Fiᜀꘂngs 150 CFM ‐ 540.0䴀턃/min 4.5 Pa ‐ 0 ‐ 0.0 Pa

2.8 Pa

6Duct 50 CFM 9"x9" 88.9 䴀턃/min ‐ 0.14 ‐ 0.00 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 50 CFM ‐ 88.9 䴀턃/min 0.1 Pa ‐ 0 ‐ 0.0 PaAir Terminal 50 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa

0.0 Pa

7Duct 0 CFM 10"x4" 0.0 䴀턃/min ‐ 0.23 ‐ 0.00 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 0 CFM ‐ 0.0 䴀턃/min 0.0 Pa ‐ 0 ‐ 0.0 Pa0.0 Pa

8Duct 50 CFM 9"x9" 88.9 䴀턃/min ‐ 0.14 ‐ 0.00 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 50 CFM ‐ 88.9 䴀턃/min 0.1 Pa ‐ 0 ‐ 0.0 PaAir Terminal 50 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa

0.0 Pa

9Duct 50 CFM 10"x4" 180.0

䴀턃/min ‐ 1.03 ‐ 0.01 in‐wg/100䴀턃 0.1 Pa

Fiᜀꘂngs 50 CFM ‐ 180.0䴀턃/min 0.5 Pa ‐ 0 ‐ 0.0 Pa

0.1 Pa

10Duct 50 CFM 9"x9" 88.9 䴀턃/min ‐ 0.14 ‐ 0.00 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 50 CFM ‐ 88.9 䴀턃/min 0.1 Pa ‐ 0 ‐ 0.0 PaAir Terminal 50 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa

0.0 Pa

11Duct 100 CFM 10"x4" 360.0

䴀턃/min ‐ 1.04 ‐ 0.05 in‐wg/100䴀턃 0.4 Pa

Fiᜀꘂngs 100 CFM ‐ 360.0䴀턃/min 2.0 Pa ‐ 0 ‐ 0.0 Pa

0.4 Pa

12Duct 350 CFM 10"x6" 840.0

䴀턃/min ‐ 2.11 ‐ 0.16 in‐wg/100䴀턃 2.7 Pa

Fiᜀꘂngs 350 CFM ‐ 840.0䴀턃/min 10.9 Pa ‐ 1.222723 ‐ 13.4 Pa

16.1 Pa

13Fiᜀꘂngs 350 CFM ‐ 662.4

䴀턃/min 6.8 Pa ‐ 0 ‐ 0.0 Pa

Equipment 350 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa0.0 Pa

Page 75: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

15 Duct 0 CFM 10"x4" 0.0 䴀턃/min ‐ 0.28 ‐ 0.00 in‐wg/100䴀턃

0.0 Pa

Fiᜀꘂngs 0 CFM ‐ 0.0 䴀턃/min 0.0 Pa ‐ 0 ‐ 0.0 Pa

0.0 Pa

16Duct 50 CFM 10"x4" 180.0

䴀턃/min ‐ 2.76 ‐ 0.01 in‐wg/100䴀턃 0.3 Pa

Fiᜀꘂngs 50 CFM ‐ 180.0䴀턃/min 0.5 Pa ‐ 1.222 ‐ 0.6 Pa

0.9 Pa

17Duct 200 CFM 10"x4" 720.0

䴀턃/min ‐ 1.21 ‐ 0.17 in‐wg/100䴀턃 1.7 Pa

Fiᜀꘂngs 200 CFM ‐ 720.0䴀턃/min 8.0 Pa ‐ 0 ‐ 0.0 Pa

1.7 Pa

18Duct 150 CFM 10"x6" 360.0

䴀턃/min ‐ 0.41 ‐ 0.03 in‐wg/100䴀턃 0.1 Pa

Fiᜀꘂngs 150 CFM ‐ 360.0䴀턃/min 2.0 Pa ‐ 0 ‐ 0.0 Pa

0.1 Pa

19Duct 50 CFM 10"x4" 180.0

䴀턃/min ‐ 1.04 ‐ 0.01 in‐wg/100䴀턃 0.1 Pa

Fiᜀꘂngs 50 CFM ‐ 180.0䴀턃/min 0.5 Pa ‐ 0 ‐ 0.0 Pa

0.1 Pa

20Duct 0 CFM 10"x4" 0.0 䴀턃/min ‐ 0.24 ‐ 0.00 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 0 CFM ‐ 0.0 䴀턃/min 0.0 Pa ‐ 0 ‐ 0.0 Pa0.0 Pa

21Duct 50 CFM 9"x9" 88.9 䴀턃/min ‐ 0.14 ‐ 0.00 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 50 CFM ‐ 88.9 䴀턃/min 0.1 Pa ‐ 0 ‐ 0.0 PaAir Terminal 50 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa

0.0 Pa

22Duct 0 CFM 10"x4" 0.0 䴀턃/min ‐ 0.24 ‐ 0.00 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 0 CFM ‐ 0.0 䴀턃/min 0.0 Pa ‐ 0 ‐ 0.0 Pa0.0 Pa

23

Duct 100 CFM 9"x9" 177.8䴀턃/min ‐ 0.14 ‐ 0.01 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 100 CFM ‐ 177.8䴀턃/min 0.5 Pa ‐ 0 ‐ 0.0 Pa

Air Terminal 100 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa

0.0 Pa

24Duct 50 CFM 9"x9" 88.9 䴀턃/min ‐ 0.14 ‐ 0.00 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 50 CFM ‐ 88.9 䴀턃/min 0.1 Pa ‐ 0 ‐ 0.0 PaAir Terminal 50 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa

0.0 Pa

25 Duct 50 CFM 10"x4" 180.0䴀턃/min ‐ 1.32 ‐ 0.01 in‐

wg/100䴀턃 0.2 Pa 0.2 Pa

26 Duct 100 CFM 10"x4" 360.0䴀턃/min ‐ 0.59 ‐ 0.05 in‐

wg/100䴀턃 0.2 Pa 0.2 Pa

Cri㐀鸂cal Path : 13‐12‐18‐5‐1‐2‐6 ; Total Pressure Loss : 20.7 Pa

Detail Informa㐀鸂on of Straight Segment by Sec㐀鸂ons

Sec㐀鸂on Element ID Flow Size Velocity VelocityPressure Length Pressure Loss Total

Pressure Loss

1 883690 100 CFM 10"x4" 360.0 䴀턃/min 2.0 Pa 1.81 0.7 Pa 0.7 Pa

2883689 50 CFM 10"x4" 180.0 䴀턃/min 0.5 Pa 1.01 0.1 Pa883690 50 CFM 10"x4" 180.0 䴀턃/min 0.5 Pa 1.73 0.2 Pa

0.3 Pa

3 883691 0 CFM 10"x4" 0.0 䴀턃/min 0.0 Pa 0.28 0.0 Pa 0.0 Pa

4 883693 0 CFM 10"x4" 0.0 䴀턃/min 0.0 Pa 0.24 0.0 Pa 0.0 Pa

5 883693 150 CFM 10"x4" 540.0 䴀턃/min 4.5 Pa 3.42 2.8 Pa 2.8 Pa

6 883699 50 CFM 9"x9" 88.9 䴀턃/min 0.1 Pa 0.14 0.0 Pa 0.0 Pa

7 883689 0 CFM 10"x4" 0.0 䴀턃/min 0.0 Pa 0.23 0.0 Pa 0.0 Pa

8 883701 50 CFM 9"x9" 88.9 䴀턃/min 0.1 Pa 0.14 0.0 Pa 0.0 Pa

9 883691 50 CFM 10"x4" 180.0 䴀턃/min 0.5 Pa 1.03 0.1 Pa 0.1 Pa

10 883703 50 CFM 9"x9" 88.9 䴀턃/min 0.1 Pa 0.14 0.0 Pa 0.0 Pa

11 883709 100 CFM 10"x4" 360.0 䴀턃/min 2.0 Pa 1.04 0.4 Pa 0.4 Pa

12883720 350 CFM 10"x6" 840.0 䴀턃/min 10.9 Pa 0.76 1.0 Pa

2.7 Pa

Page 76: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

883721 350 CFM 10"x6" 840.0 䴀턃/min 10.9 Pa 1.35 1.7 Pa

15 883705 0 CFM 10"x4" 0.0 䴀턃/min 0.0 Pa 0.28 0.0 Pa 0.0 Pa

16883705 50 CFM 10"x4" 180.0 䴀턃/min 0.5 Pa 1.02 0.1 Pa883706 50 CFM 10"x4" 180.0 䴀턃/min 0.5 Pa 1.74 0.2 Pa

0.3 Pa

17 883706 200 CFM 10"x4" 720.0 䴀턃/min 8.0 Pa 1.21 1.7 Pa 1.7 Pa

18 883720 150 CFM 10"x6" 360.0 䴀턃/min 2.0 Pa 0.41 0.1 Pa 0.1 Pa

19 883707 50 CFM 10"x4" 180.0 䴀턃/min 0.5 Pa 1.04 0.1 Pa 0.1 Pa

20 883707 0 CFM 10"x4" 0.0 䴀턃/min 0.0 Pa 0.24 0.0 Pa 0.0 Pa

21 883716 50 CFM 9"x9" 88.9 䴀턃/min 0.1 Pa 0.14 0.0 Pa 0.0 Pa

22 883709 0 CFM 10"x4" 0.0 䴀턃/min 0.0 Pa 0.24 0.0 Pa 0.0 Pa

23 883718 100 CFM 9"x9" 177.8 䴀턃/min 0.5 Pa 0.14 0.0 Pa 0.0 Pa

24 883714 50 CFM 9"x9" 88.9 䴀턃/min 0.1 Pa 0.14 0.0 Pa 0.0 Pa

25 883693 50 CFM 10"x4" 180.0 䴀턃/min 0.5 Pa 1.32 0.2 Pa 0.2 Pa

26 883706 100 CFM 10"x4" 360.0 䴀턃/min 2.0 Pa 0.59 0.2 Pa 0.2 Pa

Fiᜀꘂng and Accessory Loss Coefficient Summary by Sec㐀鸂ons

Sec㐀鸂on Element ID Loss Method ASHRAE Table Loss Coefficient Pressure Loss TotalPressure Loss

1 883694 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

2 883695 Coefficient fromASHRAE Table SR3‐1 1.222 0.6 Pa 0.6 Pa

3 883697 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

4 883698 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

5 883724 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

6 883700 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

7 883696 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

8 883702 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

9 883692 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

10 883704 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

11 883710 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

12883722 Coefficient from

ASHRAE Table SR4‐3 0.024723 0.3 Pa

883723 Coefficient fromASHRAE Table SR3‐1 1.198 13.1 Pa

13.4 Pa

13 883722 Coefficient fromASHRAE Table SR4‐3 0 0.0 Pa 0.0 Pa

15 883713 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

16 883726 Coefficient fromASHRAE Table SR3‐1 1.222 0.6 Pa 0.6 Pa

17 883725 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

18 883724 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

19 883708 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

20 883711 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

21 883717 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

Page 77: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

22 883712 Coefficient fromASHRAE Table

‐ 0 0.0 Pa 0.0 Pa

23 883719 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

24 883715 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

URC‐12 OurdoorSystem Informa㐀鸂onSystem Classifica㐀鸂on Supply AirSystem Type Outdoor AirSystem Name URC‐12 OurdoorAbbrevia㐀鸂on

Total Pressure Loss Calcula㐀鸂ons by Sec㐀鸂ons

Sec㐀鸂on Element Flow Size Velocity VelocityPressure Length Loss

Coefficient Fric㐀鸂onTotalPressureLoss

Sec㐀鸂onPressure Loss

1Fiᜀꘂngs 500 CFM ‐ 946.3

䴀턃/min 13.9 Pa ‐ 0 ‐ 0.0 Pa

Equipment 500 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa0.0 Pa

2Duct 500 CFM 10"x8" 900.0

䴀턃/min ‐ 1.48 ‐ 0.14 in‐wg/100䴀턃 1.8 Pa

Fiᜀꘂngs 500 CFM ‐ 900.0䴀턃/min 12.6 Pa ‐ 1.226718 ‐ 15.4 Pa

17.2 Pa

3Duct 0 CFM 10"x4" 0.0 䴀턃/min ‐ 0.35 ‐ 0.00 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 0 CFM ‐ 0.0 䴀턃/min 0.0 Pa ‐ 0 ‐ 0.0 Pa0.0 Pa

4Duct 0 CFM 10"x8" 0.0 䴀턃/min ‐ 0.29 ‐ 0.00 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 0 CFM ‐ 0.0 䴀턃/min 0.0 Pa ‐ 0 ‐ 0.0 Pa0.0 Pa

5Duct 0 CFM 10"x4" 0.0 䴀턃/min ‐ 0.38 ‐ 0.00 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 0 CFM ‐ 0.0 䴀턃/min 0.0 Pa ‐ 0 ‐ 0.0 Pa0.0 Pa

7

Duct 250 CFM 9"x9" 444.4䴀턃/min ‐ 0.14 ‐ 0.04 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 250 CFM ‐ 444.4䴀턃/min 3.1 Pa ‐ 0 ‐ 0.0 Pa

Air Terminal 250 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa

0.0 Pa

8Duct 250 CFM 10"x4" 900.0

䴀턃/min ‐ 3.42 ‐ 0.25 in‐wg/100䴀턃 7.0 Pa

Fiᜀꘂngs 250 CFM ‐ 900.0䴀턃/min 12.6 Pa ‐ 0 ‐ 0.0 Pa

7.0 Pa

9

Duct 250 CFM 9"x9" 444.4䴀턃/min ‐ 0.14 ‐ 0.04 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 250 CFM ‐ 444.4䴀턃/min 3.1 Pa ‐ 0 ‐ 0.0 Pa

Air Terminal 250 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa

0.0 Pa

10Duct 250 CFM 10"x4" 900.0

䴀턃/min ‐ 1.88 ‐ 0.25 in‐wg/100䴀턃 3.9 Pa

Fiᜀꘂngs 250 CFM ‐ 900.0䴀턃/min 12.6 Pa ‐ 0 ‐ 0.0 Pa

3.9 Pa

11 Duct 250 CFM 10"x8" 450.0䴀턃/min ‐ 0.00 ‐ 0.04 in‐

wg/100䴀턃 0.0 Pa 0.0 Pa

Cri㐀鸂cal Path : 1‐2‐11‐8‐7 ; Total Pressure Loss : 24.3 Pa

Detail Informa㐀鸂on of Straight Segment by Sec㐀鸂ons

Sec㐀鸂on Element ID Flow Size Velocity VelocityPressure Length Pressure Loss Total

Pressure Loss

2883731 500 CFM 10"x8" 900.0 䴀턃/min 12.6 Pa 0.94 1.1 Pa883732 500 CFM 10"x8" 900.0 䴀턃/min 12.6 Pa 0.55 0.6 Pa

1.8 Pa

3 883729 0 CFM 10"x4" 0.0 䴀턃/min 0.0 Pa 0.35 0.0 Pa 0.0 Pa

Page 78: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

4 883731 0 CFM 10"x8" 0.0 䴀턃/min 0.0 Pa 0.29 0.0 Pa 0.0 Pa

5 883730 0 CFM 10"x4" 0.0 䴀턃/min 0.0 Pa 0.38 0.0 Pa 0.0 Pa

7 883738 250 CFM 9"x9" 444.4 䴀턃/min 3.1 Pa 0.14 0.0 Pa 0.0 Pa

8 883729 250 CFM 10"x4" 900.0 䴀턃/min 12.6 Pa 3.42 7.0 Pa 7.0 Pa

9 883740 250 CFM 9"x9" 444.4 䴀턃/min 3.1 Pa 0.14 0.0 Pa 0.0 Pa

10 883730 250 CFM 10"x4" 900.0 䴀턃/min 12.6 Pa 1.88 3.9 Pa 3.9 Pa

11 883731 250 CFM 10"x8" 450.0 䴀턃/min 3.1 Pa 0.00 0.0 Pa 0.0 Pa

Fiᜀꘂng and Accessory Loss Coefficient Summary by Sec㐀鸂ons

Sec㐀鸂on Element ID Loss Method ASHRAE Table Loss Coefficient Pressure Loss TotalPressure Loss

1 883751 Coefficient fromASHRAE Table SR4‐3 0 0.0 Pa 0.0 Pa

2883750 Coefficient from

ASHRAE Table SR3‐1 1.174 14.8 Pa

883751 Coefficient fromASHRAE Table SR4‐3 0.052718 0.7 Pa

15.4 Pa

3 883736 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

4 883733 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

5 883737 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

7 883739 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

8 883734 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

9 883741 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

10 883735 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

URC‐13 OurdoorSystem Informa㐀鸂onSystem Classifica㐀鸂on Supply AirSystem Type Outdoor AirSystem Name URC‐13 OurdoorAbbrevia㐀鸂on

Total Pressure Loss Calcula㐀鸂ons by Sec㐀鸂ons

Sec㐀鸂on Element Flow Size Velocity VelocityPressure Length Loss

Coefficient Fric㐀鸂onTotalPressureLoss

Sec㐀鸂onPressure Loss

1Fiᜀꘂngs 615 CFM ‐ 1164.0

䴀턃/min 21.0 Pa ‐ 0 ‐ 0.0 Pa

Equipment 615 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa0.0 Pa

2Duct 615 CFM 10"x8" 1107.0

䴀턃/min ‐ 0.33 ‐ 0.21 in‐wg/100䴀턃 0.6 Pa

Fiᜀꘂngs 615 CFM ‐ 1107.0䴀턃/min 19.0 Pa ‐ 0.052718 ‐ 1.0 Pa

1.6 Pa

3Duct 0 CFM 10"x8" 0.0 䴀턃/min ‐ 0.31 ‐ 0.00 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 0 CFM ‐ 0.0 䴀턃/min 0.0 Pa ‐ 0 ‐ 0.0 Pa0.0 Pa

4Duct 615 CFM 10"x8" 1107.0

䴀턃/min ‐ 0.33 ‐ 0.21 in‐wg/100䴀턃 0.6 Pa

Fiᜀꘂngs 615 CFM ‐ 1107.0䴀턃/min 19.0 Pa ‐ 0 ‐ 0.0 Pa

0.6 Pa

5

Duct 0 CFM 10"x4" 0.0 䴀턃/min ‐ 0.35 ‐ 0.00 in‐wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 0 CFM ‐ 0.0 䴀턃/min 0.0 Pa ‐ 0 ‐ 0.0 Pa 0.0 Pa

0.00 in‐

Page 79: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

6 Duct 0 CFM 10"x4" 0.0 䴀턃/min ‐ 0.35 ‐ wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 0 CFM ‐ 0.0 䴀턃/min 0.0 Pa ‐ 0 ‐ 0.0 Pa

0.0 Pa

8Duct 0 CFM 10"x4" 0.0 䴀턃/min ‐ 0.23 ‐ 0.00 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 0 CFM ‐ 0.0 䴀턃/min 0.0 Pa ‐ 0 ‐ 0.0 Pa0.0 Pa

10Duct 115 CFM 10"x4" 414.0

䴀턃/min ‐ 6.66 ‐ 0.06 in‐wg/100䴀턃 3.4 Pa

Fiᜀꘂngs 115 CFM ‐ 414.0䴀턃/min 2.7 Pa ‐ 0 ‐ 0.0 Pa

3.4 Pa

11Duct 0 CFM 10"x4" 0.0 䴀턃/min ‐ 0.30 ‐ 0.00 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 0 CFM ‐ 0.0 䴀턃/min 0.0 Pa ‐ 0 ‐ 0.0 Pa0.0 Pa

12Duct 25 CFM 10"x4" 90.0 䴀턃/min ‐ 2.77 ‐ 0.00 in‐

wg/100䴀턃 0.1 Pa

Fiᜀꘂngs 25 CFM ‐ 90.0 䴀턃/min 0.1 Pa ‐ 0 ‐ 0.0 Pa0.1 Pa

13Duct 25 CFM 9"x9" 44.4 䴀턃/min ‐ 0.15 ‐ 0.00 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 25 CFM ‐ 44.4 䴀턃/min 0.0 Pa ‐ 0 ‐ 0.0 PaAir Terminal 25 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa

0.0 Pa

15

Duct 90 CFM 9"x9" 160.0䴀턃/min ‐ 0.15 ‐ 0.01 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 90 CFM ‐ 160.0䴀턃/min 0.4 Pa ‐ 0 ‐ 0.0 Pa

Air Terminal 90 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa

0.0 Pa

19

Duct 250 CFM 9"x9" 444.4䴀턃/min ‐ 0.15 ‐ 0.04 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 250 CFM ‐ 444.4䴀턃/min 3.1 Pa ‐ 0 ‐ 0.0 Pa

Air Terminal 250 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa

0.0 Pa

20Duct 250 CFM 10"x4" 900.0

䴀턃/min ‐ 1.88 ‐ 0.25 in‐wg/100䴀턃 3.9 Pa

Fiᜀꘂngs 250 CFM ‐ 900.0䴀턃/min 12.6 Pa ‐ 0 ‐ 0.0 Pa

3.9 Pa

21

Duct 250 CFM 9"x9" 444.4䴀턃/min ‐ 0.15 ‐ 0.04 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 250 CFM ‐ 444.4䴀턃/min 3.1 Pa ‐ 0 ‐ 0.0 Pa

Air Terminal 250 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa

0.0 Pa

22Duct 250 CFM 10"x4" 900.0

䴀턃/min ‐ 3.42 ‐ 0.25 in‐wg/100䴀턃 7.0 Pa

Fiᜀꘂngs 250 CFM ‐ 900.0䴀턃/min 12.6 Pa ‐ 0 ‐ 0.0 Pa

7.0 Pa

23 Duct 500 CFM 10"x8" 900.0䴀턃/min ‐ 0.80 ‐ 0.14 in‐

wg/100䴀턃 0.9 Pa 0.9 Pa

24 Duct 250 CFM 10"x8" 450.0䴀턃/min ‐ 0.00 ‐ 0.04 in‐

wg/100䴀턃 0.0 Pa 0.0 Pa

25 Duct 90 CFM 10"x4" 324.0䴀턃/min ‐ 3.82 ‐ 0.04 in‐

wg/100䴀턃 1.2 Pa 1.2 Pa

Cri㐀鸂cal Path : 1‐2‐4‐23‐24‐22‐21 ; Total Pressure Loss : 10.2 Pa

Detail Informa㐀鸂on of Straight Segment by Sec㐀鸂ons

Sec㐀鸂on Element ID Flow Size Velocity VelocityPressure Length Pressure Loss Total

Pressure Loss

2 883801 615 CFM 10"x8" 1107.0 䴀턃/min 19.0 Pa 0.33 0.6 Pa 0.6 Pa

3 883800 0 CFM 10"x8" 0.0 䴀턃/min 0.0 Pa 0.31 0.0 Pa 0.0 Pa

4 883800 615 CFM 10"x8" 1107.0 䴀턃/min 19.0 Pa 0.33 0.6 Pa 0.6 Pa

5 883804 0 CFM 10"x4" 0.0 䴀턃/min 0.0 Pa 0.35 0.0 Pa 0.0 Pa

6 883805 0 CFM 10"x4" 0.0 䴀턃/min 0.0 Pa 0.35 0.0 Pa 0.0 Pa

8 883806 0 CFM 10"x4" 0.0 䴀턃/min 0.0 Pa 0.23 0.0 Pa 0.0 Pa

10 883806 115 CFM 10"x4" 414.0 䴀턃/min 2.7 Pa 6.66 3.4 Pa 3.4 Pa

Page 80: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

11 883807 0 CFM 10"x4" 0.0 䴀턃/min 0.0 Pa 0.30 0.0 Pa 0.0 Pa

12 883807 25 CFM 10"x4" 90.0 䴀턃/min 0.1 Pa 2.77 0.1 Pa 0.1 Pa

13 883811 25 CFM 9"x9" 44.4 䴀턃/min 0.0 Pa 0.15 0.0 Pa 0.0 Pa

15 883815 90 CFM 9"x9" 160.0 䴀턃/min 0.4 Pa 0.15 0.0 Pa 0.0 Pa

19 883821 250 CFM 9"x9" 444.4 䴀턃/min 3.1 Pa 0.15 0.0 Pa 0.0 Pa

20 883804 250 CFM 10"x4" 900.0 䴀턃/min 12.6 Pa 1.88 3.9 Pa 3.9 Pa

21 883823 250 CFM 9"x9" 444.4 䴀턃/min 3.1 Pa 0.15 0.0 Pa 0.0 Pa

22 883805 250 CFM 10"x4" 900.0 䴀턃/min 12.6 Pa 3.42 7.0 Pa 7.0 Pa

23 883800 500 CFM 10"x8" 900.0 䴀턃/min 12.6 Pa 0.80 0.9 Pa 0.9 Pa

24 883800 250 CFM 10"x8" 450.0 䴀턃/min 3.1 Pa 0.00 0.0 Pa 0.0 Pa

25 883806 90 CFM 10"x4" 324.0 䴀턃/min 1.6 Pa 3.82 1.2 Pa 1.2 Pa

Fiᜀꘂng and Accessory Loss Coefficient Summary by Sec㐀鸂ons

Sec㐀鸂on Element ID Loss Method ASHRAE Table Loss Coefficient Pressure Loss TotalPressure Loss

1 883802 Coefficient fromASHRAE Table SR4‐3 0 0.0 Pa 0.0 Pa

2883802 Coefficient from

ASHRAE Table SR4‐3 0.052718 1.0 Pa

883803 Coefficient fromASHRAE Table ‐ 0 0.0 Pa

1.0 Pa

3 883825 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

4 883803 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

5 883817 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

6 883818 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

8 883813 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

10 883814 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

11 883809 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

12 883808 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

13 883812 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

15 883816 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

19 883822 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

20 883819 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

21 883824 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

22 883820 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

URC‐14 OutdoorSystem Informa㐀鸂onSystem Classifica㐀鸂on Supply AirSystem Type Outdoor AirSystem Name URC‐14 OutdoorAbbrevia㐀鸂on

Total Pressure Loss Calcula㐀鸂ons by Sec㐀鸂ons

Element Flow Size VelocityVelocityPressure Length

LossCoefficient Fric㐀鸂on

TotalPressure Sec㐀鸂on

Page 81: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

Sec㐀鸂on Loss Pressure Loss

1Fiᜀꘂngs 340 CFM ‐ 643.5

䴀턃/min 6.4 Pa ‐ 0 ‐ 0.0 Pa

Equipment 340 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa0.0 Pa

2Duct 340 CFM 12"x4" 1020.0

䴀턃/min ‐ 0.33 ‐ 0.30 in‐wg/100䴀턃 0.8 Pa

Fiᜀꘂngs 340 CFM ‐ 1020.0䴀턃/min 16.1 Pa ‐ 0.04354 ‐ 0.7 Pa

1.5 Pa

3Duct 0 CFM 12"x4" 0.0 䴀턃/min ‐ 0.32 ‐ 0.00 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 0 CFM ‐ 0.0 䴀턃/min 0.0 Pa ‐ 0 ‐ 0.0 Pa0.0 Pa

4

Duct 340 CFM 12"x12" 340.0䴀턃/min ‐ 0.12 ‐ 0.02 in‐

wg/100䴀턃 0.0 Pa

Fiᜀꘂngs 340 CFM ‐ 340.0䴀턃/min 1.8 Pa ‐ 0 ‐ 0.0 Pa

Air Terminal 340 CFM ‐ ‐ ‐ ‐ ‐ ‐ 0.0 Pa

0.0 Pa

5Duct 340 CFM 12"x4" 1020.0

䴀턃/min ‐ 1.06 ‐ 0.30 in‐wg/100䴀턃 2.6 Pa

Fiᜀꘂngs 340 CFM ‐ 1020.0䴀턃/min 16.1 Pa ‐ 0 ‐ 0.0 Pa

2.6 Pa

Cri㐀鸂cal Path : 1‐2‐5‐4 ; Total Pressure Loss : 4.1 Pa

Detail Informa㐀鸂on of Straight Segment by Sec㐀鸂ons

Sec㐀鸂on Element ID Flow Size Velocity VelocityPressure Length Pressure Loss Total

Pressure Loss

2 883835 340 CFM 12"x4" 1020.0 䴀턃/min 16.1 Pa 0.33 0.8 Pa 0.8 Pa

3 883834 0 CFM 12"x4" 0.0 䴀턃/min 0.0 Pa 0.32 0.0 Pa 0.0 Pa

4 883839 340 CFM 12"x12" 340.0 䴀턃/min 1.8 Pa 0.12 0.0 Pa 0.0 Pa

5 883834 340 CFM 12"x4" 1020.0 䴀턃/min 16.1 Pa 1.06 2.6 Pa 2.6 Pa

Fiᜀꘂng and Accessory Loss Coefficient Summary by Sec㐀鸂ons

Sec㐀鸂on Element ID Loss Method ASHRAE Table Loss Coefficient Pressure Loss TotalPressure Loss

1 883836 Coefficient fromASHRAE Table SR4‐3 0 0.0 Pa 0.0 Pa

2883836 Coefficient from

ASHRAE Table SR4‐3 0.04354 0.7 Pa

883837 Coefficient fromASHRAE Table ‐ 0 0.0 Pa

0.7 Pa

3 883838 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

4 883840 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

5 883837 Coefficient fromASHRAE Table ‐ 0 0.0 Pa 0.0 Pa

Page 82: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 27/02/12

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 32 de 34

32/34

7.2.6 Anexo CALCULO TUBERIAS DE REFRIGERACION

Page 83: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 27/02/12

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 33 de 34

33/34

7.2.7 Anexo SISTEMA ELECTRICO

Page 84: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

FECHA 13/10/2016REVISION 1 D CastroANOTACIONES Version Inicial 13/10/2016

Ajuste Arquitectonico 27/02/2017

ITEM UBICACIÓN EQUIPO TABLERO POTENCIA (Kwatt) CONSUMO (A) BRAKER (A) OBSERVACIONES

UNIDAD CONDENSADORA VARIABLE CUBIERTA BLOQUE A1 UCRV-01 1 220 3 60 31.5 KW 31.50 91.0 3x100AUNIDADES INTERIORES VARIABLES VARIAS UFCCV-XX 1 220 2 60 27.5 MCA 8.56 27.5 2x30AEXTRACTOR TIPO HONGO CUBIERTA BLOQUE A1 VE-01 1 220 2 60 0.33 HP 0.25 3.7 2x5AUNIDAD EXTRACTORA CUBIERTA BLOQUE A1 VE-06 1 220 3 60 0.5 HP 0.37 2.4 3x3AVENTILADOR DE TECHO CAFETERIA BLOQUE A1 VET-01A 1 110 1 60 0.19 KW 0.19 1.7 1x2AVENTILADOR DE TECHO CAFETERIA BLOQUE A1 VET-02A 1 110 1 60 0.19 KW 0.19 1.7 1x2AVENTILADOR DE TECHO CAFETERIA BLOQUE A1 VET-03A 1 110 1 60 0.19 KW 0.19 1.7 1x2AVENTILADOR DE TECHO CAFETERIA BLOQUE A1 VET-04A 1 110 1 60 0.19 KW 0.19 1.7 1x2AVENTILADOR DE TECHO FREE COVERED AREA A1 VET-05A 1 110 1 60 0.19 KW 0.19 1.7 1x2AVENTILADOR DE TECHO FREE COVERED AREA A1 VET-06A 1 110 1 60 0.19 KW 0.19 1.7 1x2AUNIDAD RECUPERADORA DE CALOR BIBLIOTECA URCV-01 1 220 2 60 0.36 KW 0.36 1.2 2x2AUNIDAD RECUPERADORA DE CALOR BIBLIOTECA URCV-02 1 220 2 60 0.36 KW 0.36 1.2 2x2AUNIDAD RECUPERADORA DE CALOR LABORATORIOS URCV-03 1 220 2 60 0.36 KW 0.36 1.2 2x2AUNIDAD RECUPERADORA DE CALOR LABORATORIOS URCV-04 1 220 2 60 0.36 KW 0.36 1.2 2x2AUNIDAD RECUPERADORA DE CALOR LABORATORIOS URCV-05 1 220 2 60 0.36 KW 0.36 1.2 2x2AUNIDAD RECUPERADORA DE CALOR LABORATORIOS URCV-06 1 220 2 60 0.36 KW 0.36 1.2 2x2A

UNIDAD CONDENSADORA VARIABLE CUBIERTA BLOQUE B1 UCRV-02 2 220 3 60 16 KW 16.00 42.0 3x50AUNIDADES INTERIORES VARABLES VARIAS UFCCV-XX 2 220 2 60 18.2 MCA 5.66 18.2 2x25AUNIDAD CONDENSADORA VARIABLE CUBIERTA BLOQUE B1 UCRV-03 2 220 3 60 8.8 KW 8.80 24.5 3x30AUNIDADES INTERIORES VARABLES VARIAS UFCCV-XX 2 220 2 60 6.6 MCA 2.05 6.6 2x10AEXTRACTOR TIPO HONGO CUBIERTA BLOQUE B1 VE-02 2 220 2 60 0.33 HP 0.25 3.7 2x5AEXTRACTOR TIPO HONGO CUBIERTA BLOQUE B1 VE-03 2 220 2 60 0.25 HP 0.19 2.3 2x3AVENTILADOR DE TECHO CAFETERIA BLOQUE B1 VET-01B 2 110 1 60 0.19 KW 0.19 1.7 1x2AVENTILADOR DE TECHO CAFETERIA BLOQUE B1 VET-02B 2 110 1 60 0.19 KW 0.19 1.7 1x2AVENTILADOR DE TECHO CAFETERIA BLOQUE B1 VET-03B 2 110 1 60 0.19 KW 0.19 1.7 1x2AVENTILADOR DE TECHO CAFETERIA BLOQUE B1 VET-04B 2 110 1 60 0.19 KW 0.19 1.7 1x2AVENTILADOR DE TECHO STAR BLOQUE B1 VET-05B 2 110 1 60 0.19 KW 0.19 1.7 1x2AVENTILADOR DE TECHO STAR BLOQUE B1 VET-06B 2 110 1 60 0.19 KW 0.19 1.7 1x2AVENTILADOR DE TECHO STAR BLOQUE B1 VET-07B 2 110 1 60 0.19 KW 0.19 1.7 1x2AVENTILADOR DE TECHO STAR BLOQUE B1 VET-08B 2 110 1 60 0.19 KW 0.19 1.7 1x2AUNIDAD RECUPERADORA DE CALOR AULAS URCV-07 2 220 2 60 0.74 KW 0.74 2.4 2x5AUNIDAD RECUPERADORA DE CALOR AULAS URCV-08 2 220 2 60 0.74 KW 0.74 2.4 2x5AUNIDAD RECUPERADORA DE CALOR AULAS URCV-09 2 220 2 60 0.74 KW 0.74 2.4 2x5A

ANOTACIONES

DISEÑADOR

TABLA DE DATOS

ESPACIO PARA LOGO

UNIVERSIDAD NACIONAL SEDE TUMACO

VERSIÓN 0

Ing Diego Gonzalo CastroPROYECTO

DATOS PLACA

AG-MC-002

DATOS (V/F/Hz)

UBICACIÓN TUMACO NARIÑO

MEMORIA DE CÁLCULOS: CALENDARIO ELECTRICO

Page 85: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIDAD RECUPERADORA DE CALOR AULAS URCV-10 2 220 2 60 0.47 KW 0.47 1.5 2x2AUNIDAD RECUPERADORA DE CALOR TRABAJO AUTONOMO URCV-11 2 220 2 60 0.36 KW 0.36 1.2 2x2AUNIDAD RECUPERADORA DE CALOR TRABAJO AUTONOMO URCV-12 2 220 2 60 0.47 KW 0.47 1.5 2x2A

UNIDAD CONDENSADORA VARIABLE CUBIERTA BLOQUE C1 UCRV-04 3 220 3 60 14.4 KW 14.40 41.9 3x50AUNIDADES INTERIORES VARABLES VARIAS UFCCV-XX 3 220 2 60 14.9 MCA 4.64 14.9 2x20AVENTILADOR DE TECHO RECEPCION BLOQUE C1 VET-01C 3 110 1 60 0.19 KW 0.19 1.7 1x2AVENTILADOR DE TECHO RECEPCION BLOQUE C1 VET-02C 3 110 1 60 0.19 KW 0.19 1.7 1x2AVENTILADOR DE TECHO RECEPCION BLOQUE C1 VET-03C 3 110 1 60 0.19 KW 0.19 1.7 1x2AVENTILADOR DE TECHO RECEPCION BLOQUE C1 VET-04C 3 110 1 60 0.19 KW 0.19 1.7 1x2AVENTILADOR DE TECHO RECEPCION BLOQUE C1 VET-05C 3 110 1 60 0.19 KW 0.19 1.7 1x2AUNIDAD RECUPERADORA DE CALOR ZONA DE TRABAJO AUTONOMO URC-13 3 220 2 60 0.47 KW 0.47 1.5 2x2AUNIDAD RECUPERADORA DE CALOR SALON ICI URC-14 3 220 2 60 0.36 KW 0.36 1.2 2x2A

PAQUETE VARIABLE CUBIERTA BLOQUE D1 UPA-01 4 220 3 60 20 KW 20.00 55.7 3x70AUNIDAD MINISPLIT CUBIERTA BLOQUE D1 UMSC/UCMSC-01 4 220 2 60 0.86 KW 0.86 2.8 2x5AUNIDAD MINISPLIT CUBIERTA BLOQUE D1 UMSC/UCMSC-02 4 220 2 60 0.86 KW 0.86 2.8 2x5AUNIDAD RECUPERADORA DE CALOR AUDITORIO URC-15 4 220 2 60 0.93 KW 0.93 3.0 2x5AVENTILADOR DE TECHO FREE COVERED AREA D1 VET-01D 4 110 1 60 0.19 KW 0.19 1.7 1x2AVENTILADOR DE TECHO FREE COVERED AREA D1 VET-01D 4 110 1 60 0.19 KW 0.19 1.7 1x2AVENTILADOR DE TECHO FREE COVERED AREA D1 VET-01D 4 110 1 60 0.19 KW 0.19 1.7 1x2AVENTILADOR DE TECHO FREE COVERED AREA D1 VET-01D 4 110 1 60 0.19 KW 0.19 1.7 1x2A

EXTRACTOR TIPO HONGO CUBIERTA BLOQUE B1 VE-08 5 220 2 60 0.25 HP 0.19 2.3 2x3A

VENTILADOR DE PARED BAÑO VE-04 DEL PISO 110 1 60 0.13 KW 0.13 1.2 1x2AVENTILADOR DE PARED BAÑO VE-05 DEL PISO 110 1 60 0.13 KW 0.13 1.2 1x2A

VENTILADOR DE PARED BAÑO VE-07 DE LA PORTERIA 110 1 60 0.13 KW 0.13 1.2 1x2AVENTILADOR DE PARED BAÑO VE-09 DE LA PORTERIA 110 1 60 0.13 KW 0.13 1.2 1x2AUNIDAD MINISPLIT PORTERIA UMSP/UCMSP-01 DE LA PORTERIA 220 2 60 0.86 KW 0.86 2.8 2x5A

MCA = MAXIMUN CURRENT AMPACITYFLA = FULL LOAD AMPACITY

KW = KILO WATT CARGA TOTAL Kw 87.7

HP = CABALLOS DE FUERZA NUMERO TABLEROS 5.0

RESUMEN EJECUTIVO

Page 86: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

UNIVERSIDAD NACIONAL SEDE TUMACO

Revisión 27/02/12

DISEÑO Y ESTUDIOS TÉCNICOS PARA EL SISTEMA DE HVAC

Pág. 34 de 34

34/34

7.2.8 Anexo SELECCIÓN DE EQUIPOS

Page 87: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

CRV-T

CRVT-15-0,333HP/4-825RPM-(220~1)

La gama CRV-T Extractor centrífugo de montaje en techo, marca S&P, modelo CRVT-15-0,333HP/4-825rpm-(220~1), con caudal 760 cfm y

presión 0,514 inwg. Para aplicaciones de extracción de aire limpio descarga vertical,con transmisión poleas-bandas diseñadas y calculadas

acorde a las necesidades requeridas.

Proyecto: UNAL TUMACO (rev. 1 (3)) - Referencia producto: VE-01 BLOQUE APunto de trabajo requerido CurvaCaudal 750 cfm

0 500 1000 1500 2000 2500 3000 3500 4000

Q - Caudal (cfm)

0,0

0,5

1,0

1,5

2,0

Pre

sión

Est

átic

a(inw

g)

825

640

740

940

1040

1140

1240

1340

Max 1410

rpm

51,9%

20%

30%

40%

50%

40%

0,333 hp0,180 hp0,250 hp 0,370 hp 0,550 hp

Presión estática 0,500 inwg

Temperatura 20 °C

Altitud 25 m

Densidad 1,2 kg/m³

Frecuencia 60 Hz

Tensión 220~1

Punto trabajoCaudal 760 cfm

Presión estática 0,514 inwg @ 1,2 kg/m³

Presión dinámica 0,006 inwg @ 1,2 kg/m³

Presión total 0,520 inwg @ 1,2 kg/m³

Presión estática estándar 0,515 inwg @ 1,2 kg/m³

Presión dinámica estándar 0,006 inwg @ 1,2 kg/m³

Presión total estándar 0,521 inwg @ 1,2 kg/m³

Pot Elect absorbida 0,476 hp

Rend Total 46,2 %

Potencia útil 0,135 hp @ 1,2 kg/m³

Potencia útill estándar 0,135 hp @ 1,2 kg/m³

Rend Estático 45,7 %

Velocidad descarga 1,6 m/s

Velocidad ventilador 825 rpm

Potencia específica 0,35 W/l/s

ConstrucciónTamaño ventilador 15

0 500 1000 1500 2000 2500

Q - Caudal (cfm)

0,0

0,1

0,2

0,3

0,4

0,5

0,6

Pre

sión

Est

ática

(inw

g)

Curva (1,204 kg/m³)Peso 39,80 kg

MotoresNúmero de Polos 4

Potencia motor 0,33 hp

Tensión 1-127/220V-60Hz

Intensidad máxima absorbida 7,6 A

Índice de protección IP55

Clase motor B

Dimensiones

27/2/2017 17:51:46 Page 1 of 10

Page 88: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

A B C D

749 610 745 50

27/2/2017 17:51:46 Page 2 of 10

Page 89: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

CRV-T

CRVT-15-0,333HP/4-825RPM-(220~1)

La gama CRV-T Extractor centrífugo de montaje en techo, marca S&P, modelo CRVT-15-0,333HP/4-825rpm-(220~1), con caudal 760 cfm y

presión 0,514 inwg. Para aplicaciones de extracción de aire limpio descarga vertical,con transmisión poleas-bandas diseñadas y calculadas

acorde a las necesidades requeridas.

Proyecto: UNAL TUMACO (rev. 1 (3)) - Referencia producto: VE-02 BLOQUE BPunto de trabajo requerido CurvaCaudal 750 cfm

0 500 1000 1500 2000 2500 3000 3500 4000

Q - Caudal (cfm)

0,0

0,5

1,0

1,5

2,0

Pre

sión

Est

átic

a(inw

g)

825

640

740

940

1040

1140

1240

1340

Max 1410

rpm

51,9%

20%

30%

40%

50%

40%

0,333 hp0,180 hp0,250 hp 0,370 hp 0,550 hp

Presión estática 0,500 inwg

Temperatura 20 °C

Altitud 25 m

Densidad 1,2 kg/m³

Frecuencia 60 Hz

Tensión 220~1

Punto trabajoCaudal 760 cfm

Presión estática 0,514 inwg @ 1,2 kg/m³

Presión dinámica 0,006 inwg @ 1,2 kg/m³

Presión total 0,520 inwg @ 1,2 kg/m³

Presión estática estándar 0,515 inwg @ 1,2 kg/m³

Presión dinámica estándar 0,006 inwg @ 1,2 kg/m³

Presión total estándar 0,521 inwg @ 1,2 kg/m³

Pot Elect absorbida 0,476 hp

Rend Total 46,2 %

Potencia útil 0,135 hp @ 1,2 kg/m³

Potencia útill estándar 0,135 hp @ 1,2 kg/m³

Rend Estático 45,7 %

Velocidad descarga 1,6 m/s

Velocidad ventilador 825 rpm

Potencia específica 0,35 W/l/s

ConstrucciónTamaño ventilador 15

0 500 1000 1500 2000 2500

Q - Caudal (cfm)

0,0

0,1

0,2

0,3

0,4

0,5

0,6

Pre

sión

Est

ática

(inw

g)

Curva (1,204 kg/m³)Peso 39,80 kg

MotoresNúmero de Polos 4

Potencia motor 0,33 hp

Tensión 1-127/220V-60Hz

Intensidad máxima absorbida 7,6 A

Índice de protección IP55

Clase motor B

Dimensiones

27/2/2017 17:51:46 Page 3 of 10

Page 90: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

A B C D

749 610 745 50

27/2/2017 17:51:46 Page 4 of 10

Page 91: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

CRV-T

CRVT-10-0,25HP/4-1325RPM-(208-230~3)

La gama CRV-T Extractor centrífugo de montaje en techo, marca S&P, modelo CRVT-10-0,25HP/4-1325rpm-(208-230~3), con caudal 598 cfm y

presión 0,497 inwg. Para aplicaciones de extracción de aire limpio descarga vertical,con transmisión poleas-bandas diseñadas y calculadas

acorde a las necesidades requeridas.

Proyecto: UNAL TUMACO (rev. 1 (3)) - Referencia producto: VE-03 BLOQUE BPunto de trabajo requerido CurvaCaudal 600 cfm

0 500 1000 1500 2000

Q - Caudal (cfm)

0,0

0,2

0,4

0,6

0,8

1,0

1,2

Pre

sión

Est

átic

a(inw

g)

1325

980

1080

1180

1280

1380

1480

1580

1680

1780

Max 1820

rpm

34,6%

20%

30%

0,250 hp0,180 hp 0,269 hp

Presión estática 0,500 inwg

Temperatura 20 °C

Altitud 25 m

Densidad 1,2 kg/m³

Frecuencia 60 Hz

Tensión 208-230~3

Punto trabajoCaudal 598 cfm

Presión estática 0,497 inwg @ 1,2 kg/m³

Presión dinámica 0,002 inwg @ 1,2 kg/m³

Presión total 0,499 inwg @ 1,2 kg/m³

Presión estática estándar 0,498 inwg @ 1,2 kg/m³

Presión dinámica estándar 0,002 inwg @ 1,2 kg/m³

Presión total estándar 0,501 inwg @ 1,2 kg/m³

Pot Elect absorbida 0,219 hp

Potencia útil 0,139 hp @ 1,2 kg/m³

Potencia útill estándar 0,139 hp @ 1,2 kg/m³

Velocidad descarga 1 m/s

Velocidad ventilador 1325 rpm

Potencia específica 0,53 W/l/s

ConstrucciónTamaño ventilador 10

Peso 32,82 kg

Motores

0 200 400 600 800 1000 1200 1400 1600

Q - Caudal (cfm)

0,0

0,1

0,2

0,3

0,4

0,5

0,6

Pre

sión

Est

ática

(inw

g)

Curva (1,204 kg/m³)Número de Polos 4

Potencia motor 0,25 hp

Tensión 3-208-230/460V-60Hz

Intensidad máxima absorbida 1,1 A / 0,6 A

Índice de protección IP21

Clase motor B

Dimensiones

27/2/2017 17:51:46 Page 5 of 10

Page 92: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

A B C D

667 530 638 40

27/2/2017 17:51:46 Page 6 of 10

Page 93: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

SILENT

5SILENT200 - SILENT200-127V - EXTRACTORES LÍNEA HÁBITAT

Extractor axial para baño; diseñado para la renovación ambiental de cuartos de aseo y baños, marca S&P, en su modelo SILENT200-127V, con

caudal 103 cfm y presión 0,011 inwg. Incluye silentblocks construidos en bimaterial con componentes altamente resistentes y capaces de

absorber las vibraciones generadas por el motor, incorpora rodamientos a bolas que aseguran una larga vida con las máximas prestaciones,

compuerta antirretorno para evitar la entrada del aire del exterior cuando el equipo se encuentra apagado.

Proyecto: UNAL TUMACO (rev. 1 (3)) - Referencia producto: VE-04 BLOQUE DPunto de trabajo requerido CurvaCaudal 100 cfm

0 20 40 60 80 100 120

Q - Caudal (cfm)

0,00

0,05

0,10

0,15

0,20

0,25

0,30

Pre

sión

Est

átic

a(inw

g)

127V

Presión estática 0,010 inwg

Temperatura 20 °C

Altitud 25 m

Densidad 1,2 kg/m³

Frecuencia 60 Hz

Tensión 1-127V-60Hz

Punto trabajoCaudal 103 cfm

Presión estática 0,011 inwg @ 1,2 kg/m³

Presión dinámica 0,059 inwg @ 1,2 kg/m³

Presión total 0,070 inwg @ 1,2 kg/m³

Presión estática estándar 0,011 inwg @ 1,2 kg/m³

Presión dinámica estándar 0,059 inwg @ 1,2 kg/m³

Presión total estándar 0,070 inwg @ 1,2 kg/m³

Velocidad descarga 4,9 m/s

Velocidad ventilador 2400 rpm

ConstrucciónDiámetro 112 mm

Peso 0,80 kg

MotoresNúmero de Polos 2

Tensión 1-127V-60Hz

Índice de protección -

Clase motor

0 20 40 60 80 100 120

Q - Caudal (cfm)

0,00

0,05

0,10

0,15

0,20

0,25

0,30

Pre

sión

Est

ática

(inw

g)

127V

Curva (1,204 kg/m³)

Dimensiones

A B C D E F

180 180 117 80 89 117

27/2/2017 17:51:46 Page 7 of 10

Page 94: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

SILENT

5SILENT200 - SILENT200-127V - EXTRACTORES LÍNEA HÁBITAT

Extractor axial para baño; diseñado para la renovación ambiental de cuartos de aseo y baños, marca S&P, en su modelo SILENT200-127V, con

caudal 103 cfm y presión 0,011 inwg. Incluye silentblocks construidos en bimaterial con componentes altamente resistentes y capaces de

absorber las vibraciones generadas por el motor, incorpora rodamientos a bolas que aseguran una larga vida con las máximas prestaciones,

compuerta antirretorno para evitar la entrada del aire del exterior cuando el equipo se encuentra apagado.

Proyecto: UNAL TUMACO (rev. 1 (3)) - Referencia producto: VE-05 BLOQUE DPunto de trabajo requerido CurvaCaudal 100 cfm

0 20 40 60 80 100 120

Q - Caudal (cfm)

0,00

0,05

0,10

0,15

0,20

0,25

0,30

Pre

sión

Est

átic

a(inw

g)

127V

Presión estática 0,010 inwg

Temperatura 20 °C

Altitud 25 m

Densidad 1,2 kg/m³

Frecuencia 60 Hz

Tensión 1-127V-60Hz

Punto trabajoCaudal 103 cfm

Presión estática 0,011 inwg @ 1,2 kg/m³

Presión dinámica 0,059 inwg @ 1,2 kg/m³

Presión total 0,070 inwg @ 1,2 kg/m³

Presión estática estándar 0,011 inwg @ 1,2 kg/m³

Presión dinámica estándar 0,059 inwg @ 1,2 kg/m³

Presión total estándar 0,070 inwg @ 1,2 kg/m³

Velocidad descarga 4,9 m/s

Velocidad ventilador 2400 rpm

ConstrucciónDiámetro 112 mm

Peso 0,80 kg

MotoresNúmero de Polos 2

Tensión 1-127V-60Hz

Índice de protección -

Clase motor

0 20 40 60 80 100 120

Q - Caudal (cfm)

0,00

0,05

0,10

0,15

0,20

0,25

0,30

Pre

sión

Est

ática

(inw

g)

127V

Curva (1,204 kg/m³)

Dimensiones

A B C D E F

180 180 117 80 89 117

27/2/2017 17:51:46 Page 8 of 10

Page 95: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

PL

5PLE-154-PLE-154-1/2HP-(440~3)

Extractores centrífugos para atmósferas corrosivas y/o explosivas, marca S&P, modelo 5PLE-154-PLE-154-1/2HP-(440~3), con caudal 188 cfm y

presión 0,444 inwg. Conjunto carcasa en una sola pieza fabricada en polipropileno y rodete tipo álabes curvos adelantados, motores estándar

cerrados con protección IP55. Opción a motor a prueba de explosión clase I grupo D, bajo nivel sonoro y diseño compacto que facilita la

instalación.

Proyecto: UNAL TUMACO (rev. 1 (3)) - Referencia producto: VE-06 BLOQUE APunto de trabajo requerido CurvaCaudal 200 cfm

0 50 100 150 200 250 300 350

Q - Caudal (cfm)

0,0

0,1

0,2

0,3

0,4

0,5

0,6

0,7

Pre

sión

Est

átic

a(inw

g)

220/440V

Presión estática 0,500 inwg

Temperatura 20 °C

Altitud 25 m

Densidad 1,2 kg/m³

Frecuencia 60 Hz

Tensión 440~3

Punto trabajoCaudal 188 cfm

Presión estática 0,444 inwg @ 1,2 kg/m³

Presión dinámica 0,127 inwg @ 1,2 kg/m³

Presión total 0,570 inwg @ 1,2 kg/m³

Potencia motor 1/2

Tensión 208-230/460

Intensidad máxima 1.75/0.875

Velocidad ventilador 1700 rpm

ConstrucciónDiámetro 125 mm

Tamaño ventilador 154

Peso 55,00 kg

MotoresÍndice de protección -

Clase motor

0 50 100 150 200 250 300 350

Q - Caudal (cfm)

0,0

0,1

0,2

0,3

0,4

0,5

0,6

0,7

Pre

sión

Est

ática

(inw

g)

220/440V

Curva (1,204 kg/m³)

Dimensiones

Características acústicas

63 125 250 500 1k 2k 4k 8k Total

Descarga (LwA) 62 62 52 45 45 40 35 30 65

Descarga LpA @ 1,5m 47 47 37 30 30 25 20 15 51

A B C D D1 E F G H I J

353 569 463 120 127 349 389 327 140 183 9,5

27/2/2017 17:51:46 Page 9 of 10

Page 96: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

SILENT

5SILENT200 - SILENT200-127V - EXTRACTORES LÍNEA HÁBITAT

Extractor axial para baño; diseñado para la renovación ambiental de cuartos de aseo y baños, marca S&P, en su modelo SILENT200-127V, con

caudal 103 cfm y presión 0,011 inwg. Incluye silentblocks construidos en bimaterial con componentes altamente resistentes y capaces de

absorber las vibraciones generadas por el motor, incorpora rodamientos a bolas que aseguran una larga vida con las máximas prestaciones,

compuerta antirretorno para evitar la entrada del aire del exterior cuando el equipo se encuentra apagado.

Proyecto: UNAL TUMACO (rev. 1 (3)) - Referencia producto: VE-07 PORTERIAPunto de trabajo requerido CurvaCaudal 100 cfm

0 20 40 60 80 100 120

Q - Caudal (cfm)

0,00

0,05

0,10

0,15

0,20

0,25

0,30

Pre

sión

Est

átic

a(inw

g)

127V

Presión estática 0,010 inwg

Temperatura 20 °C

Altitud 25 m

Densidad 1,2 kg/m³

Frecuencia 60 Hz

Tensión 1-127V-60Hz

Punto trabajoCaudal 103 cfm

Presión estática 0,011 inwg @ 1,2 kg/m³

Presión dinámica 0,059 inwg @ 1,2 kg/m³

Presión total 0,070 inwg @ 1,2 kg/m³

Presión estática estándar 0,011 inwg @ 1,2 kg/m³

Presión dinámica estándar 0,059 inwg @ 1,2 kg/m³

Presión total estándar 0,070 inwg @ 1,2 kg/m³

Velocidad descarga 4,9 m/s

Velocidad ventilador 2400 rpm

ConstrucciónDiámetro 112 mm

Peso 0,80 kg

MotoresNúmero de Polos 2

Tensión 1-127V-60Hz

Índice de protección -

Clase motor

0 20 40 60 80 100 120

Q - Caudal (cfm)

0,00

0,05

0,10

0,15

0,20

0,25

0,30

Pre

sión

Est

ática

(inw

g)

127V

Curva (1,204 kg/m³)

Dimensiones

A B C D E F

180 180 117 80 89 117

27/2/2017 17:51:46 Page 10 of 10

Page 97: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

© Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter. C-115

CE

ILIN

G D

IFFU

SE

RS

Performance Data

Light Commercial Directional DiffuserLCMD Series

Neck VelocityVelocity PressureTotal Pressure

3000.0060.049

4000.01

0.086

5000.0160.135

6000.0220.195

7000.0310.265

8000.0400.346

9000.0500.438

DuctSize

Total cfmNC

75--

10018

12523

15026

17530

20033

22535

6" x 6" A B A B A B A B A B A B A B4A cfm/Side 19 25 31 38 44 50 56

Throw,ft 3-4-9 4-6-12 5-7-15 6-9-17 7-10-20 8-12-21 9-13-23Duct 3A cfm/Side 19 28 25 38 31 47 38 56 44 66 50 75 56 84Area Throw,ft 3-4-9 4-5-11 4-6-12 5-7-14 5-7-15 6-9-18 6-9-17 7-11-21 7-10-20 8-12-23 8-12-21 10-14-24 9-13-23 11-16-260.25 2S, 2G cfm/Side 38 50 63 75 88 100 113ft2 Throw,ft 4-6-12 5-8-16 7-10-21 8-12-23 10-14-24 11-16-26 12-19-28

1S cfm/Side 75 100 125 150 175 200 225Throw,ft 6-9-17 8-12-23 10-15-25 12-17-28 14-20-30 16-23-32 17-24-34

DuctSize

Total cfmNC

133--

17821

22226

26630

31133

35536

40038

8" x 8" A B A B A B A B A B A B A B4A cfm/Side 33 45 56 67 78 89 100

Throw,ft 4-6-12 5-8-16 6-10-19 8-12-22 9-14-24 10-16-25 12-17-27Duct 3A cfm/Side 33 50 45 67 56 83 67 100 78 117 89 133 100 150Area Throw,ft 4-6-12 5-7-14 5-8-16 6-10-19 6-10-19 8-12-22 8-12-22 9-14-25 9-14-24 11-17-27 10-16-25 13-19-28 12-17-27 14-21-300.444 2S 2G cfm/Side 67 89 111 133 156 178 200

ft2 Throw,ft 5-8-16 7-11-22 9-14-24 11-16-27 13-19-29 15-22-31 16-23-331S cfm/Side 133 178 222 266 311 355 400

Throw,ft 8-12-23 10-16-27 13-19-30 16-23-32 18-25-35 21-27-37 23-28-40DuctSize

Total cfmNC

20817

27823

34728

41632

48635

55538

62541

10" x 10" A B A B A B A B A B A B A B4A cfm/Side 52 70 87 104 122 139 156

Throw,ft 5-7-15 6-10-19 8-12-23 10-15-25 11-17-27 13-19-29 15-22-30Duct 3A cfm/Side 52 78 70 104 87 130 104 156 122 182 139 208 156 234Area Throw,ft 5-7-15 6-9-18 6-10-19 8-12-23 8-12-23 10-15-25 10-15-25 12-18-28 11-17-27 14-21-30 13-19-29 16-23-32 15-22-30 18-24-340.694 2S 2G cfm/Side 104 139 174 208 243 278 313

ft2 Throw,ft 7-10-21 9-14-25 11-17-28 14-21-30 16-23-33 18-25-35 21-26-371S cfm/Side 208 278 347 416 486 555 625

Throw,ft 10-15-26 13-19-30 16-24-34 19-26-37 23-28-40 25-30-43 26-32-45DuctSize

Total cfmNC

30019

40025

50030

60034

70037

80040

90043

12" x 12" A B A B A B A B A B A B A B4A cfm/Side 75 100 125 150 175 200 225

Throw,ft 6-9-17 8-12-23 10-15-25 12-17-28 14-20-30 16-23-32 17-24-34Duct 3A cfm/Side 75 113 100 150 125 188 150 225 175 263 200 300 225 338Area Throw,ft 6-9-17 7-11-21 8-12-23 10-14-25 10-15-25 12-18-28 12-17-28 14-21-31 14-20-30 17-24-33 16-23-32 19-25-36 17-24-34 21-27-38

1 2S 2G cfm/Side 150 200 250 300 350 400 450ft2 Throw,ft 8-12-24 11-16-27 14-21-31 16-24-34 19-26-36 22-27-39 24-29-41

1S cfm/Side 300 400 500 600 700 800 900Throw,ft 12-17-29 16-23-33 19-26-37 23-29-41 26-31-44 27-33-47 29-35-50

DuctSize

Total cfmNC

40821

54427

68032

81636

95239

108842

122444

14" x 14" A B A B A B A B A B A B A B4A cfm/Side 102 136 170 204 238 272 306

Throw,ft 7-10-20 9-14-25 11-17-27 14-20-30 16-23-33 18-25-35 20-26-37Duct 3A cfm/Side 102 153 136 204 170 255 204 306 238 357 272 408 306 459Area Throw,ft 7-10-20 8-12-24 9-14-25 11-17-28 11-17-27 14-21-31 14-20-30 17-24-34 16-23-33 19-26-36 18-25-35 22-28-39 20-26-37 24-29-411.36 2S 2G cfm/Side 204 272 340 408 476 544 612ft2 Throw,ft 10-14-26 13-19-30 16-24-33 19-26-37 22-28-40 24-30-42 26-32-45

1S cfm/Side 408 544 680 816 952 1088 1224Throw,ft 14-20-32 18-26-36 23-29-41 26-32-45 28-34-48 30-36-52 32-39-55

DuctSize

Total cfmNC

53122

70829

88533

106237

123940

141643

159346

16" x 16" A B A B A B A B A B A B A B4A cfm/Side 133 177 221 266 310 354 398

Throw,ft 8-12-23 10-15-26 13-19-30 15-23-32 18-25-35 21-26-37 23-28-40Duct 3A cfm/Side 133 199 177 266 221 332 266 398 310 465 354 531 398 597Area Throw,ft 8-12-23 9-14-26 10-15-26 13-19-30 13-19-30 16-23-33 15-23-32 19-26-36 18-25-35 22-28-39 21-26-37 24-30-42 23-28-40 26-32-451.77 2S 2G cfm/Side 266 354 443 531 620 708 797ft2 Throw,ft 11-16-28 15-22-32 18-25-36 22-28-39 25-30-43 26-32-46 28-34-48

1S cfm/Side 531 708 885 1062 1239 1416 1593Throw,ft 15-23-34 21-28-39 25-31-44 28-34-48 30-37-52 32-39-56 34-42-59

Page 98: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

C-116 All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011. Imperial dimensions are converted to metric and rounded to the nearest millimeter.

CE

ILIN

G D

IFFU

SE

RS

Performance Data

Light Commercial Directional DiffuserLCMD Series

Neck VelocityVelocity PressureTotal Pressure

3000.0060.049

4000.010.086

5000.0160.135

6000.0220.195

7000.0310.265

8000.0400.346

9000.0500.438

DuctSize

Total cfmNC

67524

90030

112535

135038

157542

180045

202547

18" x 18" A B A B A B A B A B A B A B4A cfm/Side 169 225 281 338 394 450 506

Throw,ft 9-13-25 12-17-28 15-22-32 17-25-35 20-27-38 23-28-40 25-30-43Duct 3A cfm/Side 169 253 225 338 281 422 338 506 394 591 450 675 506 759Area Throw,ft 9-13-25 11-16-28 12-17-28 14-21-32 15-22-32 18-25-36 17-25-35 21-28-39 20-27-38 24-30-42 23-28-40 26-32-45 25-30-43 28-34-482.25 2S 2G cfm/Side 338 450 563 675 788 900 1013ft2 Throw,ft 12-19-30 16-24-35 21-27-39 24-30-42 26-32-46 28-35-49 30-37-52

1S cfm/Side 675 900 1125 1350 1575 1800 2025Throw,ft 17-26-36 23-30-42 27-33-47 30-36-52 32-39-56 34-42-60 36-45-63

DuctSize

Total cfmNC

83125

110831

138536

166240

193943

221646

249348

20" x 20" A B A B A B A B A B A B A B4A cfm/Side 208 277 346 416 485 554 623

Throw,ft 10-15-26 13-19-30 16-24-34 19-26-37 23-28-40 25-30-43 26-32-45Duct 3A cfm/Side 208 312 277 416 346 519 416 623 485 727 554 831 623 935Area Throw,ft 10-15-26 12-18-29 13-19-30 16-24-34 16-24-34 20-27-38 19-26-37 24-29-41 23-28-40 26-32-45 25-30-43 28-34-48 26-32-45 29-36-512.77 2S 2G cfm/Side 416 554 693 831 970 1108 1247ft2 Throw,ft 14-21-32 18-26-37 23-29-41 26-32-45 28-34-48 30-37-52 32-39-55

1S cfm/Side 831 1108 1385 1662 1939 2216 2493Throw,ft 19-27-39 26-32-45 29-35-50 32-39-55 34-42-59 36-45-63 39-47-67

DuctSize

Total cfmNC

100826

134432

168037

201641

235244

268847

302449

22" x 22" A B A B A B A B A B A B A B4A cfm/Side 252 336 420 504 588 672 756

Throw,ft 11-16-28 14-21-32 18-25-36 21-28-39 24-30-42 26-32-45 28-34-48Duct 3A cfm/Side 252 378 336 504 420 630 504 756 588 882 672 1008 756 1134Area Throw,ft 11-16-28 13-20-31 14-21-32 17-25-36 18-25-36 22-28-40 21-28-39 25-31-44 24-30-42 27-33-47 26-32-45 29-36-50 28-34-48 31-38-543.36 2S 2G cfm/Side 504 672 840 1008 1176 1344 1512ft2 Throw,ft 15-23-34 20-27-39 25-31-43 27-34-47 30-36-51 32-39-55 34-41-58

1S cfm/Side 1008 1344 1680 2016 2352 2688 3024Throw,ft 21-29-41 27-33-47 30-37-53 33-41-58 36-44-62 39-47-67 41-50-71

DuctSize

Total cfmNC

120027

160033

200038

240042

280045

320048

360050

24" x 24" A B A B A B A B A B A B A B4A cfm/Side 300 400 500 600 700 800 900

Throw,ft 12-17-29 16-23-33 19-26-37 23-29-41 26-31-44 27-33-47 29-35-50Duct 3A cfm/Side 300 450 400 600 500 750 600 900 700 1050 800 1200 900 1350Area Throw,ft 12-17-29 14-21-32 16-23-33 19-27-38 19-26-37 24-30-42 23-29-41 27-32-46 26-31-44 29-35-50 27-33-47 31-38-53 29-35-50 32-40-56

4 2S 2G cfm/Side 600 800 1000 1200 1400 1600 1800ft2 Throw,ft 16-25-35 22-29-41 26-32-46 29-35-50 31-38-54 33-41-58 35-43-61

1S cfm/Side 1200 1600 2000 2400 2800 3200 3600Throw,ft 23-30-43 29-35-50 32-39-55 35-43-61 38-46-66 41-50-70 43-53-74

Performance Notes:1. Tested in accordance with ASHRAE Standard 70-2006

"Method of Testing for Rating the Performance of Air Outlets and Inlets."

2. Air flow is in cfm.3. All pressures are in in. w.g.

4. Throw values are given in feet to terminal velocities of 150-100-50 fpm.

5. Throw data is based on supply air and room air at isothermal conditions.

6. NC values are based on room absorption of 10 dB re 10-12 Watts and one diffuser.

7. Blanks "--" indicate an NC level below 15.

Page 99: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

ver 2.15.11.13

UNIVERSIDAD NACIONAL DE TUMACO

Air Conditioning Proposal LG Electronics

LGE

AIR CONDITIONING PROPOSAL SHEET11/25/2016

76, Seongsan-dong, Changwon City, Gyeongnam, 641-731, Korea

Prepared by :

AIREG SAS

Page 100: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

ver 2.15.11.13

Project Name :UNIVERSIDAD NACIONAL SEDE TUMACO

1. Outdoor Units

2. Indoor Units

3. Pipes 4. Branch/Header/Common pipe

5. Accessories

Panel(1Way Cassette)

Description

32.8

Dia(Liq:Gas,inch)

1/4 : 1/2

Length(ft)

5/8 : 1+3/8

218.9

Quantity

ARNU48GTMA2 4

ARNU18GTTA2 24

ARNU24GTTA2 12

ARNU12GTRA2 2

ARNU24GTPA2

Ceiling Cassette - 4Way

Ceiling Cassette - 4Way

Ceiling Cassette - 4Way

7

Model Selection - Summary LG Electronics

Model Selection - Summary

QuantityModel Name Description

ARNU07GTUA2 5

ARUV240BTR4

ARUV500BTR4

Total 4

Model Name Quantity

1

60Hz/R410A/Cooling Only/Multi V IV/CS.America

60Hz/R410A/Cooling Only/Multi V IV/CS.America

60Hz/R410A/Cooling Only/Multi V IV/CS.America

ARUV140BTR4 1

1

1 60Hz/R410A/Cooling Only/Multi V IV/CS.AmericaARUV280BTR4

P0

Index Model Name

ARBLN01621

Total

16

Description

54

Ceiling Cassette - 1Way

Ceiling Cassette - 1Way

Ceiling Cassette - 1Way

41

3/4 : 1+3/8

3/4 : 1+5/8

36.1

IDU

IDU

Model Name

PT-UMC1

PT-UQC

PT-UUC

IDU 13

Standard Grill-4way Cassette(TN,TM,TP)Grille 4 way cassette (TR,TQ)

Quantity

13

Index

P13

P14

P12 23

P6 1/2 : 1+1/8 232.8 ARCNN21 3

P2 3/8 : 3/4 101.7 ARBLN07121 18

P7 5/8 : 1+1/8 50.9 ARCNN31 1

P1 3/8 : 5/8 412.2 ARBLN03321 15

P3 3/8 : 7/8 90.2 ARBLN14521 1

Page 101: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

ver 2.15.11.13

Project Name :UNIVERSIDAD NACIONAL SEDE TUMACO 11/25/2016

System No :1/4

1. Design conditions

2. Outdoor

3. Pipes 4. Branch/Header/Common pipe

#Notes : Correction factor conpensates Indoor unit Combination, Temperature, Pipe Length Effect etc.

The result can be slightly different from product data book due to simulation.

ARCNN21 1

5/8 : 1+1/8 16.4 ARCNN31 1

3/4 : 1+3/8 3.3

3/4 : 1+5/8 32.8

ARBLN03321 8

3/8 : 3/4 54.2 ARBLN07121 6

3/8 : 7/8 41.0 ARBLN14521 1

P14

Summer Winter

Max total over

load(kBtu/h

623.4(130%)

Indoors/Outdoor Ratio

1.05:1

Product charge(lb

s)

DB(°F)

44.64

Max indoor unit

Connectivity

Add. Ref. Amount(lb

s)

Cooling Heating Cooling Heating

ARUV500BTR4

P13

83.0 82.0

P3

P2

P1

P7

P6

478.1/468.3

Dia(Liq:Gas,inch)

Length(ft)Index

1/4 : 1/2 60.7

3/8 : 5/8 147.7

1/2 : 1+1/8 90.2

Model Name

P0

LG Electronics Model Selection - System(ODU)

Model Selection - UCRV-01

Outdoor Outdoor

64

WB(°F)

37.0

Rated Capa/Corrected Capa(kBtu/h)

DB(°F) WB(°F)

Rated Power Input/Corrected Power Input(kW)

Fluid Type / Concentration(

%)

-

39.0

39.68

37.8/31.5

Model Name Quantity

ARBLN01621 8

Page 102: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

ver 2.15.11.13

System No :1/4 11/25/2016

Warning! - Sum of IDU capacity exceeds the outdoor unit corrected capacity.Verify the outdoor unit capacity meets the block load.If there is no load diversity, upsize ODU or remove space load from the system.

Model Selection - Tree LG Electronics

Model Selection - UCRV-01

Page 103: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

ver 2.15.11.13

System No :1/4 11/25/2016

Warning! - Sum of IDU capacity exceeds the outdoor unit corrected capacity.Verify the outdoor unit capacity meets the block load.If there is no load diversity, upsize ODU or remove space load from the system.

Model Selection - Diagram LG Electronics

Model Selection - UCRV-01

Page 104: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

ver 2.15.11.13

Project Name :UNIVERSIDAD NACIONAL SEDE TUMACO 11/25/2016

System No :2/4

1. Design conditions

2. Outdoor

3. Pipes 4. Branch/Header/Common pipe

#Notes : Correction factor conpensates Indoor unit Combination, Temperature, Pipe Length Effect etc.

The result can be slightly different from product data book due to simulation.

39.0 37.0

LG Electronics Model Selection - System(ODU)

Model Selection - UCRV-02

Summer Winter

Outdoor Outdoor

Max total over

load(kBtu/h

Indoors/Outdoor Ratio

Product charge(lb

s)

Add. Ref. Amount(lb

s)

DB(°F) WB(°F) DB(°F) WB(°F)

83.0 82.0

Fluid Type / Concentration(

%)

ARUV280BTR4 56 429.4(160%) 1.03:1 24.25 27.31 -

Model NameMax indoor

unit Connectivity

Rated Capa/Corrected Capa(kBtu/h) Rated Power Input/Corrected Power Input(kW)

Cooling Heating Cooling Heating

267.6/264.5 19.4/16.0

IndexDia(Liq:Gas,inc

h)Length(ft) Model Name Quantity

P0 1/4 : 1/2 36.1 ARBLN01621 4

P1 3/8 : 5/8 157.5 ARBLN03321 4

P2 3/8 : 3/4 29.6 ARBLN07121 3

P3 3/8 : 7/8 31.2 ARCNN21 1

P6 1/2 : 1+1/8 54.1

P13 3/4 : 1+3/8 32.8

Page 105: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

ver 2.15.11.13

System No :2/4 11/25/2016

Warning! - Sum of IDU capacity exceeds the outdoor unit corrected capacity.Verify the outdoor unit capacity meets the block load.If there is no load diversity, upsize ODU or remove space load from the system.

LG Electronics Model Selection - Tree

Model Selection - UCRV-02

Page 106: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

ver 2.15.11.13

System No :2/4 11/25/2016

Warning! - Sum of IDU capacity exceeds the outdoor unit corrected capacity.Verify the outdoor unit capacity meets the block load.If there is no load diversity, upsize ODU or remove space load from the system.

LG Electronics Model Selection - Diagram

Model Selection - UCRV-02

Page 107: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

ver 2.15.11.13

Project Name :UNIVERSIDAD NACIONAL SEDE TUMACO 11/25/2016

System No :3/4

1. Design conditions

2. Outdoor

3. Pipes 4. Branch/Header/Common pipe

#Notes : Correction factor conpensates Indoor unit Combination, Temperature, Pipe Length Effect etc.

The result can be slightly different from product data book due to simulation.

39.0 37.0

LG Electronics Model Selection - System(ODU)

Model Selection - UCRV-03

Summer Winter

Outdoor Outdoor

Max total over

load(kBtu/h

Indoors/Outdoor Ratio

Product charge(lb

s)

Add. Ref. Amount(lb

s)

DB(°F) WB(°F) DB(°F) WB(°F)

83.0 82.0

Fluid Type / Concentration(

%)

ARUV140BTR4 35 268.2(200%) 1.16:1 11.02 14.85 -

Model NameMax indoor

unit Connectivity

Rated Capa/Corrected Capa(kBtu/h) Rated Power Input/Corrected Power Input(kW)

Cooling Heating Cooling Heating

133.8/143.7 9.9/8.8

IndexDia(Liq:Gas,inc

h)Length(ft) Model Name Quantity

P0 1/4 : 1/2 52.2 ARBLN01621 2

P1 3/8 : 5/8 53.2 ARBLN03321 1

P2 3/8 : 3/4 17.9 ARBLN07121 3

P6 1/2 : 1+1/8 72.1

Page 108: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

ver 2.15.11.13

System No :3/4 11/25/2016

Warning! - Sum of IDU capacity exceeds the outdoor unit corrected capacity.Verify the outdoor unit capacity meets the block load.If there is no load diversity, upsize ODU or remove space load from the system.

LG Electronics Model Selection - Tree

Model Selection - UCRV-03

Page 109: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

ver 2.15.11.13

System No :3/4 11/25/2016

Warning! - Sum of IDU capacity exceeds the outdoor unit corrected capacity.Verify the outdoor unit capacity meets the block load.If there is no load diversity, upsize ODU or remove space load from the system.

LG Electronics Model Selection - Diagram

Model Selection - UCRV-03

Page 110: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

ver 2.15.11.13

Project Name :UNIVERSIDAD NACIONAL SEDE TUMACO 11/25/2016

System No :4/4

1. Design conditions

2. Outdoor

3. Pipes 4. Branch/Header/Common pipe

#Notes : Correction factor conpensates Indoor unit Combination, Temperature, Pipe Length Effect etc.

The result can be slightly different from product data book due to simulation.

39.0 37.0

LG Electronics Model Selection - System(ODU)

Model Selection - UCRV-04

Summer Winter

Outdoor Outdoor

Max total over

load(kBtu/h

Indoors/Outdoor Ratio

Product charge(lb

s)

Add. Ref. Amount(lb

s)

DB(°F) WB(°F) DB(°F) WB(°F)

83.0 82.0

Fluid Type / Concentration(

%)

ARUV240BTR4 48 368.0(160%) 1.06:1 22.05 19.93 -

Model NameMax indoor

unit Connectivity

Rated Capa/Corrected Capa(kBtu/h) Rated Power Input/Corrected Power Input(kW)

Cooling Heating Cooling Heating

229.4/234.6 17.0/14.4

IndexDia(Liq:Gas,inc

h)Length(ft) Model Name Quantity

P0 1/4 : 1/2 69.9 ARBLN01621 2

P1 3/8 : 5/8 53.8 ARBLN03321 2

P3 3/8 : 7/8 18.0 ARBLN07121 6

P6 1/2 : 1+1/8 16.4 ARCNN21 1

P7 5/8 : 1+1/8 34.4

P12 5/8 : 1+3/8 23.0

Page 111: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

ver 2.15.11.13

System No :4/4 11/25/2016

Warning! - Sum of IDU capacity exceeds the outdoor unit corrected capacity.Verify the outdoor unit capacity meets the block load.If there is no load diversity, upsize ODU or remove space load from the system.

LG Electronics Model Selection - Tree

Model Selection - UCRV-04

Page 112: UNIVERSIDAD NACIONAL SEDE TUMACO DISEÑO Y ESTUDIOS ...contratacion.unal.edu.co/nal/2017/IP_Obra _Civil... · universidad nacional sede tumaco revisión 27/02/12 diseÑo y estudios

ver 2.15.11.13

System No :4/4 11/25/2016

Warning! - Sum of IDU capacity exceeds the outdoor unit corrected capacity.Verify the outdoor unit capacity meets the block load.If there is no load diversity, upsize ODU or remove space load from the system.

LG Electronics Model Selection - Diagram

Model Selection - UCRV-04